[F] Option setup<br />

Pump operation<br />

The pump operation field setting apply to the pump operation logic<br />

only when DIP switch SS2-3 is OFF.<br />

When the pump operation function is disabled the pump will stop if<br />

the outdoor temperature is higher than the value set by [4-02] or if the<br />

outdoor temperature drops below the value set by [F-01]. When the<br />

pump operation is enabled, the pump operation is possible at all<br />

outdoor temperatures. Refer to "Pump operation configuration" on<br />

page 23.<br />

■ [F-00] Pump operation: specifies wether the pump operation<br />

function is enabled (1) or disabled (0).<br />

Space cooling permission<br />

■ [F-01] Space cooling permission temperature: defines the<br />

outdoor temperature below which space cooling is turned off.<br />

This function is only valid for EKHBX when space<br />

cooling is selected.<br />

Bottom plate heater control<br />

Applies only to installation with an outdoor unit ERLQ or in case the<br />

option bottom plate heater kit is installed.<br />

■ [F-02] Bottom plate heater ON temperature: defines the<br />

outdoor temperature below which the bottom plate heater will<br />

be activated by indoor unit in order to prevent ice build-up in<br />

the bottom plate of the outdoor unit at lower outdoor<br />

temperatures.<br />

■ [F-03] Bottom plate heater hysteresis: defines the<br />

temperature difference between bottom plate heater ON<br />

temperature and the bottom plate heater OFF temperature.<br />

Bottom plate heater<br />

ON<br />

OFF<br />

[F-02]<br />

[F-03]<br />

T A<br />

T A<br />

Outdoor temperature<br />

CAUTION<br />

The bottom plate heater is controlled via X14A. Make sure<br />

[F-04] is correctly set.<br />

Functionality of X14A<br />

■ [F-04] Functionality of X14A: specifies if the logic of X14A<br />

follows the output signal for the solar kit model (EKSOLHW)<br />

EKHBH/X_AA/AB (0) or if the logic of X14A follows the<br />

output for the bottom plate heater (1).<br />

NOTE<br />

Independent from field setting [F-04], the contact<br />

X3-X4 (EKRP1HB) follows the logic of the output<br />

signal for the solar kit model (EKSOLHW). See figure<br />

below for the schematic location of this contact.<br />

X1 X2 X3 X4<br />

X2M<br />

OFF ON<br />

SS1<br />

X1M<br />

YC Y1 Y2 Y3 Y4<br />

Installation manual<br />

34<br />

EKHBH/X054BA<br />

Indoor unit for air to water heat pump system<br />

4PW54216-1