NRO/CON/WT/533<br />

13. Tentative Equipment layout in electrical premises <strong>with</strong> tentative<br />

dimensions of all panels.<br />

14. List <strong>and</strong> capacity of emergency loads <strong>and</strong> their feeding arrangement.<br />

15. Automation system configuration <strong>with</strong> list <strong>and</strong> details of hardware.<br />

Details about numbers & locations of RI/O panels & count of Inputs &<br />

outputs of various types considered. I/O count of each type should<br />

distinctly specify the I/O count + spare I/O count + chassis capacity of<br />

additional I/O.<br />

16. Details & Scheme of Illumination system <strong>and</strong> Emergency lighting.<br />

17. Details & BOM of Electrics related to Yard Machines, <strong>Wagon</strong> <strong>Tippler</strong> &<br />

<strong>Side</strong> <strong>Arm</strong> <strong>Charger</strong>, Ventilation <strong>and</strong> Air conditioning system etc.<br />

18. List of commissioning spares.<br />

19. List of spares <strong>for</strong> 2 years normal operation.<br />

20. List of insurance spares.<br />

21. List of special tools, tackles, instruments <strong>and</strong> calibration equipment &<br />

devices.<br />

22. List of deviations, if any, from Technical <strong>Specification</strong> & G.T.S.<br />

23. List of exclusions.<br />

24. Duly filled in questionnaire.<br />

25. Reference list of similar jobs.<br />

26. Time bar chart indicating various activities starting from date of<br />

placement of order till commissioning.<br />

27. Any other details which may be felt necessary.<br />

(b) Basic Engineering drawings (Electrical)<br />

1. List of drawings (Basic Engg /Detailed Engg/ Reference) <strong>and</strong> drawing<br />

numbering system along <strong>with</strong> schedule of submission.<br />

2. Single line diagrams of MCCs /Control Panels, PDBs, MLDBs, LDBs,<br />

SLDBs, Main fire detection <strong>and</strong> alarm panel etc. <strong>with</strong> rating of<br />

components, cable sizes <strong>and</strong> details of protection <strong>and</strong> metering etc.<br />

3. HT & LT Motor <strong>and</strong> component list including field mounted electrics<br />

4. HT <strong>and</strong> LT Motor data sheets as per enclosed <strong>for</strong>mat.<br />

5. Type-II Co-ordination chart as per IS: 13947-1993 <strong>for</strong> MPCB/ MCCB,<br />

Contactor <strong>and</strong> Overload relay.<br />

6. Schematic drawing of different feeders, control, alarm, indications,<br />

interlocking <strong>and</strong> other schematics.<br />

7. Shop/Unit wise Maximum Dem<strong>and</strong> calculations.<br />

8. Relay settings <strong>with</strong> calculations <strong>for</strong> total network to ensure proper coordination.<br />

9. Busbars sizing calculation <strong>with</strong> respect to temperature rise & short<br />

circuit <strong>with</strong>st<strong>and</strong> capacity.<br />

10. Design Calculations <strong>for</strong> selection of main equipment such as<br />

trans<strong>for</strong>mers drive motors, AC drives, bus bars, cables, batteries etc.<br />

11. Typical schemes of DOL, RDOL feeders indicating inputs & outputs<br />

applicable to the various feeders indicated in SLDs.<br />

12. Power <strong>and</strong> regulation schemes of AC drives.<br />

13. Calculation <strong>for</strong> temperature rise of busbars.<br />

14. Layout of substations, electrical rooms <strong>and</strong> control rooms including<br />

ventilation <strong>and</strong> air-conditioning rooms, h<strong>and</strong>ling facilities. The layout<br />

drawings indicating cable trench, wall openings, conduit inserts, plate<br />

inserts, Minimum clearances from electrical panels <strong>for</strong> installation of<br />

panels, cable trays, conduits <strong>for</strong> concealed wiring etc.<br />

EPI – New Delhi Volume-2B, Rev.0 Page 28 of 63