[A] Quiet mode<br />

This field setting allows to select the desired quiet mode. Two quiet<br />

modes are available: quiet mode A and quiet mode B.<br />

In quiet mode A, priority is given to the outdoor unit operating quietly<br />

under all circumstances. Fan and compressor speed (and thus<br />

performance) will be limited to a certain percentage of the speed at<br />

normal operation. In certain cases, this might result in reduced<br />

performance.<br />

In quiet mode B, quiet operation might be overridden when higher<br />

performance is required. In certain cases, this might result in less<br />

quiet operation of the outdoor unit to meet the requested<br />

performance.<br />

■ [A-00] Quiet mode type: defines whether quiet mode A (0) or<br />

quiet mode B (2) is selected.<br />

■ [A-01] Parameter 01: do not change this setting. Leave it set<br />

to its default value.<br />

NOTE<br />

Do not set other values than the ones mentioned.<br />

[C] Setup on EKRP1HB digital I/O PCB<br />

Solar priority mode<br />

■ [C-00] Solar priority mode setting: for information concerning<br />

the EKSOLHW solar kit, refer to the installation manual of<br />

that kit.<br />

Alarm output logic<br />

■ [C-01] Alarm output logic: defines the logic of the alarm<br />

output on the EKRP1HB digital I/O PCB.<br />

[C-01]=0, the alarm output will be powered when an alarm<br />

occurs (default).<br />

[C-01]=1, the alarm output will not be powered when an<br />

alarm occurs. This field setting allows for distinction between<br />

detection of an alarm and detection of a power failure to the<br />

unit.<br />

[C-01] Alarm No alarm<br />

No power supply<br />

to unit<br />

0 Closed output Open output Open output<br />

(default)<br />

1 Open output Closed output Open output<br />

Bivalent operation<br />

Applies only to installations with an auxiliary boiler (alternating<br />

operation, parallel connected). The purpose of this function is to<br />

determine —based on the outdoor temperature— which heating<br />

source can/will provide the space heating, either the <strong>Daikin</strong> indoor<br />

unit or an auxiliary boiler.<br />

The field setting "bivalent operation" apply only the indoor unit space<br />

heating operation and the permission signal for the auxiliary boiler.<br />

When the "bivalent operation" function is enabled, the indoor unit will<br />

stop automatically in space heating operation when the outdoor<br />

temperature drops below "bivalent ON temperature" and the<br />

permission signal for the auxiliary boiler becomes active.<br />

When the bivalent operation function is disabled, the space heating<br />

by indoor unit is possible at all outdoor temperatures (see operation<br />

ranges) and permission signal for auxiliary boiler is always<br />

disactivated.<br />

■ [C-02] Bivalent operation status: defines whether bivalent<br />

operation is enabled (1) or disabled (0).<br />

■ [C-03] Bivalent ON temperature: defines the outdoor<br />

temperature below which the permission signal for the<br />

auxiliary boiler will be active (closed, KCR on EKRP1HB) and<br />

space heating by indoor unit will be stopped.<br />

■ [C-04] Bivalent hysteresis: defines the temperature difference<br />

between bivalent ON temperature and bivalent OFF<br />

temperature.<br />

Permission signal X1–X2 (EKRP1HB)<br />

closed<br />

[C-04]<br />

open<br />

T [C-03] A<br />

T A<br />

Outdoor temperature<br />

CAUTION<br />

Make sure to observe all rules mentioned in<br />

application 5 when bivalent operation function is<br />

enabled.<br />

<strong>Daikin</strong> shall not be held liable for any damage<br />

resulting from failure to observe this rule.<br />

■<br />

■<br />

■<br />

In case the outdoor unit is single phase, the<br />

combination of setting [4-03]=0/2 with bivalent<br />

operation at low outdoor temperature can result<br />

in domestic hot water shortage.<br />

The bivalent operation function has no impact on<br />

the domestic water heating mode. The domestic<br />

hot water is still and only heated by the indoor<br />

unit.<br />

The permission signal for the auxiliary boiler is<br />

located on the EKRP1HB (digital I/O PCB).<br />

When it is activated, the contact X1, X2 is closed<br />

and open when it is disactivated. See figure for<br />

the schematic location of this contact.<br />

X1 X2 X3 X4<br />

X2M<br />

X1M<br />

YC Y1 Y2 Y3 Y4<br />

OFF ON<br />

SS1<br />

Installation manual<br />

32<br />

EKHBH/X054BA<br />

Indoor unit for air to water heat pump system<br />

4PW54216-1