TABLE 14<br />

Manifold Pressure Settings at all Altitudes<br />

Unit<br />

Input<br />

070<br />

090<br />

110<br />

135<br />

<strong>Gas</strong><br />

Manifold<br />

Pressure in.wg.<br />

0−4500 ft.<br />

Manifold<br />

Pressure in.wg.<br />

4501−7500 ft. 1<br />

Supply Line<br />

Manifold<br />

7501 − 10,000 ft. 2 in. w.g.<br />

Pressure in.wg. Pressure<br />

Low Fire High Fire Low Fire High Fire Low Fire High Fire Min Max<br />

Natural 1.7 3.5 1.6 3.4 1.7 3.5 4.5 13.0<br />

LP/propane 3 4.9 10.0 4.9 10.0 4.9 10.0 11.0 13.0<br />

Natural 1.7 3.5 1.5 3.2 1.7 3.5 4.5 13.0<br />

LP/propane 3 4.9 10.0 4.9 10.0 4.9 10.0 11.0 13.0<br />

Natural 1.7 3.5 1.5 3.2 1.7 3.5 4.5 13.0<br />

LP/propane 3 4.9 10.0 4.9 10.0 4.9 10.0 11.0 13.0<br />

Natural 1.7 3.5 1.5 2.8 1.7 3.5 4.5 13.0<br />

LP/propane 3 4.9 10.0 4.9 10.0 4.9 10.0 11.0 13.0<br />

1 This is the only permissible derate for these units.<br />

2 Natural gas high altitude orifice kit required.<br />

3 A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion<br />

procedure.<br />

NOTE − Units may be installed at altitudes up to 4500 ft. above sea level without modifications.<br />

Unit<br />

Input<br />

070<br />

TABLE 15<br />

Pressure Switch and <strong>Gas</strong> Conversion Kits at all Altitudes<br />

High Altitude Pressure Switch Kit<br />

High Altitude<br />

Natural <strong>Gas</strong> Kit<br />

LP/Propane <strong>Gas</strong> Kit<br />

LP/Propane to<br />

Natural Kit<br />

0 − 4500 ft. 4501 − 7500 ft. 7501 − 10,000 ft. 7501 − 10,000 ft. 0 − 7500 ft 7501 − 10,000 ft. 0 − 7500 ft.Min<br />

91W53<br />

73W35<br />

090 91W53 73W35<br />

No Change<br />

110 91W53 73W35<br />

135 73W33 73W34<br />

73W37 77W07 77W11 77W09<br />

NOTE − A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion<br />

procedure.<br />

Page 34