Functional diagram<br />

<strong>INSTALLATION</strong> OF THE INDOOR UNIT<br />

2 3 4 5 6 7 8<br />

1<br />

R1T<br />

t ><br />

R3T<br />

t ><br />

H 2 O<br />

13<br />

R4T<br />

t ><br />

1 Outdoor unit 10 Shut-off valve water outlet<br />

2 Indoor unit<br />

with drain valve (field<br />

installation)<br />

3 Expansion vessel 11 Shut-off valve water inlet with<br />

4 Manometer<br />

drain valve (field installation)<br />

5 Air purge valve 12 Filter<br />

6 Pressure relief valve 13 Heat exchanger<br />

7 Backup heater R1T<br />

8 Pump<br />

R2T<br />

R3T<br />

Temperature sensors<br />

9 Flow switch<br />

R4T<br />

R2T<br />

t ><br />

12<br />

9<br />

10<br />

11<br />

Selecting an installation location<br />

The unit is to be wall mounted in an indoor location that meets the<br />

following requirements:<br />

■ The installation location is frost-free.<br />

■ The space around the unit is adequate for servicing. (See<br />

figure 2).<br />

■ The space around the unit allows for sufficient air circulation.<br />

■ There is a provision for condensate drain (only for EKHBX<br />

models with drain pan kit EKHBDP) and pressure relief valve<br />

blow-off.<br />

■ The installation surface is a flat and vertical non-combustible<br />

wall, capable of supporting the operation weight of the unit (see<br />

"Technical specifications" on page 43).<br />

■ There is no danger of fire due to leakage of inflammable gas.<br />

■ All piping lengths and distances have been taken into<br />

consideration.<br />

■<br />

■<br />

■<br />

■<br />

■<br />

■<br />

■<br />

■<br />

Requirement<br />

Maximum allowable refrigerant piping length between<br />

outdoor unit and indoor unit<br />

Minimum required refrigerant piping length between<br />

outdoor unit and indoor unit<br />

Maximum allowable height difference between<br />

outdoor unit and indoor unit<br />

Maximum allowable distance between the 3-way<br />

valve and the indoor unit (only for installations with<br />

domestic hot water tank).<br />

Maximum allowable distance between the domestic<br />

hot water tank and the indoor unit (only for<br />

installations with domestic hot water tank). The<br />

thermistor cable supplied with the domestic hot water<br />

tank is 12 m in length.<br />

Value<br />

246 ft<br />

(75 m)<br />

9.8 ft (a)<br />

(3 m)<br />

98.4 ft<br />

(30 m)<br />

9.8 ft<br />

(3 m)<br />

32.8 ft<br />

(10 m)<br />