EQUIPMENT IN CONFINED SPACE<br />
ALL AIR FROM OUTSIDE<br />
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)<br />
CHIMNEY OR<br />
GAS VENT<br />
VENTILATION LOUVERS<br />
(Each end of attic)<br />
FURNACE<br />
OUTLET<br />
AIR<br />
WATER<br />
HEATER<br />
VENTILATION<br />
LOUVERS<br />
(For unheated crawl space)<br />
INLET<br />
AIR<br />
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645<br />
mm 2 ) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.<br />
FIGURE 4<br />
CHIMNEY<br />
OR GAS<br />
VENT<br />
EQUIPMENT IN CONFINED SPACE<br />
ALL AIR FROM OUTSIDE<br />
(All Air Through Ventilated Attic)<br />
VENTILATION LOUVERS<br />
(Each end of attic)<br />
CHIMNEY<br />
OR GAS<br />
VENT<br />
WATER<br />
HEATER<br />
EQUIPMENT IN<br />
CONFINED SPACE<br />
ALL AIR FROM<br />
OUTSIDE<br />
OUTLET<br />
AIR<br />
OUTLET AIR<br />
FURNACE<br />
INLET AIR<br />
(Ends 12 in.<br />
above bottom)<br />
FURNACE<br />
INLET AIR<br />
WATER<br />
HEATER<br />
NOTE−The inlet and outlet air openings shall each have a<br />
free area of at least one square inch (645 mm 2 ) per 4,000<br />
Btu (1.17 kW) per hour of the total input rating of all equipment<br />
in the enclosure.<br />
FIGURE 5<br />
NOTE − Each air duct opening shall have a free area of at least one<br />
square inch (645 mm 2 ) per 2,000 Btu (.59 kW) per hour of the total<br />
input rating of all equipment in the enclosure. If the equipment room<br />
is located against an outside wall and the air openings communicate<br />
directly with the outdoors, each opening shall have a free area<br />
of at least one square inch (645 mm 2 ) per 4,000 Btu (1.17 kW) per<br />
hour of the total input rating of all other equipment in the enclosure.<br />
FIGURE 6<br />
Page 8