20.04.2014 Views

TVA Flowmeter for Saturated Steam Service with ... - Spirax Sarco

TVA Flowmeter for Saturated Steam Service with ... - Spirax Sarco

TVA Flowmeter for Saturated Steam Service with ... - Spirax Sarco

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

3378553/1<br />

IM-P337-62<br />

MI Issue 1<br />

<strong>TVA</strong> <strong>Flowmeter</strong> <strong>for</strong> <strong>Saturated</strong> <strong>Steam</strong> <strong>Service</strong><br />

<strong>with</strong> WirelessHart TM Option<br />

Installation and Maintenance Instructions<br />

1. Safety in<strong>for</strong>mation<br />

2. General<br />

product in<strong>for</strong>mation<br />

3. Installation<br />

4. Commissioning<br />

5. Operation<br />

6. Maintenance<br />

7. Spare parts<br />

8. Fault finding<br />

9. Technical data<br />

10. Setting table<br />

© Copyright 2012<br />

IM-P337-62 MI Issue 1 1<br />

Printed in the UK


2<br />

IM-P337-62 MI Issue 1


Safe operation of this unit can only be guaranteed if it is properly installed,<br />

commissioned and maintained by a qualified person (see Section 1.11) in compliance<br />

<strong>with</strong> the operating instructions. General installation and safety instructions <strong>for</strong><br />

pipeline and plant construction, as well as the proper use of tools and safety<br />

equipment must also be complied <strong>with</strong>.<br />

Manufacturer:-<br />

<strong>Spirax</strong>-<strong>Sarco</strong> Limited<br />

Charlton House<br />

Charlton Kings<br />

Cheltenham<br />

Glos<br />

GL53 8ER<br />

The product is designed and constructed to <strong>with</strong>stand the <strong>for</strong>ces encountered<br />

during normal use. Use of the product <strong>for</strong> any other purpose, or failure to install the<br />

product in accordance <strong>with</strong> these Installation and Maintenance Instructions, could<br />

cause damage to the product, will invalidate the marking, and may cause injury or<br />

fatality to personnel.<br />

EMC directive<br />

The product complies <strong>with</strong> the Electromagnetic Compatibility Directive 2004 / 108 / EC.<br />

A technical file <strong>with</strong> a reference number of 'UK Supply <strong>TVA</strong> flowmeter' supports the<br />

<strong>Spirax</strong> <strong>Sarco</strong> claim that the product complies <strong>with</strong> the requirements of the Directive<br />

and the product can be used in Class A (heavy industrial) and Class B (domestic /<br />

commercial areas).<br />

The following conditions should be avoided as they may create interference above<br />

the heavy industrial limits if:<br />

- The product or its wiring is located near a radio transmitter.<br />

- Cellular telephones and mobile radios may cause interference if used <strong>with</strong>in<br />

approximately 1 metre (39") of the product or its wiring. The actual separation<br />

distance necessary will vary according to the surroundings of the installation<br />

and the power of the transmitter.<br />

If this product is not used in the manner specified by this IMI, then the protection<br />

provided may be impaired.<br />

1.1 Intended use<br />

Referring to the Installation and Maintenance Instructions, name-plate and Technical<br />

In<strong>for</strong>mation Sheet, check that the product is suitable <strong>for</strong> the intended use / application.<br />

The product listed complies <strong>with</strong> the requirements of the European Pressure Equipment<br />

Directive 97 / 23 / EC, carries the mark when so required. The product falls <strong>with</strong>in<br />

the following Pressure Equipment Directive categories:<br />

<strong>TVA</strong> flowmetering<br />

system<br />

1. Safety in<strong>for</strong>mation<br />

Product<br />

Group 1<br />

Gases<br />

Group 2<br />

Gases<br />

Group 1<br />

Liquids<br />

Group 2<br />

Liquids<br />

DN50 to DN100 - 1 - -<br />

i) The product has been specifically designed <strong>for</strong> use on saturated steam only<br />

which is in Group 2 of the above mentioned Pressure Equipment Directive.<br />

IM-P337-62 MI Issue 1 3


ii)<br />

Check material suitability, pressure and temperature and their maximum<br />

and minimum values. If the maximum operating limits of the product are lower than<br />

those of the system in which it is being fitted, or if malfunction of the product<br />

could result in a dangerous overpressure or overtemperature occurrence, ensure<br />

a safety device is included in the system to prevent such over-limit situations.<br />

iii) Determine the correct installation situation and direction of fluid flow.<br />

iv) <strong>Spirax</strong> <strong>Sarco</strong> products are not intended to <strong>with</strong>stand external stresses that<br />

may be induced by any system to which they are fitted. It is the responsibility of<br />

the installer to consider these stresses and take adequate precautions to<br />

minimise them.<br />

v) Remove protection covers from all connections and protective film from all<br />

name-plates, where appropriate, be<strong>for</strong>e installation on steam or other high<br />

temperature applications.<br />

1.2 Access<br />

Ensure safe access and if necessary a safe working plat<strong>for</strong>m (suitably guarded)<br />

be<strong>for</strong>e attempting to work on the product. Arrange suitable lifting gear if required.<br />

1.3 Lighting<br />

Ensure adequate lighting, particularly where detailed or intricate work is required.<br />

1.4 Hazardous liquids or gases in the pipeline<br />

Consider what is in the pipeline or what may have been in the pipeline at some<br />

previous time. Consider: flammable materials, substances hazardous to health,<br />

extremes of temperature.<br />

1.5 Hazardous environment around the product<br />

Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases,<br />

extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive<br />

noise, moving machinery.<br />

1.6 The system<br />

Consider the effect on the complete system of the work proposed. Will any proposed<br />

action (e.g. closing isolation valves, electrical isolation) put any other part of the<br />

system or any personnel at risk?<br />

Dangers might include isolation of vents or protective devices or the rendering<br />

ineffective of controls or alarms. Ensure isolation valves are turned on and off in a<br />

gradual way to avoid system shocks.<br />

1.7 Pressure systems<br />

Ensure that any pressure is isolated and safely vented to atmospheric pressure.<br />

Consider double isolation (double block and bleed) and the locking or labelling of<br />

closed valves. Do not assume that the system has depressurised even when the<br />

pressure gauge indicates zero.<br />

1.8 Temperature<br />

Allow time <strong>for</strong> temperature to normalise after isolation to avoid the danger of burns<br />

and consider whether protective clothing (including safety glasses) is required.<br />

4<br />

IM-P337-62 MI Issue 1


1.9 Tools and consumables<br />

Be<strong>for</strong>e starting work ensure that you have suitable tools and / or consumables<br />

available. Use only genuine <strong>Spirax</strong> <strong>Sarco</strong> replacement parts.<br />

1.10 Protective clothing<br />

Consider whether you and /or others in the vicinity require any protective clothing<br />

to protect against the hazards of, <strong>for</strong> example, chemicals, high / low temperature,<br />

radiation, noise, falling objects, and dangers to eyes and face.<br />

1.11 Permits to work<br />

All work must be carried out or be supervised by a suitably competent person.<br />

