Trident Model <strong>PD765</strong> Universal Input Meter<br />

<strong>Instruction</strong> <strong>Manual</strong><br />

Program the Sensor Break Output Value (SEbr)<br />

The sensor break value corresponds to the output signal generated<br />

when the meter detects a sensor break for thermocouple and RTD inputs.<br />

For example if there is an open thermocouple, the meter displays the<br />

message “open” and the analog output goes to the programmed sensor<br />

break value (e.g. 3.00 mA).<br />

The sensor break value can be programmed from 0.00 to 23.99.<br />

The typical output signal range is 1.00 to 23.00 mA (e.g. If sensor break<br />

value is programmed to 0.00, the actual output will not be greater than<br />

1.00 mA).<br />

Aout<br />

scal<br />

Press Enter to Accept Setting<br />

Press Up to Set Digit Value<br />

Press Right to Select Next Digit<br />

Press Menu to Exit at any Time<br />

sEbr<br />

03.00<br />

Program<br />

Menu<br />

Set Sensor<br />

Break Value<br />

Analog Output when Display is Out of Range<br />

The analog output reflects the display out of range conditions as follows:<br />

Input Condition Display Analog Output<br />

Underrange Flashing -1999 3.00 mA<br />

Overrange Flashing 9999 21.00 mA<br />

Open TC or RTD Flashing open Sensor break value<br />

42