Trident Model <strong>PD765</strong> Universal Input Meter<br />
<strong>Instruction</strong> <strong>Manual</strong><br />
Program the Sensor Break Output Value (SEbr)<br />
The sensor break value corresponds to the output signal generated<br />
when the meter detects a sensor break for thermocouple and RTD inputs.<br />
For example if there is an open thermocouple, the meter displays the<br />
message “open” and the analog output goes to the programmed sensor<br />
break value (e.g. 3.00 mA).<br />
The sensor break value can be programmed from 0.00 to 23.99.<br />
The typical output signal range is 1.00 to 23.00 mA (e.g. If sensor break<br />
value is programmed to 0.00, the actual output will not be greater than<br />
1.00 mA).<br />
Aout<br />
scal<br />
Press Enter to Accept Setting<br />
Press Up to Set Digit Value<br />
Press Right to Select Next Digit<br />
Press Menu to Exit at any Time<br />
sEbr<br />
03.00<br />
Program<br />
Menu<br />
Set Sensor<br />
Break Value<br />
Analog Output when Display is Out of Range<br />
The analog output reflects the display out of range conditions as follows:<br />
Input Condition Display Analog Output<br />
Underrange Flashing -1999 3.00 mA<br />
Overrange Flashing 9999 21.00 mA<br />
Open TC or RTD Flashing open Sensor break value<br />
42