Installation and operating personnel should be trained in the correct use of the product<br />

according to the Installation and Maintenance Instructions.<br />

Where a <strong>for</strong>mal 'permit to work' system is in <strong>for</strong>ce it must be complied <strong>with</strong>. Where<br />

there is no such system, it is recommended that a responsible person should know<br />

what work is going on and, where necessary, arrange to have an assistant whose<br />

primary responsibility is safety.<br />

Post 'warning notices' if necessary.<br />

1.12 Handling<br />

Manual handling of large and /or heavy products may present a risk of injury. Lifting,<br />

pushing, pulling, carrying or supporting a load by bodily <strong>for</strong>ce can cause injury<br />

particularly to the back. You are advised to assess the risks taking into account the<br />

task, the individual, the load and the working environment and use the appropriate<br />

handling method depending on the circumstances of the work being done.<br />

1.13 Residual hazards<br />

In normal use the external surface of the product may be very hot. If used at the<br />

maximum permitted operating conditions the surface temperature of some products<br />

may reach temperatures of 250°C (482°F).<br />

Many products are not self-draining. Take due care when dismantling or removing the<br />

product from an installation (refer to 'Maintenance instructions').<br />

1.14 Freezing<br />

Provision must be made to protect products which are not self-draining against<br />

frost damage in environments where they may be exposed to temperatures below<br />

freezing point.<br />

1.15 Disposal<br />

Unless otherwise stated in the Installation and Maintenance Instructions, this product<br />

is recyclable and no ecological hazard is anticipated <strong>with</strong> its disposal providing due<br />

care is taken.<br />

1.16 Returning products<br />

Customers and stockists are reminded that under EC Health, Safety and Environment<br />

Law, when returning products to <strong>Spirax</strong> <strong>Sarco</strong> they must provide in<strong>for</strong>mation on<br />

any hazards and the precautions to be taken due to contamination residues or<br />

mechanical damage which may present a health, safety or environmental risk. This<br />

in<strong>for</strong>mation must be provided in writing including Health and Safety data sheets<br />

relating to any substances identified as hazardous or potentially hazardous.<br />

IM-P337-62 MI Issue 1 5


2. General product in<strong>for</strong>mation<br />

This manual explains how to install, commission and maintain the <strong>Spirax</strong> <strong>Sarco</strong> <strong>TVA</strong> flowmeter<br />

<strong>for</strong> use on saturated steam.<br />

2.1 Product description<br />

The <strong>Spirax</strong> <strong>Sarco</strong> <strong>TVA</strong> flowmeter is designed to reduce the cost of flowmetering and is<br />

used as an accurate means to measure saturated steam flowrates and record total flow.<br />

The <strong>TVA</strong> flowmeter is a stand alone device and requires no other equipment, such as differential<br />

pressure transmitters, pressure sensors, etc. to calculate mass flowrates of saturated steam.<br />

The <strong>TVA</strong> <strong>with</strong> wirelessHART TM utilises power harvested by the <strong>Spirax</strong> <strong>Sarco</strong> TEG10 and<br />

communicates via wirelessHART TM protocol.<br />

2.2 Equipment delivery and handling<br />

Factory shipment<br />

Prior to shipment, the <strong>Spirax</strong> <strong>Sarco</strong> <strong>TVA</strong> flowmeter is tested, calibrated and inspected to<br />

ensure proper operation. The wireless communications are also tested.<br />

Receipt of shipment<br />

Each carton should be inspected at the time of delivery <strong>for</strong> possible external damage. Any<br />

visible damage should be recorded immediately on the carrier’s copy of the delivery slip.<br />

Each carton should be unpacked carefully and its contents checked <strong>for</strong> damage.<br />

If it is found that some items have been damaged or are missing, notify <strong>Spirax</strong> <strong>Sarco</strong><br />

immediately and provide full details. In addition, damage must be reported to the carrier <strong>with</strong> a<br />

request <strong>for</strong> their on-site inspection of the damaged item and its shipping carton.<br />

Storage<br />

If a flowmeter is to be stored prior to installation, the environmental storage conditions should<br />

be at a temperature between 0°C and 55°C (32°F and 131°F), and between 10% and 90%<br />

relative humidity (non-condensing).<br />

2.3 Sizes and pipe connections<br />

DN50, DN80 and DN100<br />

The <strong>TVA</strong> flowmeter is of a wafer design, suitable<br />

<strong>for</strong> fitting between the following flanges:<br />

- EN 1092 PN16, PN25 and PN40<br />

- BS 10 Table H<br />

- ASME B 16.5 Class 150 and 300<br />

- Korean Standard KS 20.<br />

Fig. 1 <strong>TVA</strong> flowmeter<br />

6<br />

IM-P337-62 MI Issue 1


*<br />

2.4 Pressure/temperature limits<br />

Temperature °C<br />

200<br />

150<br />

100<br />

50<br />

0<br />

0<br />

3 5 10 15 20 25 30 32<br />

Pressure bar g<br />

The product should not be used in this region due to the limitations of the software.<br />

PMA Maximum allowable pressure @ 239°C (462°F)<br />

<strong>Saturated</strong> steam 32 bar g (464 psi g)<br />

otherwise as the specified flange rating<br />

TMA Maximum allowable temperature 239°C (462°F)<br />

Minimum allowable temperature 0°C (32°F)<br />

PMO Maximum operating pressure Horizontal flow 32 bar g (464 psi g)<br />

<strong>for</strong> saturated steam service Vertical flow 7 bar g (101 psi g)<br />

Minimum operating pressure 3 bar g (43.5 psi g)<br />

TMO Maximum operating temperature 239°C (462°F)<br />

Minimum operating temperature 0°C (32°F)<br />

Maximum electronics ambient temperature 55°C (131°F)<br />

Maximum electronics humidity level<br />

Maximum<br />

PMX differential<br />

pressure<br />

Pressure psi g<br />

0 100 200 300 400<br />

239<br />

90% RH (non-condensing)<br />

The pressure drop across the <strong>TVA</strong> flowmeter at the maximum<br />

rated flow is nominally 750 m bar (300 inches wg) <strong>for</strong> the DN50,<br />

