CATALOGUE TIME and MONITORING RELAYS - Hiquel
CATALOGUE TIME and MONITORING RELAYS - Hiquel
CATALOGUE TIME and MONITORING RELAYS - Hiquel
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
TCP-V/PCP-V<br />
overview<br />
detects phase failure or<br />
reduction of phase voltage<br />
DPCO output max. 6A<br />
normal or inverted function available<br />
constant measuring<br />
TCP-V U s=Un x 0.7<br />
PCP-V U s=Un x 0.7<br />
TCP-V-I U s=Un x 0.85<br />
will not trip with regenerated<br />
voltage present<br />
requires neutral connection<br />
(3-phase 4-wire)<br />
adjustable reaction timer 0.1 - 10s<br />
LED indicators for power supply,<br />
relay <strong>and</strong> reaction timer<br />
45mm DIN rail mount housing<br />
or 11pin plug in housing<br />
specification<br />
supply voltage variation nominal voltage +10% / -20%<br />
frequency range<br />
48-63Hz<br />
duty cycle<br />
100%<br />
reaction timer<br />
0,1 - 10s<br />
reset time<br />
< 100ms<br />
output relay specification max. 6A 230V~<br />
Ue/Ie AC-15<br />
120V/4A 240V/3A<br />
Ue/Ie DC-13<br />
24V/2A<br />
expected life time<br />
DPCO SPCO<br />
mechanical<br />
2x10<br />
electrical<br />
6<br />
resp. 1 x 10 7 operations<br />
1x10 5<br />
resp. 1 x 10 5 operations<br />
screws<br />
pozidrive 1<br />
screw tightening torque 0,6..0,8Nm<br />
operating conditions<br />
-20 to +60°C non condensing<br />
ordering information<br />
L1-N 100%<br />
0%<br />
100%<br />
L2-N<br />
0%<br />
L3-N<br />
100%<br />
0%<br />
TCP -V<br />
U<br />
L1-N 230V AC 3x230V/400V<br />
Us = Un x 0,7<br />
R<br />
0,1<br />
Time 10<br />
0,1 - 10s<br />
part no supply output sup. galv. Gehäusetypen<br />
iso*<br />
housing types<br />
TCP-V 3x440Vac 3x 250/440V~ 2,5VA DPCO<br />
yes<br />
no<br />
C<br />
TCP-V 3x400Vac 3x 230/400V~ 2,5VA DPCO<br />
yes<br />
yes<br />
C<br />
PCP-V 3x400Vac 3x 230/400V~ 2,5VA DPCO<br />
yes<br />
no<br />
G<br />
TCP-V 3x230Vac 3x 115/230V~ 2,5VA DPCO<br />
yes<br />
yes<br />
C<br />
TCP-V-I 3x440Vac 3x 250/440V~ 2,5VA DPCO<br />
yes<br />
no<br />
C<br />
TCP-V-I 3x400Vac 3x 230/400V~ 2,5VA DPCO<br />
yes<br />
no<br />
C<br />
TCP-V-I 3x230Vac 3x 115/230V~ 2,5VA DPCO<br />
yes<br />
no<br />
C<br />
* The measurement input<br />
is galvanically isolated from the power supply<br />
* EN 60947-5-1 VDE 0435<br />
Function<br />
HIQUEL 2009<br />
X01.00<br />
L1<br />
5<br />
L2<br />
L3<br />
6<br />
7<br />
L1<br />
Control relay active<br />
Control relay passive<br />
Contact closed<br />
Contact open<br />
Phase Failure<br />
N<br />
10<br />
HIGH QUALITY ELECTRONICS<br />
R<br />
L1-N 100%<br />
0%<br />
100%<br />
L2-N<br />
0%<br />
L3-N<br />
100%<br />
0%<br />
R<br />
Us=Unx0,7<br />
Us=Unx0,7<br />
t t t<br />
Us=Unx0,85<br />
Us=Unx0,85<br />
t t t<br />
L1<br />
5<br />
L1<br />
L2<br />
L2<br />
L3<br />
6<br />
7<br />
Us=Unx0,7<br />
Us=Unx0,85<br />
L3<br />
PCP -V<br />
U<br />
L1-N 230V AC<br />
N<br />
10<br />
TCP-V<br />
PCP-V<br />
normal function<br />
TCP-V-I<br />
invers function<br />
Phase failure relay 3-phase <strong>and</strong> neutral<br />
The TCP-V is a phase failure relay for monitoring 4-wire, 3-phase<br />
systems for phase failure or phase voltage reduction down to<br />
Vn x 0.7 or less. When the control relay detects all 3 phases within<br />
the correct range, the output relay R energises.<br />
At a loss of one phase (> 30% under nominal voltage) the reaction<br />
time t starts. At the end of time t the output relay R de-energises.<br />
Time t is adjustable between 0.1s <strong>and</strong> 10s, <strong>and</strong> is used to time out<br />
short transients which would otherwise cause nuisance tripping.<br />
The relay energises again, when phase L1, L2 <strong>and</strong> L3 return to the<br />
correct range.<br />
The TCP-V may be used for monitoring a 1-phase system, in<br />
which case L1, L2 & L3 must be connected together (see below).<br />
3x230V/400V<br />
Us = Un x 0,7<br />
Phase Failure<br />
1-phase connection 3-phase connection<br />
0,1<br />
Time 10<br />
0,1 - 10s<br />
R<br />
11<br />
1<br />
12<br />
4<br />
R R<br />
14<br />
3<br />
21<br />
11<br />
22<br />
8<br />
24<br />
9<br />
2<br />
3<br />
DIN<br />
11<br />
C US<br />
3 phase monitoring relay (phase to neutral measurement)<br />
2:17