15.08.2013 Views

ECOi 2 Way Installation Manual - Panasonic

ECOi 2 Way Installation Manual - Panasonic

ECOi 2 Way Installation Manual - Panasonic

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

1-13. Example of Tubing Size Selection and Refrigerant Charge Amount<br />

Additional refrigerant charging<br />

Based on the values in Tables 1-3, 4, 5, 7, 10-1 and 10-2, use the liquid tubing size and length, and calculate the amount of additional<br />

refrigerant charge using the formula below.<br />

Required additional<br />

refrigerant charge (oz)<br />

Example:<br />

CAUTION<br />

Outdoor unit<br />

96 type 96 type<br />

B<br />

A<br />

LA<br />

● Example of each tubing length<br />

= Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit<br />

+ 3.93 × (a) + 2.78 × (b) + 1.99 × (c) + 1.38 × (d) + 0.602 × (e) + 0.279 × (f)<br />

(a) : Liquid tubing Total length of ø7/8" (ft.) (d) : Liquid tubing Total length of ø1/2" (ft.)<br />

(b) : Liquid tubing Total length of ø3/4" (ft.) (e) : Liquid tubing Total length of ø3/8" (ft.)<br />

(c) : Liquid tubing Total length of ø5/8" (ft.) ( f ) : Liquid tubing Total length of ø1/4" (ft.)<br />

● Charging procedure<br />

Be sure to charge with R410A refrigerant in liquid form.<br />

1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be in the “fully<br />

closed” position.<br />

2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant<br />

from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.<br />

However if only one outdoor unit is installed, a balance tube is not used. Therefore, leave the valves fully closed.)<br />

Charge with R410A refrigerant in liquid form.<br />

With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from<br />

backing up.<br />

● After charging is completed, turn all valves to the “fully open” position.<br />

● Replace the tubing covers as they were before.<br />

1. R410A additional charging absolutely must<br />

be done through liquid charging.<br />

2. The R410A refrigerant cylinder has a gray<br />

base color, and the top part is pink.<br />

3. The R410A refrigerant cylinder includes a<br />

siphon tube. Check that the siphon tube is<br />

present. (This is indicated on the label at the<br />

top of the cylinder.)<br />

4. Due to differences in the refrigerant, pressure,<br />

and refrigerant oil involved in installation,<br />

it is not possible in some cases to use<br />

the same tools for R22 and for R410A.<br />

LB LC<br />

1 2 3 4<br />

48 type 48 type 48 type 36 type<br />

Main tubing Distribution joint tubing<br />

LA = 131 ft. Outdoor side Indoor side<br />

LB = 16 ft. A = 7 ft. 1 = 98 ft.<br />

LC = 16 ft. B = 7 ft.<br />

14<br />

2 = 16 ft.<br />

3 = 16 ft.<br />

4 = 65 ft.<br />

Balance tube<br />

Use a flathead screwdriver and<br />

open by turning the part with the<br />

screw groove to the right,<br />

from “–” to “|”.<br />

Liquid tube<br />

Use a hex wrench (width 5/32 inch)<br />

and turn to the left to open.<br />

Gas tube<br />

Use a flathead screwdriver and<br />

open by turning the part with the<br />

screw groove to the right,<br />

from “–” to “|”.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!