and 500 m bar (200 inches wg) <strong>for</strong> the DN80 and DN100<br />

Cold hydraulic test pressure of: 52 bar g (754 psi g)<br />

* Important note<br />

<strong>Steam</strong><br />

saturation<br />

curve<br />

The product cannot be used below 3 bar g (43.5 psi g).<br />

400<br />

300<br />

200<br />

100<br />

Temperature °F<br />

Caution: If the electronic housing is<br />

mounted at an angle of 45° (or more)<br />

from the vertically downward position<br />

the PMO (maximum operating pressure)<br />

must be limited to 7 bar g (101 psi g).<br />

Fig. 2 Installation limiting conditions<br />

IM-P337-62 MI Issue 1 7


2.5 Technical data<br />

IP Rating<br />

Power supply<br />

Communication<br />

System uncertainty<br />

Per<strong>for</strong>mance to ISO 17025<br />

WL HT<br />

Wireless<br />

IP65<br />

TEG10 (TI-P196-01)<br />

WirelessHART TM maintenance port<br />

±2% of reading over the range of 10% to<br />

100% of maximum rated flow<br />

(95% confidence to 2 STD)<br />

±0.2% FSD from 2% to 10% of maximum rated flow<br />

Turndown: up to 50:1<br />

2.6 Electrical connections<br />

Power supply<br />

TEG10 2 pin plug<br />

2.7 Materials<br />

<strong>Flowmeter</strong> body<br />

Internals<br />

Spring<br />

<strong>Flowmeter</strong> stem<br />

Electronics housing<br />

Antenna<br />

Stainless steel 1.4408 CF8M<br />

431 S29 / S303 / S304 / S316<br />

Inconel ® X750 or equivalent<br />

Stainless steel 431 S29<br />

Aluminium alloy<br />

UV stabalised ABS<br />

8<br />

IM-P337-62 MI Issue 1


2.8 Dimensions/weights (approximate) in mm and kg<br />

<strong>TVA</strong> flowmeter <strong>with</strong> WirelessHART TM option<br />

Size A B C D E F G Weight<br />

DN50 35 103 333 160 105 142 401 3.37 kg<br />

DN80 45 133 345 160 105 142 401 5.08 kg<br />

DN100 60 162 355 215 105 142 401 7.98 kg<br />

D<br />

A<br />

B<br />

C<br />

G<br />

E<br />

F<br />

Fig. 3<br />

IM-P337-62 MI Issue 1 9


3. Installation<br />

Note: Be<strong>for</strong>e actioning any installation observe the 'Safety in<strong>for</strong>mation' in Section 1.<br />

To meet its specified accuracy and per<strong>for</strong>mance it is essential that the following installation<br />

guidelines are followed carefully. For steam applications sound steam engineering practices<br />

should be followed, including the use of separators. The installation must con<strong>for</strong>m to all<br />

relevant construction and electrical codes.<br />

There are three parts to the installation of the <strong>TVA</strong> flowmeter <strong>with</strong> WirelessHART TM :<br />

3.1 WirelessHART TM commissioning (Device based).<br />

3.2 HART TM gateway installation - Page 14.<br />

3.3 Mechanical installation - Page 18.<br />

It is advised that the device based HART TM configuration is carried out on a workbench<br />

be<strong>for</strong>e the flowmeter is installed into a pipeline (mechanical installation).<br />

3.1 Device based WirelessHART TM commissioning<br />

Quick start commissioning guide<br />

For commissioning, the device can be powered by the TEG10 or a standard dc supply, wired<br />

to the internal green power connector (located inside the enclosure).<br />

The device’s parameters are modified using a HART TM user configuration tool connected<br />

to the maintenance port located inside the enclosure. When communications have been<br />

established the device automatically enters the commissioning mode.<br />

During commission mode:<br />

- MODBUS communication to the flowmeter will stop.<br />

- The device will not update the wireless gateway <strong>with</strong> the current steam flow data.<br />

- If power is being supplied via the internal green power connector, the flowmeter will<br />

remain switched off (i.e. the front panel display will not illuminate).<br />

- If power is being supplied via the TEG10, the flowmeter will power up and will continue to<br />

update the total flow internally. It will not transmit the current total flow wirelessly.<br />

The device will automatically enter the run mode, 60 seconds after the configuration tool has<br />

been disconnected or has been exited. The gateway will be updated <strong>with</strong> the current flow<br />

data and parameters.<br />

Equipment required:<br />

- HART TM configuration tool: Communicator or PC / PDA / Smart phone, DD based host and<br />

a HART TM modem (drivers to be installed).<br />

- <strong>Spirax</strong> DDL software (Device Description Language) ~ obtained from <strong>Spirax</strong> <strong>Sarco</strong> http://<br />

www.spiraxsarco.com/<br />

- Commissioning supply: 5 - 12 Vdc, 20 mAmax (Class II Safety Extra Low Voltage).<br />

- WirelessHART TM Gateway.<br />

10<br />

IM-P337-62 MI Issue 1


Set-up:<br />

- Using a Phillips screw driver, unscrew the four<br />

black screws on the front of the device.<br />

- Separate the main and back enclosures (front<br />

panel and centre body come away together),<br />

sliding them over the four hexagonal standoffs<br />

- See Figure 4.<br />

Note: Do not separate the bonded front and<br />

centre enclosures.<br />

- It is not necessary to disconnect the sensor<br />

cable.<br />

- Apply a 5 - 12 Vdc supply via the commissioning<br />

supply connector (green). A 9 V battery would<br />

be suitable. See Figure 5. Note: The resistor Fig. 4<br />

normally required by other HART TM devices is<br />

not required.<br />

- Connect the HART TM configuration tool to the device’s maintenance port. The connections<br />

are not polarised so terminals can be connected either way round. See Figure 5.<br />

- Wait until the devices power-up sequence has been completed.<br />

Commission wiring diagram<br />

FSK HART<br />

maintenance port terminals<br />

+ -<br />

HART<br />

configuration<br />

tool<br />

Warning:<br />

Must be an approved Class II<br />

safety extra low voltage supply<br />

5-12 V dc<br />

20 mA max.<br />

(regulated)<br />

Use antistatic<br />

precautions<br />

FSK HART<br />

maintenance port terminals<br />

5 - 12 Vdc<br />

internal power<br />

supply<br />

Sensor cable<br />

assembly<br />

Fig. 5<br />

External TEG10 port<br />

IM-P337-62 MI Issue 1 11


- Wait until the devices power-up sequence has been completed (see Section 5.2.1 - status<br />

lights). Note: The screen will remain blank only the status lights illuminate.<br />

- Open, from a PC / PDA / Smart-phone the DD-host by double clicking on the icon (e.g.<br />

'DevCom2000') or switch on the HART TM communicator. See Figure 6.<br />

Fig. 6<br />

- 'Learning device' will appear <strong>for</strong> a couple of seconds. See Figure 6.<br />

Note: If the device is powered via the 5 - 12 Vdc commissioning supply (green connector),<br />

a device status window will pop up at regular interval, stating that more status are<br />

available. This is normal as the flowmeters will not be powered up (i.e. 9 V power supply<br />

is switched off). Select 'ignore all messages' or enter 9999 messages and 'ignore'.<br />

- Select 'Main->Online-> Device Setup-> Basic Setup'. See Figure 7.<br />

- Double click on 'Long tag'.<br />

- Enter a suitable unique long tag name (e.g. Boiler House <strong>Steam</strong> Meter) - 32 characters<br />

maximum. Note factory default 'IDX', where 'X' is the unique serial / hart device id number.<br />

No other device on the network must have the same long tag.<br />

- Press set (the long tag name line will turn grey and yellow).<br />

- Press the send button on the icon bar at the top of the page (the line will clear).<br />

