Sigma<br />
2.06 Top outlet Flue Connection<br />
Three different connection are available from top of the <strong>boiler</strong>, using accessories as reported on fig. 30a, b e c and<br />
on examples a next page.<br />
1 Top outlet horizontal 2 Top outlet two 3<br />
2.06.01 Examples of top fl ue connection<br />
1 Example of concentric flue Ø 100<br />
with appliance bend use<br />
Fig. 31<br />
Note • Bear in mind that the two concentric<br />
pipes must slope downwards away from the<br />
<strong>boiler</strong> at a rate of about 3 mm/m to avoid<br />
rainwater entering the <strong>boiler</strong>. Outside, the<br />
pipes should protrude from the <strong>wall</strong> between<br />
10 and 60 mm.<br />
Warning • Back exit with coaxial bend is<br />
not possible<br />
concentric fl ue<br />
Vertical Connection, concentric bend<br />
and two pipe separator can be<br />
supplied on request.<br />
2 Example of direct roof flue outlet<br />
and <strong>wall</strong> air inlet with 2 pipe system<br />
Fig. 32<br />
pipe system<br />
Fig. 30a Fig. 30b Fig. 30c<br />
Warning • Back exit with Air/Flue T separator<br />
is not possible<br />
Top outlet vertical<br />
concentric fl ue<br />
3 Example of concentric flue Ø 100<br />
with vertical outlet flue use.<br />
Fig. 33<br />
Fig. 30