<strong>Installation</strong><br />
WARNING: Shock Hazard<br />
Ensure there is only one Neutral-to-Ground Bond in the system. The<br />
<strong>FLEXpower</strong> <strong>ONE</strong> comes with a Neutral-to-Ground Bond installed. If a Neutralto-Ground<br />
bond exists elsewhere in the system (e.g., in the main panel, or a<br />
generator), the Neutral-to-Ground Bond in the <strong>FLEXpower</strong> <strong>ONE</strong> AC Enclosure<br />
will need to be removed. See Figure 18. Check local code for specific<br />
requirements.<br />
AC Enclosure<br />
Factory-installed<br />
Neutral-To-Ground<br />
Bond<br />
The factory-installed<br />
Neutral-to-Ground Bond<br />
must be removed if<br />
another Neutral-to-<br />
Ground Bond exists<br />
elsewhere in the<br />
configuration.<br />
Internal components shown may vary from model to model.<br />
Factory wiring is not shown.<br />
See Table 5 on page 32 for recommended<br />
conductor sizes and torque requirements.<br />
Figure 18<br />
AC OUT Connections<br />
32 900-0095-01-00 Rev A