<strong>Combiner</strong> <strong>Boxes</strong> Defined<br />

<strong>Combiner</strong> boxes are used in solar installations to combine<br />

the inputs from multiple strings of solar panels into one<br />

output circuit. If viewed on a one-line diagram, combiner<br />

boxes would look like a “reverse-fed panelboard.” Meaning<br />

that instead of one feeder being broken into multiple branch<br />

circuits, the combiner takes multiple branch feeds from<br />

solar strings and groups them into one output.<br />

An "array" may be one PV panel or many in series, and may<br />

range from a single 12 volt panel up to multi panel high<br />

voltage arrays <strong>for</strong> grid tie systems. <strong>Solar</strong> PV Grid tied<br />

systems are typically 600 volts DC.<br />

String <strong>Combiner</strong>s, often referred to as source combiners,<br />

are located closest to the “strings” of solar panels. Since<br />

each string of PV panels are connected in series, the<br />

maximum current potential tends to be less than 15A per<br />

string. At <strong>Eaton</strong> we utilize individual fuse holders capable<br />

of accepting up to a 30A fuse. There are normally between 4<br />

and 12 strings connected to each combiner box. They may<br />

be grouped together using copper bus which is tied to a set<br />

of outgoing terminals.<br />

Combination String <strong>Combiner</strong><br />

In most solar installations it is advisable that a load break<br />

DC switch be included in order to isolate the individual<br />

string fuses <strong>for</strong> safe removal. At <strong>Eaton</strong>, we have combined<br />

our DC Disconnect along with our individual string inputs<br />

into a CSA Approved Combination String <strong>Combiner</strong>.<br />

Array combiners provide the next level of connection. An<br />

array combiner is made up of larger incoming connection<br />

points (100A-200A fuse blocks or DC breakers) and allows<br />

<strong>for</strong> the grouping of multiple string combiner outputs into a<br />

single set of outgoing terminals. You will normally only<br />

find array combiners on a large projects above 100kW and<br />

they are often provided as part of the inverter assembly<br />

although it is not uncommon to see multiple array<br />

combiners used on a large scale project.<br />

Smart <strong>Combiner</strong>s<br />

With income generation tied to <strong>Solar</strong> PV production it is not<br />

uncommon <strong>for</strong> owners to demand that per<strong>for</strong>mance<br />

monitoring be included. At <strong>Eaton</strong> we offer a scalable string<br />

monitoring solution that will allow <strong>for</strong> monitoring up to 15<br />

strings in a single combiner box. <strong>Eaton</strong>’s string monitoring<br />

package is capable of providing antitheft control and solar<br />

PV analysis (DC V,A and W metering). Modbus<br />

communication is standard and may include a smart energy<br />

management box with built in web sever.<br />

Combination and Non-combination<br />

String <strong>Combiner</strong>s<br />

<strong>Solar</strong> <strong>Photovoltaic</strong> installations<br />

Features<br />

• Suitable <strong>for</strong> NEC article 690 applications to UL 1741<br />

• CSA certified to C22.2 No. 107.1 and assembled in Ontario<br />

• Range 60, 100, 200Ampere 600VDC, single pole safety<br />

switch available as fusible or non fusible main disconnect,<br />

with 4 to 24 string circuit, 30Ampere, 600VDC, finger-safe<br />

fuse holders<br />

• Continuous duty rated<br />

• Main Disconnect load break rated.<br />

• Main fuse is isolated when switch is in OFF position.<br />

• Class R fuse clips standard <strong>for</strong> the main disconnect and<br />

midget class finger-safe fuse holders <strong>for</strong> the string circuits.<br />

Fuses not included.<br />

• Main disconnect is single pole and suitable <strong>for</strong> switching one<br />

circuit<br />

• Multi-position isolated negative ground<br />

• Short circuit withstand rating 10kA @600VDC<br />

• Standard offering type 12/3R enclosure electrostatic coated<br />

painted steel ASA 61 grey (Optional 4X stainless)<br />

• Highly visible, electrical shock warning label <strong>for</strong> line and<br />

load terminals mounted on front door of switch.<br />

• Highly visible ON / OFF marking on enclosure.<br />

• Operation temperature: -30ºC to +50ºC<br />

• Multi-position equipment ground and separate single<br />

conductor lay in lug <strong>for</strong> continuous ground #4 –14 awg.<br />

PA08323011K www.eatoncanada.ca/solar 2