Performance Tests<br />

Performance test for a F.D. <strong>Fan</strong> in the <strong>TLT</strong><br />

workshop with reduced speed, driven by diesel<br />

engine.<br />

Seite 82<br />

volume flow: 304.3 m 3 /s<br />

pressure increase: 4,454 Pa<br />

temperature: 40 °C<br />

shaft power: 1,509 kW<br />

efficiency: 88.1 %<br />

control: combined hydraulic<br />

coupling, inlet vane<br />

control<br />

year of delivery: 1996<br />

© <strong>TLT</strong>-<strong>Turbo</strong> <strong>GmbH</strong><br />