Maintenance and assembly<br />

<strong>univers</strong> N<br />

In order to correctly fit and assemble the kits, please consult the<br />

user instructions which are included in delivery<br />

<strong>The</strong> maintenance specifications for <strong>univers</strong> (see below), must be<br />

followed (in accordance with VDE 0100 Part 610)<br />

Maintenance specification (according to VDE 0100 Part 610)<br />

- Visual inspection of covers and encasements for damage,<br />

which impact on the IP rating of the product<br />

- Visual inspection of terminals<br />

- Test of the terminals in the main circuit, and re tightening of<br />

torques if necessary (as outlined in the busbar terminal table)<br />

- Functional test of switchgear, e.g. earth fault protection switch<br />

- Functional test of display functions of analogue measuring<br />

devices<br />

- Checking of the setting values on the operational devices e.g.<br />

MCBs, as per the switch documentation<br />

- Visual inspection for damage of individual wires<br />

- Visual inspection of the individual devices for shape or colour<br />

changes which may have occurred from thermal effects<br />

- Removal / correction of any identified faults (e.g. through replacement<br />

of faulty parts)<br />

Univers N<br />

System<br />