3. Installation<br />

Note: Be<strong>for</strong>e actioning any installation observe the 'Safety in<strong>for</strong>mation' in Section 1.<br />

To meet its specified accuracy and per<strong>for</strong>mance it is essential that the following installation<br />

guidelines are followed carefully. For steam applications sound steam engineering practices<br />

should be followed, including the use of separators. The installation must con<strong>for</strong>m to all<br />

relevant construction and electrical codes.<br />

There are three parts to the installation of the <strong>TVA</strong> flowmeter <strong>with</strong> WirelessHART TM :<br />

3.1 WirelessHART TM commissioning (Device based).<br />

3.2 HART TM gateway installation - Page 14.<br />

3.3 Mechanical installation - Page 18.<br />

It is advised that the device based HART TM configuration is carried out on a workbench<br />

be<strong>for</strong>e the flowmeter is installed into a pipeline (mechanical installation).<br />

3.1 Device based WirelessHART TM commissioning<br />

Quick start commissioning guide<br />

For commissioning, the device can be powered by the TEG10 or a standard dc supply, wired<br />

to the internal green power connector (located inside the enclosure).<br />

The device’s parameters are modified using a HART TM user configuration tool connected<br />

to the maintenance port located inside the enclosure. When communications have been<br />

established the device automatically enters the commissioning mode.<br />

During commission mode:<br />

- MODBUS communication to the flowmeter will stop.<br />

- The device will not update the wireless gateway <strong>with</strong> the current steam flow data.<br />

- If power is being supplied via the internal green power connector, the flowmeter will<br />

remain switched off (i.e. the front panel display will not illuminate).<br />

- If power is being supplied via the TEG10, the flowmeter will power up and will continue to<br />

update the total flow internally. It will not transmit the current total flow wirelessly.<br />

The device will automatically enter the run mode, 60 seconds after the configuration tool has<br />

been disconnected or has been exited. The gateway will be updated <strong>with</strong> the current flow<br />

data and parameters.<br />

Equipment required:<br />

- HART TM configuration tool: Communicator or PC / PDA / Smart phone, DD based host and<br />

a HART TM modem (drivers to be installed).<br />

- <strong>Spirax</strong> DDL software (Device Description Language) ~ obtained from <strong>Spirax</strong> <strong>Sarco</strong> http://<br />

www.spiraxsarco.com/<br />

- Commissioning supply: 5 - 12 Vdc, 20 mAmax (Class II Safety Extra Low Voltage).<br />

- WirelessHART TM Gateway.<br />

10<br />