Fig. 7<br />

12<br />

IM-P337-62 MI Issue 1


Setting network-id and join-key:<br />

- The network-id and join-key in the Gateway / Network must be the same as the details<br />

written to the device. See gateway set-up <strong>for</strong> details. If a new network is being established,<br />

then the examples below can be used. Note: If more than one network is in operation,<br />

then the network-id must differ and the join-key should differ.<br />

- Select 'Main-Online-DeviceSetup-DetailedSetup-OutputCondition-WirelessHartOutput'<br />

- Double click on 'Join Network' at the top of the screen. See Figure 8.<br />

- Enter Network id (decimal) e.g. "12345", press OK.<br />

- Enter Join Key 1 (hexadecimal) e.g. "53504952", press OK.<br />

- Enter Join Key 2 (hexadecimal) e.g. "41585341", press OK.<br />

- Enter Join Key 3 (hexadecimal) e.g. "52434F52", press OK.<br />

- Enter Join Key 4 (hexadecimal) e.g. "554C455A", press OK.<br />

- Press OK until the device joins the network.<br />

Basic commissioning is complete - For a more detailed set-up, see Section 9.<br />

Fig. 8<br />

System verification:<br />

- Close down the DD host and PC.<br />

- Disconnect the HART TM configuration tool from the maintenance port.<br />

- Ensure the WirelessHART TM gateway has 'advertising' activated.<br />

- From the gateway screen, verify the device joins to the network. (i.e. a device <strong>with</strong> your<br />

chosen long tag appears). This may take a number of minutes.<br />

- Remove the 5 - 12 Vdc commissioning supply.<br />

- Re-join the two enclosures and secure <strong>with</strong> the four black screws.<br />

WARNING: Ensure the sensor wires are not trapped / pinched by the enclosures.<br />

Follow the mechanical installation.<br />

IM-P337-62 MI Issue 1 13


3.2 HART TM Gateway installation<br />

Network guidelines<br />

WirelessHART TM field devices can be sited as they would have been placed <strong>with</strong> a wired<br />

installation in most cases. The network is self-organising and will take care of <strong>for</strong>ming the<br />

mesh network and establishing communications. It will adapt to the process plant environment<br />

<strong>with</strong>out additional interaction by an operator or engineer. However, some conditions must be<br />

considered and could require relocation of the WirelessHART TM field device (or at least the<br />

antenna).<br />

3.2.1 Placing Gateways<br />

In most cases the WirelessHART TM gateway (GW) should be sited first as this is the core<br />

element of a WirelessHART TM network.<br />

Where to place the gateway:<br />

1. The gateway can be placed close to the existing hard wired network interface, perhaps<br />

by a control or plant room. This will enable the shortest possible cable run to the wired<br />

network interface.<br />

2. Fitting the gateway central to the proposed Wireless device (<strong>TVA</strong>) network. This will allow<br />

as many of the wireless devices to have a direct link to the gateway, making the network<br />

more robust and reliable.<br />

For the best results, ensure that in either case each wireless device (<strong>TVA</strong>) has at least two<br />

neighbours <strong>with</strong>in range.<br />

Ensure:<br />

- Devices are located <strong>with</strong>in the specified range. See Technical wireless data.<br />

- The device has at least two or more neighbours, located <strong>with</strong>in the specified range.<br />

Other considerations:<br />

- Mount the devices at least 0.5 m (19.5") from any vertical surface (wall) to avoid near<br />

field reflections which can disturb the radio communication. The radio waves need some<br />

space in order to become established.<br />

- Mount the devices at least 1.5 m (58.5") off the ground. Radio waves need some vertical<br />

space to provide good connection between communication partners.<br />

- Ensure that the devices are at least 0.5 m (19.5") apart from each other to avoid cross-talk.<br />

If neighbouring units are to close the radio waves could disturb each other.<br />

- The best practice is to use at least five devices in a WirelessHART TM network. Less will<br />

work, but <strong>with</strong> more devices the network becomes stronger and more reliable because<br />

more alternative paths are available. The network can be extended any time, either due<br />

to the need <strong>for</strong> more measurement signals or also <strong>with</strong> repeaters <strong>with</strong>out measurement<br />

functionality to strengthen the network.<br />

- Aim <strong>for</strong> a signal strength of better than -70 dBm.<br />

- Do not place neighbours greater than 45° elevation.<br />

- Place repeater above the areas of dense infrastructure.<br />

- Outside: Only one neighbour maybe acceptable.<br />

Inside: Two is the minimum and three if there is a robust network.<br />

These rules can be relaxed, depending on the environment, but may result in the network<br />

becoming less reliable and can cause installation difficulties.<br />

14<br />

IM-P337-62 MI Issue 1


If the above guidelines are followed then a wireless site survey is not necessary. These can<br />

be helpful but should be conducted over a period of time as wireless networks are constantly<br />

changing.<br />

Note - Ensure:<br />

- Device(s) and gateway(s) have the same join-key and network-id.<br />

- Gateway(s) has advertising activated when initially setting up the network.<br />

- In multiple networks, the device join-key and network-id is the same as the intended<br />

gateways join-key and network-id.<br />

Gateway<br />

LAN (Ethernet)<br />

Fig. 9 Network<br />

IM-P337-62 MI Issue 1 15


Antenna<br />

To avoid unnecessary attenuation of the wireless signal, resulting in impaired operation, all<br />

antennas must be:<br />

- At least 6 cm (2.5") away from any structure.<br />

- Always be aligned to the vertical.<br />

- In sight of intended neighbours.<br />

Fig. 10<br />

To change the orientation of the antenna, loosen the knurled collar enough to allow<br />

movement, reposition and retighten finger tight. It may be necessary to rotate the electronics<br />

enclosure (see separate section <strong>for</strong> instructions).<br />

16<br />

IM-P337-62 MI Issue 1


Fig. 11<br />

WARNING:<br />

Do not completely disconnect the antenna.<br />

IM-P337-62 MI Issue 1 17


3.3 Mechanical installation<br />

CAUTION: If the electronic housing is mounted at an angle of 45° (or more) from the<br />

vertically downward position the PMO (maximum operating pressure) must be limited<br />

to 7 bar g (101 psi g) - see Figure 12.<br />

A bypass line will enable safe removal of the <strong>TVA</strong><br />

flowmeter <strong>for</strong> maintenance or calibration. Closing<br />

valves V1 and V2 and opening valve V3 will allow the<br />

<strong>TVA</strong> flowmeter to be isolated.<br />

Fig. 12<br />

Installation<br />

limiting conditions<br />

<strong>Steam</strong><br />

Separator<br />

Strainer<br />

V1<br />

V3<br />

Spool<br />

piece<br />

V2<br />

Fig. 13 Typical installation<br />

Trap set<br />

<strong>TVA</strong><br />

flowmeter<br />

3.3.1 Environmental conditions<br />

The flowmeter should be located in an environment that minimises the effects of heat, vibration,<br />

shock and electrical interference. (Pressure / temperature limits are detailed in Section 2.4).<br />

