B U R - M O D S Y S T E M S<br />
INSTALLATION PARAMETERS<br />
SECTION 1.00<br />
INSULATION<br />
In all cases a minimum of 1 ⁄ 2"<br />
thick perlite or high density wood<br />
fiber board insulation will be<br />
installed as a buffering layer. Other<br />
insulations are acceptable for use<br />
within these systems provided the<br />
insulation manufacturer’s specifications<br />
<strong>and</strong> <strong>BITEC</strong>’s specifications<br />
are followed. See the General<br />
Requirements SECTION 6.02 of<br />
this manual.<br />
Insulation must be used with all<br />
systems unless its use has been<br />
waived by <strong>BITEC</strong>’s Technical<br />
Services Department.<br />
SECTION 2.00<br />
BASE SHEETS<br />
AND PLY SHEETS<br />
Unless otherwise specified all<br />
base <strong>and</strong> ply sheets will be<br />
installed using hot asphalt as per<br />
<strong>BITEC</strong>’s published requirements<br />
which determine the type of<br />
asphalt to be used, asphalt application<br />
rate, <strong>and</strong> asphalt application<br />
temperature. See the General<br />
Requirements SECTIONS 1.02,<br />
1.03 <strong>and</strong> 1.04 of this manual.<br />
Under no circumstances will any<br />
Type IV or Type VI Ply Sheet be<br />
mechanically attached. Under certain<br />
conditions, however, the G2<br />
base sheet called for in the schedule<br />
may be mechanically attached.<br />
Allowance for this must be preapproved<br />
by <strong>BITEC</strong>’s Technical<br />
Services Department. For parameters<br />
involving mechanically<br />
attaching G2 base sheets refer to<br />
SECTION 2.02, on pg.17 of this<br />
manual.<br />
According to The NRCA<br />
<strong>Roofing</strong> <strong>and</strong> Waterproofing<br />
Manual:<br />
“...plies shall be embedded<br />
into a fluid, continuous applica-<br />
tion of asphalt. The asphalt shall<br />
be applied in such a way that at<br />
no place will felt touch felt. All<br />
plies of felt shall be broomed into<br />
place as they are applied to aid<br />
in adhesion ...”<br />
SECTION 3.00<br />
CAP SHEET<br />
Cap sheet shall be installed as<br />
per specifications given in the<br />
General Requirements SECTIONS<br />
2.03 <strong>and</strong> 2.04, pgs.17-18 of this<br />
manual.<br />
SECTION 4.00<br />
SPECIFICATIONS<br />
AND DETAILS<br />
Primary consultation for this<br />
information shall come from this<br />
book, <strong>and</strong> The NRCA <strong>Roofing</strong> <strong>and</strong><br />
Waterproofing Manual.<br />
All applicable publications shall<br />
be consulted before work begins.<br />
Some details for BUR-MOD systems<br />
are included in the following<br />
section of this manual. These<br />
details are simply variations of the<br />
details used for modified bitumen<br />
systems.<br />
Typically, for BUR-MOD systems,<br />
all Modified <strong>Bitumen</strong> <strong>Details</strong><br />
may be adapted to be used with<br />
BUR-MOD Systems.<br />
This is generally accomplished<br />
by using the base <strong>and</strong>/or ply<br />
sheets in lieu of the base <strong>and</strong>/or<br />
interply membrane of the modified<br />
bitumen system.<br />
For any specific details not<br />
shown, contact <strong>BITEC</strong> Technical<br />
Services Dept. at (800) 535-8597.<br />
SECTION 5.00<br />
ACCEPTABLE<br />
BASE AND PLY SHEET<br />
Base sheet <strong>and</strong> ply sheet from<br />
the following companies are<br />
60<br />
acceptable for use within the<br />
<strong>BITEC</strong> Bur-Mod systems:<br />
1) <strong>BITEC</strong>, INC.<br />
2) TAMKO <strong>Roofing</strong> Prod., Inc.<br />
3) Black Warrior <strong>Roofing</strong>, Inc.<br />
4) Fields Corporation<br />
5) Johns Manville (Schuller)<br />
No other base or ply sheet shall<br />
be used other than those given<br />
above unless approval is granted<br />
from <strong>BITEC</strong>’s Technical Service<br />
Department.<br />
The above companies publish<br />
their compliance with st<strong>and</strong>ards for<br />
the products shown on the next<br />
page, Table 1.<br />
SECTION 6.00<br />
APPROVAL FOR USE<br />
OF BUR-MOD SYSTEMS<br />
AS A SUBSTITUTE FOR<br />
OUR STANDARD<br />
WARRANTY SYSTEMS<br />
Pre-approval by the Technical<br />
Services Department is necessary<br />
in order to obtain a warranty for<br />
these systems.<br />
All Warranty Requests must be<br />
submitted in a reasonable amount<br />
of time prior to the start of the project<br />
for pre-approval.<br />
As is always done with any<br />
extraordinary warranty scenario, a<br />
special warranty document is used.<br />
However, our st<strong>and</strong>ard Limited<br />
Insured <strong>Roofing</strong> Warranty is applicable<br />
for any of the following systems<br />
listed in Table 2, next page.<br />
SECTION 7.00<br />
SPECIFICATION<br />
NUMBERS<br />
Specification number format will<br />
remain virtually the same with the<br />
following changes shown in chart<br />
on the next page.