6 Internal wiring<br />

Visually check the switch box on loose connections or damaged<br />

electrical components.<br />

7 Fixation<br />

Check that the unit is properly fixed, to avoid abnormal noises<br />

and vibrations when starting up the unit.<br />

8 Damaged equipment<br />

Check the inside of the unit on damaged components or<br />

squeezed pipes.<br />

9 Refrigerant leak<br />

Check the inside of the unit on refrigerant leakage. If there is a<br />

refrigerant leak, call your local dealer.<br />

10 Power supply voltage<br />

Check the power supply voltage on the local supply panel. The<br />

voltage must correspond to the voltage on the identification label<br />

of the unit.<br />

11 Air purge valve<br />

Make sure the air purge valve is open (at least 2 turns).<br />

12 Pressure relief valve<br />

Check if the backup heater is completely filled with water by<br />

operating the pressure relief valve. It should purge water instead<br />

of air.<br />

NOTE<br />

Operating the system with the backup heater not<br />

completely filled with water will damage the backup<br />

heater!<br />

13 Shut-off valves<br />

Make sure that the shut-off valves are correctly installed and<br />

fully open.<br />

NOTE<br />

Operating the system with closed valves will damage<br />

the pump!<br />

Powering up the indoor unit<br />

When power supply to the indoor unit is turned on, "88" is displayed<br />

on the user interface during its initialisation, which might take up to<br />

30 seconds. During this process the user interface cannot be<br />

operated.<br />

Setting the pump speed<br />

The pump speed can be selected on the pump (see "Main<br />

components" on page 10).<br />

The default setting is high speed (I). If the water flow in the system is<br />

too high (e.g., noise of running water in the installation) the speed<br />

can be set to medium speed (II) or low speed (III).<br />

The available external static pressure (ESP, expressed in psi (kPa)) in<br />

function of the water flow (gallons/min (l/min)) is shown in the graph<br />

below.<br />

ESP [psi]<br />

ESP [kPa]<br />

13<br />

12<br />

11<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

0<br />

4 6 8 10 12 14 16 18<br />

III<br />

[gallons/min]<br />

70<br />

65<br />

60<br />

55<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

0<br />

16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58<br />

[l/min]<br />

III<br />

II<br />

I<br />

I I II<br />

II<br />

Installation manual<br />

24<br />

EKHBH/X054BA<br />

Indoor unit for air to water heat pump system<br />