ENGLISHThe low pressure switch opens then closes again: Verify the points mentioned in the "lowpressure switch tripped" section above.Intermittent contact on machine control unit: Repair or replace the faulty electrical part. Checkthe Temperature control unitMake sure the equipment is not too large for the facilities.THE EQUIPMENT DOES NOT SHUT DOWN:Verify that the humidistat functions properly, repairing or replacing it if necessary.Compressor contactor contacts are stuck together: Check that the coil is functioning properlyand that the contacts are not burned.The pressure of the intake duct is too low: Check the refrigerant charge of the equipment forleaks, to solve this problem please refer to the refrigerant charge section. Check that there are noobstructions in the cooling circuit,, dehydrating filter, expansion valve etc. and replace ifnecessary.Verify that the equipment is powerful enough for the existing thermal conditions.EXCESSIVE NOISE:The fastening screws of the compressor or fan are loose: Tighten all the fastening elements.Check the compressor oil level.The compressor produces internal bumping noises: Check that the noise does not come fromany fluid leak from overheating (see section of refrigerant charge).18. R<strong>EF</strong>RIGERANT CHARGECOOLER AXIAL FANHigh pressure valve.Low pressure valve.For the procedures described below, we recommend you contact a professional specialised inheating and air conditioning units.© TALLERES DEL <strong>AGUA</strong> S.L. 2008. TODOS LOS DERECHOS RESERVADOS. DOCUMENTO CONFIDENCIAL Y EN PROPIEDAD.Page 45 of 50

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!