22.03.2013 Views

DGC Brushless Excitation - Emerson Process Management

DGC Brushless Excitation - Emerson Process Management

DGC Brushless Excitation - Emerson Process Management

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>DGC</strong> <strong>Brushless</strong> <strong>Excitation</strong><br />

System Description<br />

The Voltage Feedback Signal is modified by a multiplication factor. The multiplication factor is<br />

equal to 1.0 when there is no VAR loading on the generator, thus the value of the feedback signal is<br />

unchanged.<br />

As VAR loading increases in the VARS OUT direction, the compensator multiplication factor rises<br />

above unity, causing the perceived generator voltage to be higher than actual. As VAR loading<br />

increases in the VARS IN direction, the compensator multiplication factor drops below unity,<br />

causing the perceived generator voltage to be lower than actual.<br />

The compensation factor is applied proportionally based on the percentage of VAR loading and the<br />

Compensation setpoint.<br />

4.3.e Line Compensation<br />

Line Compensation is used when the voltage at the end of a long transmission-line is of concern.<br />

The compensation is used to overcome the voltage drop that occurs as the line is loaded with real<br />

(resistive) and reactive current.<br />

For Reactive load (MVAR) on the line, the effect of the compensation is to make the apparent<br />

terminal voltage lower as the reactive loading of the line increases in the VARS OUT direction. This<br />

causes the <strong>DGC</strong> to increase excitation, boosting the voltage at the end of the line.<br />

For Real load (MW) on the line, the effect of the compensation is to make the apparent terminal<br />

voltage lower as the megawatt loading of the line increases. This causes the <strong>DGC</strong> to increase<br />

excitation, boosting the voltage at the end of the line.<br />

Each of these calculations develops a compensation factor that modifies the feedback signal.<br />

The multiplication factor is equal to 1.0 when there is no load on the generator, thus the value of the<br />

feedback signal is unchanged. As loading of the line increases with real load or VARS Out reactive<br />

load, the compensator multiplication factor drops below unity causing the perceived generator<br />

voltage to be lower than actual. The compensation factor is applied proportionally based on the<br />

percentage of VAR loading and the compensation setpoints.<br />

4.4 Controller Characteristics<br />

The controller is a Proportional plus Integral controller with transient gain reduction (TGR) via rate<br />

feedback. The setpoint to the controller is the voltage adjuster value (va_volts_value) and the<br />

measured variable is the compensated feedback from the generator PT’s (fb_comp). The rate<br />

feedback signal, the limiter outputs, and the power system stabilizer output (if installed) contribute to<br />

the difference signal. The difference (auto_error) is applied to the proportional and integral sections<br />

of the controller. The proportional (p_output) and intregral (i_output) outputs are summed to<br />

produce the PID controller output (ctlr_out).<br />

If the Regulator Mode is OFF or TEST then the controller output is held at zero.<br />

4.4.a Proportional Action<br />

The Proportional Action section of the controller multiplies the error signal by a gain factor. The<br />

value of the gain factor can be dynamically adjusted as a function of the megawatt load on the<br />

generator, using a gain (gain_curve) vs. load curve (load_curve). Proportional control alone cannot<br />

reduce the error signal to zero. This is not usually an issue unless setpoint matching is needed. In<br />

most cases, the setpoint (va_volts_value) is adjusted by the operator to get the desired output<br />

without knowledge of the setpoint value. The fact that the controller error is not zero is of no<br />

concern to the operator.<br />

© <strong>Emerson</strong> <strong>Process</strong> <strong>Management</strong> Power & Water Solutions. - 19 -<br />

PWS_005075 [3]

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!