Operation<br />

De-energize/Shutdown<br />

WARNING: Lethal Voltage<br />

Review the system configuration to identify all possible sources of energy.<br />

Ensure ALL sources of power are disconnected before performing any<br />

installation or maintenance on this equipment. Confirm that the terminals are<br />

de-energized using a validated voltmeter (rated for a minimum 1000 Vac and<br />

1000 Vdc) to verify the de-energized condition.<br />

WARNING: Burn Hazard<br />

Internal parts can become hot during operation. Do not remove the cover<br />

during operation or touch any internal parts. Be sure to allow them sufficient<br />

time to cool down before attempting to perform any maintenance.<br />

2<br />

1. Open the PV Breakers. 1<br />

2. Open the AC Breakers. 2<br />

A<br />

3. Open the DC Breaker for the Battery.<br />

4. Using a digital volt-meter, verify 0 Vdc on the<br />

Battery terminals of the Inverter<br />

(i.e., place voltmeter leads on and in<br />

Figure 34 on page 47).<br />

5. Using a digital volt-meter, verify 0 Vdc on the<br />

PV terminal<br />

(i.e., place voltmeter leads on and<br />

in Figure 34 on page 47).<br />

6. Using a digital volt-meter, verify 0 Vac on the<br />

AC Breakers<br />

(i.e., Place voltmeter leads on 6+ and 6– in<br />

Figure 34 on page 47).<br />

1<br />

3<br />

A<br />

Outlets are model-dependent.<br />

120 V systems will have a 120V outlet,<br />

230 V <strong>Systems</strong> will have a 230 V outlet.<br />

Figure 33<br />

Shutdown Procedures<br />

46 900-0095-01-00 Rev A