CAUTION: Do not lag (insulate) the <strong>TVA</strong> flowmeter or mating flanges as this may<br />

result in excessive temperatures in the electronics. Exceeding specified temperature<br />

limits will invalidate the warranty, adversely effect the per<strong>for</strong>mance and may damage<br />

the <strong>TVA</strong> flowmeter, see Figure 14.<br />

Fig. 14 Pipeline insulation<br />

Do not<br />

insulate the flanges of the <strong>TVA</strong> flowmeter<br />

Flow<br />

Other considerations<br />

Be sure to allow sufficient clearance <strong>for</strong>:<br />

- Removal of the enclosure end caps.<br />

- Viewing of the display. Note electronics housing<br />

and display can be rotated.<br />

- Antenna rotation.<br />

- Wireless communication (min. 1 m distance from source of interference).<br />

Warning: Do not install the flowmeter outdoors where it is subjected to driving rain or<br />

can freeze.<br />

18<br />

IM-P337-62 MI Issue 1


3.3.2 Mechanical installation<br />

Warning: Do not alter the adjustment nut at the back of the <strong>TVA</strong> flowmeter shaft, as<br />

this will affect the flowmeters calibration.<br />

Orientation<br />

The <strong>TVA</strong> flowmeter can be installed in any orientation when the pressure is below 7 bar g<br />

(101 psi g), see Figures 15, 16 and 17.<br />

When the pressure is above 7 bar g the <strong>TVA</strong> flowmeter must be installed in a horizontal pipe, <strong>with</strong><br />

the electronics housing below the body, see Figure 17.<br />

Note: The <strong>TVA</strong> flowmeter operates <strong>with</strong> flow in one direction only. It is not intended <strong>for</strong> use<br />

<strong>with</strong> bi-directional flow. The <strong>TVA</strong> flowmeter is clearly marked <strong>with</strong> a direction of flow arrow.<br />

Flow<br />

Fig. 15 Vertical flow limited to 7 bar g<br />

Flow<br />

CAUTION: If the electronic housing is<br />

mounted at an angle of 45° (or more) from<br />

the vertically downward position the PMO<br />

(maximum operating pressure) must be<br />

limited to 7 bar g (101 psi g) - see Figure 12.<br />

Flow<br />

Flow<br />

Fig. 16 Horizontal flow limited to 7 bar g<br />

Fig. 17 Horizontal flow up to 32 bar g<br />

IM-P337-62 MI Issue 1 19


Rotating the electronics enclosure<br />

The electronics housing can be rotated 270°<br />

to enable sufficient clearance <strong>for</strong> installation.<br />

To rotate the electronics housing, loosen the<br />

6 mm grub screw located on the rear of the<br />

electronics housing (see Figure 18). The<br />

electronics housing can now be rotated<br />

to the required position.<br />

When the electronics housing has been<br />

located into the correct position retighten the<br />

grub screw to a torque of 1.3 N m (11.5 lbf in).<br />

Warning: Do not loosen / remove the stem<br />

from the main body of the unit.<br />

Warning: Do not<br />

loosen / remove the<br />

stem from the main<br />

body of the unit.<br />

6 mm grub screw<br />

Fig. 18<br />

Upstream / downstream pipework<br />

The <strong>TVA</strong> flowmeter should be installed in pipework manufactured to BS 1600, ASME B 36.10<br />

Schedule 40 or EN 10216-2 / EN 10216-5 equivalent, which corresponds to the following<br />

pipeline internal diameters:<br />

Nominal diameter<br />

Nominal internal diameter<br />

50 mm 52 mm<br />

80 mm 77 mm<br />

100 mm 102 mm<br />

For different pipe standards / schedules, if the flowmeter is being operated at the extreme<br />

of its published maximum range, and maximum accuracy is required, downstream spool<br />

pieces manufactured from pipe to the above standard should be used.<br />

It is important that the internal upstream and downstream diameters of pipe are smooth.<br />

Ideally seamless pipes should be used and there should be no intrusive weld beads on the<br />

internal diameter. It is recommended that slip-on flanges be used to avoid any intrusive weld<br />

beads on the internal diameter of the pipe.<br />

Note: See Figures 19 to 22 <strong>for</strong> other considerations which need to be noted be<strong>for</strong>e<br />

determining the correct installation location.<br />

20<br />

IM-P337-62 MI Issue 1


The <strong>TVA</strong> flowmeter normally only requires a minimum of 6 pipe diameters upstream and<br />

3 downstream of clear straight pipe. These dimensions assume a measurement from a single<br />

90° bend (see Figure 19).<br />

6D Minimum<br />

3D Minimum<br />

Fig. 19<br />

Flow<br />

If any of the following configurations are present upstream of the <strong>TVA</strong> flowmeter:<br />

- Two right angled bends in two planes.<br />

- Pressure reducing valve.<br />

- Partly open valve.<br />

Then it is recommended that the minimum upstream clear pipework is doubled to 12 diameters<br />

(See Figure 20).<br />

12D Minimum<br />

3D Minimum<br />

Fig. 20<br />

Flow<br />

IM-P337-62 MI Issue 1 21


Avoid installing the <strong>TVA</strong> flowmeter downstream of an actuated valve as rapid cycling<br />

of the valve could give rise to inaccurate results or damage the flowmeter. See Figure 21.<br />

In configurations where there is more than one rapid acting pressure reducing valve<br />

close coupled, the <strong>TVA</strong> flowmeter should be installed <strong>with</strong> a minimum of 25 upstream and<br />

3 downstream pipe diameters away from the valves.<br />

Safety valves should also be as far away as possible from the flowmeter - at least 25D.<br />

25D Minimum<br />

3D Minimum<br />

Flow<br />

Fig. 21<br />

To install the <strong>TVA</strong> flowmeter pipeline unit into<br />

existing pipework and <strong>for</strong> aiding possible<br />

flowmeter removal, a spool piece can be<br />

fabricated locally - See dimension (A) in<br />

Figure 22.<br />

Size DN50 DN80 DN100<br />

180 mm 240 mm 300 mm<br />

Dimension A<br />

7.1" 9.5" 11.8"<br />

A<br />

Flow<br />

Spool piece<br />

Fig. 22<br />

22<br />

IM-P337-62 MI Issue 1


Location in pipework<br />

Bolt ring gaskets having the same internal diameter of the pipework are recommended. This<br />

will prevent possible inaccuracies being created by the gasket protruding into the pipe.<br />

It is important that the <strong>TVA</strong> flowmeter is located centrally in the pipework as any eccentricity<br />

may cause inaccurate readings. The <strong>TVA</strong> flowmeter has integral centering webs, which locate<br />

on the internal diameter of the pipework (see Figure 23).<br />

Integral centering webs<br />

Integral centering webs<br />

Fig. 23 Integral centering webs<br />

Fig. 24 Gaskets fitted correctly<br />

Fig. 25 Gaskets fitted incorrectly<br />

Fig. 26 Gaskets and pipe offline,<br />

fitting incorrectly<br />

IM-P337-62 MI Issue 1 23


3.4 Electrical installation<br />

The <strong>TVA</strong> flowmeter is designed to be powered by the <strong>Spirax</strong> <strong>Sarco</strong> TEG10 thermoelectric<br />

generator only. The power connection on the <strong>TVA</strong> head will accept the 2 pin connector<br />

from the TEG10 - For further Technical data regarding the TEG10 see either the Technical<br />

