3-polige klemmenstrook<br />

Klem Functie<br />

1 Netwerk data line A<br />

2 Netwerk data line B<br />

3 Scherm<br />

Parameters<br />

Para- Beschrijving Fabr. Para- Beschrijving Fabr.<br />

meter<br />

inst meter<br />

inst<br />

15.01 Module ID code 401 15.30 Load option defaults OFF<br />

15.02 Firmware version 15.31 Save option parameters OFF<br />

15.03 Node address 0 15.32 Request to re-initialise OFF<br />

15.06 Diagnostics: messages per second 0 15.33 Restore parameters from option module OFF<br />

15.07 Network loss trip 0 15.34 Initialise drive reference selectors OFF<br />

15.10 Subnet ID 15.35 Option module serial number -<br />

15.11 Domain ID length 0 15.36 Transmit service pin message OFF<br />

15.12 Domain ID byte 1 0 15.37 Winl active OFF<br />

15.13 Domain ID byte 2 0 15.38 Unconfigure option module 0<br />

15.14 Domain ID byte 3 0 15.39 Default configuration property storage 0<br />

15.15 Domain ID byte 4 0<br />

15.16 Domain ID byte 5 0 15.50 SM-LON error codes 0<br />

15.17 Domain ID byte 6 0 15.51 Minor firmware version<br />

Error codes<br />

De errorcode is weergegeven in #15.50<br />

Kleur:<br />

Zacht groen<br />

<strong>SK</strong> menu 15<br />

SM-LON optiemodule<br />

Errorcode<br />

Fout Beschrijving<br />

0 Geen fout gedetecteerd Indicatie dat de trip niet werd veroorzaakt door SM-LON, mogelijk via externe<br />

communicatie kanalen.<br />

58 Incorect non-volatile storage At least one configuration property was incorrectly formatted or corrupt.<br />

Configuration property defaults are downloaded<br />

61 Invalid configuration parameters This trip will occur if the SM-LON option module is installed in a Unidrive SP<br />

configured in regen mode<br />

65 Network loss<br />

70 No valid fieldbus data available No valid fieldbus data available in the module to download to the drive. The<br />

user may not have saved any data or the data save may not have completed<br />

successfully<br />

74 Overtemperatuur in de optiemodule Temperatuur in de optiemodule > 82 °C, <strong>Commander</strong> <strong>SK</strong> geeft trip 74<br />

99 Interne software fout<br />

<strong>SK</strong> handleiding, versie 7 pagina 138 van 154<br />

SM-Optiemodule frontaanzicht<br />

Dipschakelaar<br />

out<br />

in<br />

1 2 3<br />

A B S<br />

2 stuks 56 Ohm<br />

ballast weerstanden<br />

W<br />

S<br />

Wink LED<br />

Service LED