COMPRESSORS<br />

HANDBOOK<br />

Chapter<br />

RUNNING DATA AND COMPRESSOR CHECKING PROCEDURES<br />

7.4.2 Standard version RSIR - RSCR EM Series with PTC starting device<br />

(Refer to the RSIR e RSCR electric diagrams represented on Figure 10, page 24)<br />

Verify with a voltmeter the presence of the correct voltage on the “L” and “N” terminals of the<br />

PTC starting device. If there is insufficient voltage, the thermostat is defective due to open contacts,<br />

connections, or an interruption in the cables.<br />

Disconnect the other electrical components if present (motor fan, gear motor, etc.), disconnect<br />

the voltage to the circuit at the supply line, and carry out the following operations and checks:<br />

1. Check the continuity on the terminals L3 of PTC starting device. If continuity lack,s the thermostat<br />

must be replaced due to open contacts.<br />

2. Take off the PTC starting device from the hermetic terminal.<br />

3. If there is a run capacitor (RSCR version) disconnect it.<br />

4. Take off the protector from the PTC starting device and check between points 1 and 3. If there<br />

is no continuity, be sure that the protector has no open contacts due to its trip. In this case,<br />

repeat the check after about 10 minutes. Otherwise, the protector is defective due to open contacts.<br />

5. Check the electric motor according to the procedure described in par.7.5.1.<br />

6. Check the ohmic resistance of the stator run and start windings according to the procedure<br />

described in par.7.5.2.<br />

7. On the PTC starting device check between the two fastons N and 2, the ohmic resistance of<br />

the PTC pill which must be 8÷16 for the 230V model and 2÷4 for the 115V model, at<br />

the ambient temperature of 25 °C. (CAUTION: the ohmic resistance values measured with a<br />

normal tester can be out of the indicated by as much as 25% ÷ 30%).<br />

8. If there is a run capacitor (RSCR version), check it according to the procedure described in<br />

section 7.5.3.<br />

If from all the above checks no problem was found, there is no capillary clogging and the system<br />

does not yet run correctly, replace the compressor.<br />

7.4.3 Standard version RSIR NB - NE - NT - T Series with electromagnetic<br />

current relay<br />

(Refer to the RSIR electric diagram represented in Figure 11, page 25)<br />

PLEASE NOTE: The contacts of the starting relay are normally open.<br />

Verify with a voltmeter the presence of the correct voltage on terminals “1” of relay and “3” of<br />

protector. If there is insufficient voltage, the thermostat is defective due to open contacts, connections,<br />

or there is an interruption in the cables.<br />

Disconnect the other electric components if present (motor fan, gear motor, etc.), disconnect the<br />

voltage to the circuit at the supply line, and carry out the following operations and checks:<br />

1. Check the continuity between the points “1” - “3” of protector: If there is no continuity, be<br />

sure that the protector has no open contacts due to its trip. In this case, repeat the check after<br />

about 10 minutes.<br />

2. Take off the start relay from the hermetic terminal and keeping it in the same vertical position,<br />

(do not incline or overturn) carry out the following continuity checks.<br />

3. Between the terminals “1” and “S” on the relay: If there no continuity the relay is faulty due<br />

to closed contacts.<br />

Doc. Code Emission Revision Date Page<br />

MP01E 2000-04 0 20-02 88 - 98