Earthing conductor connection <strong>univers</strong> N<br />

for enclosure housing and carrier rails<br />

TT-System (Principle Diagram)<br />

L1<br />

L2<br />

L3<br />

N<br />

In case of fault:<br />

mit R B ≈ 3 Ω<br />

R A ≈ 20 Ω<br />

I F is small and doesn't bring the fuse to trip within 0.2s to 0.5s<br />

RB<br />

RA<br />

IF<br />

Tripping condition:<br />

R A · I a ≤ U L<br />

with<br />

R A = Earthing resistance of chassis in Ω<br />

I a = Current in A, which makes the protection device disconnect<br />

U L = maximum continuous allowable touch voltage:<br />

U L ~ = 50 V, U L – = 120 V from DIN VDE 0100 part 200<br />

<strong>The</strong>refore the earth fault switch with breaking sensitivity up to<br />

max 500mA is fitted. With a "small" residual current, it is sufficient<br />

to use the 10mm 2 copper wire cable (included) and connect<br />

the carrier rails with the metal rail connector.<br />

TN-System (Principle Diagram)<br />

L1<br />

In case of fault:<br />

PEN<br />

L2<br />

L3<br />

N<br />

Protective earthing:<br />

Earthing:<br />

PE<br />

IF<br />

IF<br />

I F –> ∞<br />

with R –> 0<br />

I F –> ∞<br />

RB<br />

RA<br />

Nullung<br />

RA<br />

Erdung<br />

Tripping condition:<br />

Z S · I a ≤ U 0<br />

with<br />

Z S = Surge impedance of the wire loop in Ω<br />

I a = Current in A, which causes the automatic tripping<br />

U 0 = Nominal Voltage against earthed currents in V<br />

It is necessary to lay out the earth protected current accordingly<br />

with the continuous current. <strong>The</strong>refore the 10mm 2 and 16mm 2<br />

copper wire cable must be used to earth the carrier rails for a<br />

nominal current of 250A. This gives a earth protected current<br />

width of 25mm 2 . For 400A the width for earth protection is<br />

50mm 2 , and 630A is 75mm 2 (values according to DIN VDE 0660<br />

part 500). Corresponding wires are offered in the <strong>univers</strong> range<br />

276