01.02.2013 Views

CATALOGUE TIME and MONITORING RELAYS - Hiquel

CATALOGUE TIME and MONITORING RELAYS - Hiquel

CATALOGUE TIME and MONITORING RELAYS - Hiquel

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

TCL<br />

overview<br />

monitors one or two levels<br />

of conductive liquids<br />

DPCO output max. 6A<br />

programmable filling or emptying mode<br />

programmable sensitivity 250 Ohm - 100 kOhm<br />

or 50 kOhm - 1 MOhm<br />

LED indicators for power supply,<br />

relay <strong>and</strong> reaction timer<br />

45mm DIN rail mount housing or<br />

11pin plug in housing<br />

supply voltage variation<br />

frequency range<br />

duty cycle<br />

delay time<br />

reset time<br />

max measuring voltage<br />

max measuring current<br />

probes<br />

output relay specification<br />

Ue/Ie AC-15<br />

Ue/Ie DC-13<br />

expected life time<br />

mechanical<br />

electrical<br />

screws<br />

specification<br />

nominal voltage +10% / -20%<br />

48-63Hz<br />

100%<br />

1s (fixed)<br />

< 100ms<br />

± 5,3V<br />

~ 5mA<br />

cable length max. 100m<br />

max. 6A 230V~<br />

120V/4A 240V/3A<br />

24V/2A<br />

DPCO SPCO<br />

2x10 6<br />

resp. 1 x 10 7 operations<br />

resp. 1 x 10 5<br />

operations<br />

1x10 5<br />

pozidrive 1<br />

screw tightening torque 0,6..0,8Nm<br />

operating conditions -20 to +60°C non condensing<br />

ordering information<br />

Function<br />

1 level<br />

Single Point<br />

Sensing<br />

using 2 Sensors<br />

C<br />

S1<br />

S2<br />

HIQUEL 2009<br />

X01.00<br />

Level<br />

U<br />

S1<br />

emptying<br />

R 4<br />

filling<br />

R 5<br />

U<br />

1<br />

Max. S2<br />

Min. S1<br />

2<br />

emptying<br />

R 4<br />

filling<br />

5<br />

R<br />

Control relay active<br />

Control relay passive<br />

Contact closed<br />

Contact open<br />

C S1<br />

2 level<br />

Two Point<br />

Sensing<br />

using 3 Sensors<br />

HIGH QUALITY ELECTRONICS<br />

3<br />

CS1S2<br />

+<br />

~<br />

A2 A1<br />

-~<br />

2<br />

1 max. level<br />

2 min. level<br />

3 monitored level<br />

4 Output relay, emptying function<br />

5 Output relay, filling function<br />

Control relay to monitor the level of<br />

conductive liquids<br />

15<br />

3<br />

Supply = U = A1-A2<br />

16<br />

><br />

18<br />

The TCL controls the level of<br />

conductive liquids in a<br />

conductive or non-conductive<br />

container <strong>and</strong> works by<br />

passing a low voltage through<br />

the liquid from a suitable probe<br />

to an earth return which can<br />

either be the container or<br />

another probe.<br />

Single point sensing:<br />

The relay changes over each<br />

time the liquid contacts C <strong>and</strong><br />

S1.<br />

Two point sensing:<br />

The relay changes over each<br />

time the liquid contacts C, S1<br />

<strong>and</strong> S2.<br />

The relay resets when the<br />

liquid level returns<br />

below S1.<br />

The polarity of the sensor<br />

voltage is periodically reversed<br />

<strong>and</strong> is sufficiently low to avoid<br />

electrolytic action between the<br />

probes.<br />

Note:<br />

Do not make a connection<br />

between A2 <strong>and</strong> C when using<br />

TCL without galvanic isolation.<br />

(DC supplied versions)<br />

><br />

R R<br />

part no supply ouput sup. galv. Gehäusetypen<br />

iso*<br />

housing types<br />

TCL 230Vac<br />

230V~ 2,5VA<br />

DPCO<br />

yes<br />

-<br />

C<br />

TCL 115Vac<br />

115V~ 2,5VA<br />

DPCO<br />

yes<br />

-<br />

C<br />

TCL 24Vac<br />

24V~ 2,5VA<br />

DPCO<br />

yes<br />

-<br />

C<br />

TCL 24Vdc<br />

24V= 2W<br />

DPCO<br />

no<br />

-<br />

C<br />

PCL 230Vac<br />

230V~ 2,5VA<br />

DPCO<br />

yes<br />

-<br />

G<br />

PCL 115Vac<br />

115V~ 2,5VA<br />

DPCO<br />

yes<br />

-<br />

G<br />

PCL 24Vac<br />

24V~ 2,5VA<br />

DPCO<br />

yes<br />

-<br />

G<br />

PCL 24Vdc<br />

24V= 2W<br />

DPCO<br />

no<br />

-<br />

G<br />

* The measurement input is galvanically isolated from the power supply.<br />

* EN 60947-5-1 VDE 0435<br />

TCL<br />

U<br />

230VAC<br />

Level<br />

Func.<br />

Sens.<br />

R<br />

0<br />

50<br />

100%<br />

high<br />

low<br />

Level Control<br />

one<br />

level<br />

C S1S2<br />

two<br />

levels<br />

C S1<br />

filling<br />

emptying<br />

50K -1M<br />

250 -100K<br />

25<br />

26<br />

28<br />

2<br />

DIN<br />

11<br />

2:21<br />

liquid level control, 2 levels

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!