EQUIPMENT IN CONFINED SPACE<br />

ALL AIR FROM OUTSIDE<br />

(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)<br />

CHIMNEY OR<br />

GAS VENT<br />

VENTILATION LOUVERS<br />

(Each end of attic)<br />

FURNACE<br />

OUTLET<br />

AIR<br />

WATER<br />

HEATER<br />

VENTILATION<br />

LOUVERS<br />

(For unheated crawl space)<br />

INLET<br />

AIR<br />

NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645<br />

mm 2 ) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.<br />

FIGURE 4<br />

CHIMNEY<br />

OR GAS<br />

VENT<br />

EQUIPMENT IN CONFINED SPACE<br />

ALL AIR FROM OUTSIDE<br />

(All Air Through Ventilated Attic)<br />

VENTILATION LOUVERS<br />

(Each end of attic)<br />

CHIMNEY<br />

OR GAS<br />

VENT<br />

WATER<br />

HEATER<br />

EQUIPMENT IN<br />

CONFINED SPACE<br />

ALL AIR FROM<br />

OUTSIDE<br />

OUTLET<br />

AIR<br />

OUTLET AIR<br />

FURNACE<br />

INLET AIR<br />

(Ends 12 in.<br />

above bottom)<br />

FURNACE<br />

INLET AIR<br />

WATER<br />

HEATER<br />

NOTE−The inlet and outlet air openings shall each have a<br />

free area of at least one square inch (645 mm 2 ) per 4,000<br />

Btu (1.17 kW) per hour of the total input rating of all equipment<br />

in the enclosure.<br />

FIGURE 5<br />

NOTE − Each air duct opening shall have a free area of at least one<br />

square inch (645 mm 2 ) per 2,000 Btu (.59 kW) per hour of the total<br />

input rating of all equipment in the enclosure. If the equipment room<br />

is located against an outside wall and the air openings communicate<br />

directly with the outdoors, each opening shall have a free area<br />

of at least one square inch (645 mm 2 ) per 4,000 Btu (1.17 kW) per<br />

hour of the total input rating of all other equipment in the enclosure.<br />

FIGURE 6<br />

Page 8