2.2.6 CONSTRUCTION SIZE 5 (<strong>VCB</strong> 400–460 TO –610)<br />

<strong>VCB</strong><br />

400-460<br />

Output motor side, at 400 V connecting voltage<br />

Recommended<br />

rated motor output<br />

Equipment continuous<br />

output<br />

Output current,<br />

effective<br />

Output voltage,<br />

effective<br />

1.2 / 1.5 for 60 s,<br />

Overload capacity -<br />

according to model<br />

P1 06/05 2-11<br />

<strong>VCB</strong><br />

400-570<br />

<strong>VCB</strong><br />

400-610<br />

P kW 250 315 355<br />

S kVA 318.7 395 422.6<br />

I A 460 570 610<br />

U V 3 x 0 ... mains voltage input<br />

1.2 for 60 s<br />

Protection short circuit / earth fault<br />

Rotary field frequency f Hz 0 ... 400, according to switching frequency<br />

Switching frequency f kHz 1 ... 4<br />

Connection bolt<br />

Input mains side<br />

- - M12<br />

Recommended<br />

wiring cross section<br />

A mm 2<br />

2 x 185 2 x 240<br />

Voltage U V 3 x 400 (-20%) ... 460 (+10%)<br />

Frequency f Hz 50 (-10%) ... 60 (+10%)<br />

Power factor cos φ - ~1 (Power factor of the fundamental)<br />

Efficiency (approx.) η % 98, at 2 kHz switching frequency<br />

Line fuses<br />

Mechanical<br />

- - external<br />

Dimensions WxHxD mm<br />

518x820x406 1)<br />

518x1095x406 2)<br />

518x1095x406<br />

Weight (approx.) m kg<br />

110 2)<br />

120 3)<br />

Protection class - - IP 20<br />

Installation type - - Vertical wall mounting<br />

Environmental conditions<br />

Dissipation, at<br />

2 kHz switching freq.<br />

P W 4840 5984 6399<br />

Min. air consumption Q m 3 /h 700 1) , 1200 2) 1200<br />

Coolant temperature Tn °C 0 ... 40, forced ventilation<br />

Storage temperature TL °C -25 ... +55<br />

Transport<br />

temperature<br />

TT °C -25 ... +70<br />

Relative humidity - % 15 ... 85, no condensation<br />

Power reduction<br />

see Chapter 3.3.1<br />

ΔP %<br />

120<br />

2.5%/K above 40 °C; Tmax=50 °C;<br />

5%/1000 m above 1000 m above sea level;<br />

hmax=4000m<br />

Options and accessories<br />

Line choke (u k=4%) - - external<br />

EMC filter - - external<br />

Brake chopper - - optional internal<br />

Digital control unit - - optional<br />

1) 2)<br />

overload capacity 1.2, overload capacity 1.5<br />

Internal fuses used<br />

Fuse for switching power supply 2 pcs. 1A6 / 500V super-quick-acting, 6.3 x 32 mm<br />

Fuse protection power supply cables and fan 5 pcs. 10A / 500V semi-time-lag,<br />

6.3 x 32 mm