6 Internal wiring<br />
Visually check the switch box on loose connections or damaged<br />
electrical components.<br />
7 Fixation<br />
Check that the unit is properly fixed, to avoid abnormal noises<br />
and vibrations when starting up the unit.<br />
8 Damaged equipment<br />
Check the inside of the unit on damaged components or<br />
squeezed pipes.<br />
9 Refrigerant leak<br />
Check the inside of the unit on refrigerant leakage. If there is a<br />
refrigerant leak, call your local dealer.<br />
10 Power supply voltage<br />
Check the power supply voltage on the local supply panel. The<br />
voltage must correspond to the voltage on the identification label<br />
of the unit.<br />
11 Air purge valve<br />
Make sure the air purge valve is open (at least 2 turns).<br />
12 Pressure relief valve<br />
Check if the backup heater is completely filled with water by<br />
operating the pressure relief valve. It should purge water instead<br />
of air.<br />
NOTE<br />
Operating the system with the backup heater not<br />
completely filled with water will damage the backup<br />
heater!<br />
13 Shut-off valves<br />
Make sure that the shut-off valves are correctly installed and<br />
fully open.<br />
NOTE<br />
Operating the system with closed valves will damage<br />
the pump!<br />
Powering up the indoor unit<br />
When power supply to the indoor unit is turned on, "88" is displayed<br />
on the user interface during its initialisation, which might take up to<br />
30 seconds. During this process the user interface cannot be<br />
operated.<br />
Setting the pump speed<br />
The pump speed can be selected on the pump (see "Main<br />
components" on page 10).<br />
The default setting is high speed (I). If the water flow in the system is<br />
too high (e.g., noise of running water in the installation) the speed<br />
can be set to medium speed (II) or low speed (III).<br />
The available external static pressure (ESP, expressed in psi (kPa)) in<br />
function of the water flow (gallons/min (l/min)) is shown in the graph<br />
below.<br />
ESP [psi]<br />
ESP [kPa]<br />
13<br />
12<br />
11<br />
10<br />
9<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
4 6 8 10 12 14 16 18<br />
III<br />
[gallons/min]<br />
70<br />
65<br />
60<br />
55<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
15<br />
10<br />
5<br />
0<br />
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58<br />
[l/min]<br />
III<br />
II<br />
I<br />
I I II<br />
II<br />
Installation manual<br />
24<br />
EKHBH/X054BA<br />
Indoor unit for air to water heat pump system<br />
4PW54216-1