In<strong>for</strong>mation sheet TI-P196-01 or Installation and Maintenance Instructions IM-P196-02.<br />

Do not connect any other power supply to this port.<br />

4. Commissioning<br />

After all mechanical and electrical work<br />

has been completed, the following<br />

commissioning instructions should be<br />

followed.<br />

Note: The <strong>TVA</strong> flowmeter is factory set to<br />

display data in metric units. To commission<br />

the <strong>TVA</strong> to display imperial units see<br />

Section 4.4.2, page 30.<br />

LCD<br />

display<br />

5 button<br />

keypad<br />

Commissioning of the flowmeter is carried<br />

out through the display unit. The display<br />

unit consists of a small LCD display and a<br />

5 button key pad.<br />

Mounting<br />

screws<br />

Rotating the display<br />

The display can be rotated through 180° to enable ease of commissioning. To rotate the<br />

display disconnect the power supply, remove the mounting screws on the front, carefully remove<br />

the front and middle sections and rotate. Do not attempt to separate the display and the<br />

centre section. Carefully replace the display unit and replace mounting screws. Do not <strong>for</strong>ce<br />

the display unit into position. Reconnect the power supply. Note: Electrostatic discharge<br />

(ESD) procedures should be followed while rotating the display.<br />

4.1 Run mode<br />

Normally, the <strong>TVA</strong> flowmeter will operate in the run mode, displaying the total flow, flow, power,<br />

pressure or temperature of the fluid passing through the pipeline.<br />

After initial power up, the <strong>TVA</strong> flowmeter will automatically enter the run mode and all<br />

commissioning menus can be accessed from this mode. (See Section 4.2, Commissioning<br />

mode, <strong>for</strong> details on how to commission).<br />

In the run mode the fluid data is displayed on several screens which can be accessed by pressing<br />

the up or down keys. The display shows a numeric<br />

value and an arrow indicating the reading type, i.e.<br />

total flow, flow, power, pressure or temperature.<br />

All units (except °C) are implied <strong>with</strong> imperial or<br />

metric units being indicated by another arrow. The<br />

value of total flow is shown in two parts. The first<br />

five digits of the total flow will be displayed and<br />

after 10 seconds the following five digits will be<br />

displayed. To access the first five digits of total<br />

flow again it will be necessary to scroll up or down<br />

and return to the total flow display.<br />

Fig. 27 <strong>TVA</strong> flowmeter display unit<br />

Arrow<br />

total<br />

temp<br />

flow<br />

imp<br />

power pres<br />

Fig. 28<br />

24<br />

IM-P337-62 MI Issue 1


4.1.1 Run mode data sequence<br />

TOTAL<br />

HIGH<br />

FLOW<br />

POWER<br />

Power kW or MBtu/h.<br />

Pressure<br />

Pressure bar g or psi g, depending if<br />

metric or imperial units are selected.<br />

Temp. °C<br />

Temperature °C or °F.<br />

The following chart indicates the run mode data display sequence.<br />

Depending on the configuration, the flow units will be:<br />

Units <strong>Steam</strong><br />

Metric Kg/h, KW, bar g, °C<br />

Imperial lb/h, MBtu/h, psi g, °F<br />

The <strong>TVA</strong> flowmeter is factory set to display steam data in metric units and pressing the up or<br />

down keys will scroll through the following data.<br />

total<br />

flow power pres<br />

Total flow<br />

imp<br />

temp<br />

total<br />

flow power pres<br />

Temperature<br />

total<br />

flow power pres<br />

imp<br />

temp<br />

Flow<br />

imp<br />

temp<br />

total<br />

flow power pres<br />

Pressure<br />

total<br />

flow power pres<br />

imp<br />

temp<br />

Power<br />

Fig. 29<br />

imp<br />

temp<br />

IM-P337-62 MI Issue 1 25


4.1.2 Error display messages<br />

Any errors that occur will be displayed in the run mode. The errors will alternate <strong>with</strong> the normal<br />

run mode display and will be prioritised. The errors will be latched and can only be cancelled by<br />

pressing the 'OK' button. Once the error message has been cancelled the display will show the<br />

next (if any) error.<br />

Any continuous error will reinstate itself 2 seconds after it has been cancelled, and will be indicated<br />

by a flashing exclamation mark (!).<br />

The error messages are displayed over two screens and are:<br />

POWER<br />

OUt<br />

= Power interrupted.<br />

NO<br />

SIGNL<br />

= No signal from sensor.<br />

SENSR<br />

CONSt<br />

= Signal from sensor constant.<br />

HIGH<br />

FLOW<br />

= Flow above the maximum.<br />

26<br />

IM-P337-62 MI Issue 1


4.2 Commissioning mode - <strong>Flowmeter</strong><br />

The commissioning mode is used to re-range, and change the pass code.<br />

All data entry is per<strong>for</strong>med via a menu and sub menu configuration <strong>with</strong> the key pad buttons<br />

used <strong>for</strong> navigation, i.e. to go deeper into the menu the right hand key is pressed, to scroll up and<br />

down the menu the up and down keys are pressed and to exit from a sub-menu the left key is pressed.<br />

Any data is entered using the OK button. The previously entered selection will<br />

flash. After a period of five minutes <strong>with</strong>out any keys being pressed the <strong>TVA</strong> flowmeter will<br />

automatically default to the run mode.<br />

For a full commissioning flow chart see Section 4.3.<br />

To enter the commissioning mode press and hold down the 'OK' key <strong>for</strong> 3 seconds. The display<br />

then shows:<br />

ENtER<br />

PASS<br />

Followed by:<br />

BASIC<br />

dAtA<br />

7452<br />

The leading digit will flash indicating that this is the position of the cursor.<br />

The default factory set pass code is 7452. (This can be changed from <strong>with</strong>in the commissioning<br />

mode). The pass code can be entered by using the up and down keys to increment the flashing<br />

value and the left and right keys to move the cursor. Pressing 'OK' will enter the pass code.<br />

If an incorrect pass code is used the display will automatically return to the run mode.<br />

After the correct pass code is entered the display shows:<br />

To exit from the commissioning mode at any stage, continually pressing the left key will return to<br />

the run mode.<br />

Pressing the up and down buttons scrolls through the various first level menus.<br />

