2. General<br />
2.1 Application / Inst<strong>all</strong>ation<br />
The Aqualift F <strong>Pumpstation</strong> is designed to automatic<strong>all</strong>y<br />
pump wastewater (with or without sewage collected below<br />
the outgoing sewer level) up to the sewer level so that it may<br />
flow with gravity out of the building and into a septic system<br />
/ public sewer piping. This system is only for use with wastewater<br />
draining from single and multi-family homes, commercial<br />
buildings, hotels, restaurants, hospitals, schools or<br />
similar buildings. In circumstances where the interruption of<br />
wastewater is not <strong>all</strong>owed or desired, a twin pump system<br />
(<strong>Pumpstation</strong> Aqualift F <strong>Duo</strong>) is required for inst<strong>all</strong>ation.<br />
The <strong>KESSEL</strong> <strong>Pumpstation</strong> Aqualift F is designed for outdoor<br />
underground inst<strong>all</strong>ation. Pumps are equipped with macerating<br />
blades which cut <strong>all</strong> soft objects into sm<strong>all</strong>er pumpable<br />
pieces. Due to the cutting blades, outlet pipes of DN 40<br />
or larger may be connected to the outlet of the <strong>Pumpstation</strong><br />
Aqualift F. Objects. The system is designed to handle a continuous<br />
inflow of wastewater up to 40 deg C (104 deg F).<br />
Options for the <strong>KESSEL</strong> <strong>Pumpstation</strong> Aqualift F include:<br />
• Single (1 pump) or Twin (2 pumps)<br />
• Pumps available with various power ratings<br />
• In <strong>KESSEL</strong> 800 or 1000mm diameter Inspection Chamber<br />
• Inst<strong>all</strong>ation depths from 1.5 to 5 meters.<br />
The pump support bases, closure valve, backflow prevention<br />
flap, outlet pressure pipe and float switches have already<br />
been inst<strong>all</strong>ed in the base of the chamber. The pump(s), additional<br />
chamber sections and the electrical control unit are<br />
shipped separately with the system. The pumps, depending<br />
on their size, are shipped either in the chamber upper section<br />
or on a separate p<strong>all</strong>et. The pumps are to be inst<strong>all</strong>ed<br />
only after the complete chamber has been completely assembled<br />
and inst<strong>all</strong>ed. In order to prevent the build up of dangerous<br />
gases in the chamber which can cause an explosion<br />
risk, the system must be ventilated appropriately.<br />
2.2 Aqualift F description<br />
The <strong>KESSEL</strong> <strong>Pumpstation</strong> Aqualift F in single or twin pump<br />
variations is comprised of the following systems.<br />
1. Single or double sewage pumps with cutting assembly<br />
2. <strong>KESSEL</strong> Inspection Chamber 800 or 1000<br />
(mm diameter)<br />
3. Curve pump support base<br />
4. Closure valve for each pump<br />
5. Backflow prevention flap<br />
6. Pressure pipe outlet connection PN 10 from<br />
PEHD DN 50 (Outside Diameter – 63 mm or DN 80<br />
(Outside Diameter – 90 mm)<br />
7. Connection for ventilation pipe (DN 100)<br />
8. Connection for power / control cables (DN 100)<br />
9. Connection for inlet DN 100/150<br />
10. Float switch<br />
11. Electrical control unit (See Chapter 8)<br />
8<br />
7<br />
9<br />
2<br />
4<br />
6<br />
5<br />
1<br />
3<br />
10<br />
Illustration shows <strong>KESSEL</strong> <strong>Pumpstation</strong> Aqualift F<br />
twin pumping unit<br />
6