The electrician's system: univers N - Hager
The electrician's system: univers N - Hager
The electrician's system: univers N - Hager
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Maintenance and assembly<br />
<strong>univers</strong> N<br />
In order to correctly fit and assemble the kits, please consult the<br />
user instructions which are included in delivery<br />
<strong>The</strong> maintenance specifications for <strong>univers</strong> (see below), must be<br />
followed (in accordance with VDE 0100 Part 610)<br />
Maintenance specification (according to VDE 0100 Part 610)<br />
- Visual inspection of covers and encasements for damage,<br />
which impact on the IP rating of the product<br />
- Visual inspection of terminals<br />
- Test of the terminals in the main circuit, and re tightening of<br />
torques if necessary (as outlined in the busbar terminal table)<br />
- Functional test of switchgear, e.g. earth fault protection switch<br />
- Functional test of display functions of analogue measuring<br />
devices<br />
- Checking of the setting values on the operational devices e.g.<br />
MCBs, as per the switch documentation<br />
- Visual inspection for damage of individual wires<br />
- Visual inspection of the individual devices for shape or colour<br />
changes which may have occurred from thermal effects<br />
- Removal / correction of any identified faults (e.g. through replacement<br />
of faulty parts)<br />
Univers N<br />
System<br />
275