Pressing the right arrow button enters a particular sub-menu.<br />

ENtER<br />

PASS<br />

xxxx<br />

BASIC<br />

dAtA<br />

MEtER<br />

OUt<br />

PUts<br />

tESt<br />

ALARM<br />

SW.VER<br />

SEt<br />

PASS<br />

IM-P337-62 MI Issue 1 27


4.3 Wireless <strong>TVA</strong> flowmeter commissioning flow chart<br />

Software<br />

version number<br />

Normal run mode<br />

display sequence<br />

Default = 8888<br />

but user settable.<br />

Configuration<br />

sub-menus<br />

(test<br />

display)<br />

VER x.x<br />

Total<br />

high<br />

ENTER<br />

PASS<br />

xxxx<br />

BASIC<br />

dAtA<br />

Power on sequence; turn<br />

on all segments, then<br />

show the software version<br />

no.<br />

Total<br />

low<br />

kg or lbs<br />

(kWh or Mbtu)<br />

Flow<br />

Power<br />

Pressure<br />

Temp. °C<br />

kg/h or lb/h<br />

kW or MBtu/h<br />

bar g or psi g, depending if metric or<br />

imperial units are selected.<br />

°C or °F<br />

MEtER<br />

OUt<br />

PUtS<br />

Shaded areas of the menu are<br />

not applicable <strong>for</strong> the wireless<br />

<strong>TVA</strong> communications.<br />

Error Messages<br />

These alternate <strong>with</strong> the normal run mode display.<br />

They will be prioritised and will be latched when<br />

they occur.<br />

Pressing the 'OK' button will cancel the displayed<br />

alarm and allow the next one to be viewed.<br />

A continuous alarm will re-occur on the display<br />

2 seconds after it has been cancelled.<br />

xxxx<br />

xxxx<br />

SEt<br />

PASS<br />

SW.VER<br />

Power<br />

interrupted<br />

POWER<br />

OUt<br />

HIGH<br />

O/P<br />

ALARM<br />

ALARM<br />

LOW<br />

No<br />

signal from<br />

sensor<br />

NO<br />

SIGNL<br />

The 4-20 mA<br />

alarm can also<br />

be activated<br />

OFF<br />

tESt<br />

Signal<br />

from sensor<br />

constant<br />

SENSR<br />

CONST<br />

The 4-20 mA<br />

alarm can also<br />

be activated<br />

ON<br />

OFF<br />

Power<br />

alarm<br />

Flow<br />

above<br />

maximum<br />

HIGH<br />

FLOW<br />

Shows when<br />

flow exceeds<br />

maximum<br />

ON<br />

OFF<br />

CONST<br />

ALARM<br />

28<br />

IM-P337-62 MI Issue 1


dRy<br />

xxx%<br />

UNItS<br />

MEt<br />

tOtAL<br />

Mass<br />

IMP<br />

AtMOS<br />

PRES<br />

xxx.xx<br />

Energy<br />

dIR<br />

HORIZ<br />

S/N<br />

xxxxx<br />

DOWN<br />

CLEAR tOtAL<br />

ZErO MEtER<br />

UP<br />

4-20 mA<br />

SORCE<br />

FLOW<br />

POWER<br />

PULSE<br />

yES<br />

NO<br />

SORCE<br />

tOtAL<br />

ENRgy<br />

SEt.4 mA<br />

xxxxx<br />

in kg/h or lb/h,<br />

kW or Btu/h.<br />

Comms<br />

Baud<br />

NUM/<br />

PULSE<br />

PULSE<br />

WIDTH<br />

xxxxx<br />

in kg or lbs,<br />

kWh or MBtu.<br />

xxxmS<br />

Must not<br />

exceed 4 pulses<br />

per second.<br />

1200<br />

SEt.20 mA<br />

CHECK<br />

4 mA<br />

CHECK<br />

20 mA<br />

xxxxx<br />

OP = 4 mA<br />

Connect a DVM<br />

and use the up<br />

and down keys to<br />

set 4 or 20 mA.<br />

OP = 20 mA<br />

Type<br />

ASCII<br />

9600<br />

Modbus<br />

Add<br />

XXX<br />

Press OK to select<br />

dISP<br />

Display TEST<br />

4-20 mA<br />

OUt<br />

xxx.xxmA<br />

Shaded areas of the menu are<br />

not applicable <strong>for</strong> the wireless<br />

<strong>TVA</strong> communications.<br />

PULSE OUt<br />

ON<br />

CANCL<br />

OFF<br />

IM-P337-62 MI Issue 1 29


4.4 BASIC DAtA Sub menu<br />

BASIC<br />

dAtA<br />

dRy<br />

xxx%<br />

UNItS<br />

MEt<br />

tOtAL<br />

Mass<br />

IMP<br />

AtMOS<br />

PRES<br />

xxx.xx<br />

Energy<br />

4.4.1 dRy<br />

Pressing the right key will display the dryness fraction. This is the dryness fraction of the<br />

saturated steam being measured. This can then be edited to suit the application. Press the 'OK'<br />

button to confirm the selection.<br />

After the dryness fraction is entered the display will automatically step to the next sub menu<br />

and show 'UNItS'<br />

4.4.2 UNItS<br />

The units displayed and transmitted can be selected between metric (MEt), and imperial (IMP).<br />

A summary of the units is detailed in the Table below.<br />

Units <strong>Steam</strong><br />

Metric Kg/h, KW, bar g, °C<br />

Imperial lb /h, MBtu/h, psi g, °F<br />

Select either 'MEt' or 'IMP' and press the 'OK' button to confirm.<br />

Note: Only metric units in kg can be wirelessly transmitted.<br />

4.4.3 tOtAL<br />

This function allows selection of the units to be shown as Mass flow or Energy rate.<br />

4.4.4 AtMOS PRES<br />

This value compensates the flowrates <strong>for</strong> atmospheric pressure. It should be used if a high degree<br />

of accuracy is required or when the <strong>TVA</strong> flowmeter is installed high above sea level.<br />

Note: Values up to two decimal places can be entered.<br />

If metric units are selected pressure units are bar absolute, <strong>for</strong> imperial units psi absolute.<br />

30<br />

IM-P337-62 MI Issue 1


4.5 MEtER Sub-menu<br />

MEtER<br />

dIR<br />

HORIZ<br />

This sub-menu contains in<strong>for</strong>mation about the<br />

flowmeter and is used to zero the flowmeter<br />

and clear the total.<br />

S/N<br />

ZErO MEtER<br />

xxxxx<br />

DOWN<br />

UP<br />

CLEAR tOtAL<br />

4.5.1 dIR<br />

dIR is the orientation that the <strong>TVA</strong> flowmeter is installed in. The <strong>TVA</strong> flowmeter can be<br />

installed <strong>with</strong> horizontal flow up to a pressure of 32 bar g (464 psi g). For installations that require<br />

vertical flow either up or down the maximum pressure must not exceed 7 bar g<br />

(101 psi g). By selecting down or up the effect of gravity on the cone is taken into account.<br />

Note: Upon entering the dIR sub-menu, HORIZ is always shown first. The actual direction<br />

selected is the one which is flashing.<br />

4.5.2 S/N<br />

This is the factory set serial number of the <strong>TVA</strong> flowmeter and is displayed by pressing<br />

the right key.<br />

4.5.3 ZErO MEtER - Not used <strong>with</strong> wireless <strong>TVA</strong><br />

This function is used to zero the <strong>TVA</strong> flowmeter manually to compensate <strong>for</strong> any<br />

electronic drift.<br />

The procedure <strong>for</strong> zeroing the flowmeter is as follows:<br />

- Isolate the pipeline where the flowmeter is installed and ensure that there is no flow.<br />

