The electrician's system: univers N - Hager
The electrician's system: univers N - Hager
The electrician's system: univers N - Hager
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Earthing conductor connection <strong>univers</strong> N<br />
for enclosure housing and carrier rails<br />
Classification of minimum cross section of separately laid,<br />
mechanical unprotected PE wire to the corresponding outer<br />
wire cross sections.<br />
Note: when using uninsulated wire (PE) no plastic insulation can<br />
be touched.<br />
Table 6<br />
NHgL Fuse<br />
PVC insulated<br />
outer wire<br />
Smallest related protective wire cross section from copper<br />
(mechanical unprotected, lay separately as single circuit)<br />
Copper PVC insulated insulated like<br />
outer wires<br />
uninsulated<br />
wire used<br />
uninsulated<br />
I N [A] S [mm 2 ] S [mm 2 ] S [mm 2 ] S [mm 2 ] S [mm 2 ]<br />
16 1.5 1.5 25<br />
20 2.5 2.5 25<br />
25 4 4 25<br />
35 6 6 25<br />
50 10 10 25<br />
63 16 16 25<br />
80 25 16 25<br />
100 35 16 25<br />
125 50 25 25<br />
160 70 35 25<br />
200 95 20.3 (25) 47.5 18.3 (25) 25<br />
250 120 26.6 (35) 60 23.9 (25) 25<br />
250 150 26.6 (35) 75 23.9 (25) 25<br />
315 185 32.8 (35) 92.5 29.5 (35) 2 x 25<br />
355 240 39.9 (50) 120 35.9 (50) 2 x 25<br />
400 300 43.8 (50) 150 39.4 (50) 2 x 25<br />
500 400 59.4 (70) 200 53.4 (70) 3 x 25<br />
630 500 78.2 (95) 200 70.3 (70) 3 x 25<br />
1) 2) 3) 4)<br />
1) PVC insulated wire (30°C) Group 2 (DIN VDE 0100 T. 523);<br />
Classification of gL fuses<br />
2) Characteristics for PVC insulated PE according to DIN VDE<br />
0100 T. 540/11.91 and rounding up to the next possible cross<br />
section (values in brackets)<br />
3) Minimum values for protective wire with same insulation material<br />
as outer wires according to table 4, VDE 0660 T. 500<br />
4) Characteristics for uninsulated mechanical unprotected copper<br />
wire according to DIN VDE 0100 T.540/11.91 and rounding up<br />
(values in brackets)<br />
Comment: for the determination of PE cross section either see<br />
Table 6 (values as per 3)<br />
or the calculation when t = 5s, K = 159<br />
(see values as per 4)<br />
<strong>The</strong>reby one of the installation regulations for adjusted earthing<br />
can be kept; the copper wires from the <strong>univers</strong> range are to be<br />
used<br />
Univers N<br />
System<br />
Use of DIN Rails as earthing conductor - busbar<br />
According to DIN VDE 0611 T.3/11.89 Paragraph 3.1.1 approved<br />
rails, (including DIN rails complying with DIN EN 50 022) may be<br />
used as protective earth conductor busbars, as long as the<br />
values of thermal short circuit and thermal current rating, as outlined<br />
in the table, are not exceeded.<br />
Exception<br />
Steel earth conductor busbars may not be used as PEN wires or<br />
N wires. <strong>The</strong>refore there is no values given in the table for max<br />
allowable thermal rated current for PEN function.<br />
Our steel device carrier rails according to DIN EN 50 022<br />
DIN Rails according<br />
to DIN EN 50 022<br />
- Steel<br />
<strong>The</strong>rmal short circuit<br />
capacity circuit current<br />
Max thermal short<br />
according to a E Cu 1 second / kA<br />
wire with cross<br />
section<br />
Installation is only possible for PE function and not for PEN<br />
or N function<br />
35 mm x 7.5 mm 16 1.92<br />
35 mm x 15 mm 50 6<br />
277