22.03.2013 Views

DGC Brushless Excitation - Emerson Process Management

DGC Brushless Excitation - Emerson Process Management

DGC Brushless Excitation - Emerson Process Management

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DGC</strong> <strong>Brushless</strong> <strong>Excitation</strong><br />

System Description<br />

When the integrator output value reaches the maximum allowable value, the MXL is said to have<br />

“timed out”. This is the equivalent of the rotor temperature having reached its thermal limit.<br />

The MXL is a proportional plus integral controller whose output is from the main controller error<br />

signal. The setpoint to the MXL controller is the calculated maximum allowable field current. The<br />

feedback is the measured exciter field current. The output of the controller is a function of the<br />

difference between actual measured field current and the setpoint, and the duration of the transient.<br />

The MXL controller setpoint is modified during the thermal integration phase. It starts out set to the<br />

ceiling current and stays there until reaching a thermal integration setpoint, which is configurable<br />

from 100% of the maximum allowable value down to 0%. Upon reaching the corner, the controller<br />

setpoint ramps from the instantaneous current setpoint towards the maximum allowable sustained<br />

setpoint. As the setpoint drops below the actual value of field current, the controller output will<br />

begin to act. As the setpoint continues to ramp lower, the control action will increase gradually,<br />

ensuring a smooth transition into the limiting condition.<br />

If the field current rises above the ceiling current, the time delay action of the integrator is bypassed<br />

and the limiter is activated instantly.<br />

The MXL calculation generates two alarms. The MXL TIMING alarm is generated when the<br />

integrator starts. The MXL LIMITING is generated when the limiter is actively limiting excitation.<br />

Both alarms have hysteresis to prevent relay chatter.<br />

4.5.b Minimum <strong>Excitation</strong> Limiter<br />

The purpose of the Minimum <strong>Excitation</strong> Limiter (MEL) is twofold. It protects the generator end-iron<br />

from overheating when operating extremely under-excited and it prevents loss of synchronization<br />

which may result from insufficient excitation. These conditions occur when the generator is<br />

operating with excessive "VARs In". Both of these conditions are avoided by preventing the<br />

regulator output from going too low.<br />

The MEL is a proportional plus integral controller. Its output is added to the main controller's error<br />

signal calculation. The output of the MEL controller is clamped at 0 until VARs fall below the<br />

minimum allowable value. As VARs fall below the setpoint, the MEL controller output adds to the<br />

main controller error signal. The MEL setpoint is expressed in VARs and is calculated from a<br />

setpoint curve as a function of MW, described below. The measured variables are VARs and MW<br />

from the Machine PTs and CT.<br />

The setpoint is a value of minimum allowable VARs for a given megawatt load, which becomes<br />

more restrictive as the megawatt load increases. The setpoint is defined in a four-segment "XY"<br />

curve, where X is in Megawatts and Y is in VARs. The data points for the curve are selected such<br />

that the curve approximates the bottom segment of the generator capability curve. The values for<br />

the curve are unit specific and are extracted from the particular unit's capability curve. There are no<br />

default values.<br />

An additional limit can be generated by enabling the steady state stability limit calculation. This is<br />

calculated continuously when enabled. The MEL limit will be the most conservative of the two limit<br />

sources.<br />

The setpoint is modified by the Damping Factor such that the faster the excitation current<br />

decreases; the more the setpoint value is raised to account for the lag of the generator response to<br />

a change in excitation.<br />

© <strong>Emerson</strong> <strong>Process</strong> <strong>Management</strong> Power & Water Solutions. - 21 -<br />

PWS_005075 [3]

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!