The line temperatures should be above 5°C (41°F) and below 30°C (86°F).<br />

- Press and hold the 'OK' button <strong>for</strong> three seconds.<br />

On completion the display will step back to S/N.<br />

If 'ZErO ErrOr' is displayed, check to ensure that the line is isolated <strong>with</strong> no flow. If 'tEMP ErrOr'<br />

is displayed the line temperature is below 5°C (41°F). Allow the temperature to move above 5°C<br />

(41°F) and re-zero. Note: The flowmeter should ideally be zeroed once every 12 months.<br />

4.5.4 CLEAR tOtAL<br />

This function is used to clear the total by pressing and holding the OK key <strong>for</strong> 3 seconds.<br />

Note: The total is backed-up every 8 minutes in the <strong>TVA</strong> flowmeter's non-volatile memory.<br />

If power is lost the <strong>TVA</strong> flowmeter could lose up to 8 minutes worth of totalised steam.<br />

IM-P337-62 MI Issue 1 31


4.6 ALARM O/P and Power - Not used <strong>with</strong> wireless <strong>TVA</strong><br />

This sub-menu gives access to setting the action that is required on the 4-20 mA output<br />

when an error is detected by the <strong>TVA</strong> flowmeter electronics. It also gives access to the<br />

power alarm function.<br />

HIGH<br />

O/P<br />

ALARM<br />

LOW<br />

OFF<br />

POWER<br />

ALARM<br />

ON<br />

OFF<br />

4.6.1 CONSt ALARM<br />

This allows the constant flow alarm to be turned off.<br />

The constant alarm is switched to on by the default factory setting. It detects if the flow has<br />

been constant <strong>for</strong> long periods when at pressure, which may indicate a stuck cone due to<br />

debris.<br />

If the system that the <strong>TVA</strong> is fitted to, has long periods where there is zero flow, but the line<br />

is kept at a constant pressure, it is advisable to turn the alarm off to avoid unwanted alarm<br />

messages.<br />

ON<br />

CONST<br />

ALARM<br />

OFF<br />

4.7 SW.VER<br />

This allows the software version to be viewed.<br />

SW.VER<br />

xxxx<br />

4.8 SEt PASS<br />

This allows the default pass code to be changed to a user defined value.<br />

It is important that if the default pass code is changed that the new value is noted and kept safe.<br />

The new pass code can be recorded on the Table in Section 9, page 41.<br />

SEt<br />

PASS<br />

xxxx<br />

32<br />

IM-P337-62 MI Issue 1


5. Operation<br />

The <strong>TVA</strong> flowmeter operates by measuring the strain produced on a moving cone by an<br />

instantaneous flowrate. This strain is then converted into a density compensated mass flowrate<br />

and is transmitted via WirelessHART TM protocol. The unique design of the <strong>TVA</strong> flowmeter<br />

produces the high turndowns and high accuracy required in process applications.<br />

5.1 Operation modes<br />

The device has three operating modes; Power-up, Commissioning and Run mode.<br />

Power-up: The device goes through a self-test procedure, which takes approximately<br />

5 seconds. When the self-test is satisfactorily completed, the device enters into an initialization<br />

procedure, which takes approximately 26 seconds. During this period (a total of 31 seconds),<br />

it is not possible to connect to the network or communicate via the maintenance port.<br />

Power is then applied to the flowmeter and the device enters run mode. Note: If the initial<br />

self-test actually reveals a problem, the device enters a system failed state. See Light Status<br />

section. Note: the display will not illuminate until after the 31 second initialisation procedure.<br />

Commissioning: The device automatically enters commissioning mode when a HART TM<br />

configuration tool is communicating via the device’s maintenance port (see wiring diagram).<br />

Once commissioning procedure has been completed, the device will automatically revert back<br />

to run mode 60 seconds later. See the 'Quick start commissioning guide', Section 3.1, page 10.<br />

Run mode: The device transmits steam flow data and device parameters via a WirelessHART TM<br />

network to a wired host / HMI interface.<br />

5.2 Other features<br />

Reset: The device can be reset by sending the 'device reset' command (HART command 42). It<br />

can take up to 50 seconds to execute as the other devices in the network need to be in<strong>for</strong>med<br />

first. The resulting restart is identical to the normal power up sequence.<br />

Self-test: The device’s internal power supplies and non-volatile memory can be tested by<br />

sending the self-test command (HART command 41). A memory failure will cause the device<br />

to enter the system failure state. There is no recovery from system failure state, other than the<br />

failure is indicated by the lights. See the 'Light status' Sections - Page 34 to 36.<br />

IM-P337-62 MI Issue 1 33


5.2.1 Status lights<br />

The device has two dual-coloured and one single-coloured light. They are used to indicate the<br />

system (SYS), wireless network (RF) and MODBUS / FSK (COMM) operation. Note: In normal<br />

operation, no more than one light is on at the same time (i.e. there is a short delay between<br />

each light).<br />

1. Initial systems self-test (SYS) 2. System initialising (SYS)<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

Solid green light on <strong>for</strong> 4 to 5s<br />

All other lights are off.<br />

Slow (3s off) flashing green light.<br />

The device takes 26 seconds to initialize.<br />

All other lights are off<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

3. Normal system operation (SYS) 4. System failure (SYS)<br />

Fast flashing green light (1s off time).<br />

The other lights maybe illuminated. See<br />

below <strong>for</strong> further details<br />

Fast flashing green, amber and red light<br />

means a system failure (1s off time).<br />

5. SYS light permanently switch off<br />

There is a fault <strong>with</strong> the device or no power has been applied.<br />

34<br />

IM-P337-62 MI Issue 1


5.2.2 Wireless Communication (RF – Radio Frequency)<br />

The 'RF' light has two colours, green and amber. It shows the state of the wireless<br />

communication.<br />

1. Attempting to join the network: 2. Now connected to network:<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

Fast flashing green light (1s off time)<br />

Slow flashing green light (3s off time)<br />

3. The requested burst rate has been declined by the network manager (RF):<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

COMM<br />

RF<br />

SYS<br />

Slow flashing amber light (3s off time)<br />

4. RF light permanently switched off<br />

RF idle<br />

IM-P337-62 MI Issue 1 35


5.2.3 MODBUS / FSK HART Communication (COMM)<br />

The COMM light has two colours, green and red. It primarily shows the status of the internal<br />

MODBUS communication to the flowmeter. When a HART TM configuration tool is connected<br />

to the maintenance port and communication has been established, the light will flash red<br />

quickly, indicating commissioning mode has been entered.<br />

1. Initializing MODBUS<br />

communications:<br />

2. MODBUS normal communication <strong>with</strong><br />

flowmeter:<br />

COMM<br />

RF RF<br />

SYS<br />

COMM<br />

RF RF<br />

SYS<br />

COMM<br />

RF RF<br />

SYS<br />

COMM<br />

RF RF<br />

SYS<br />

COMM<br />

RF RF<br />

SYS<br />

COMM<br />

RF RF<br />

SYS<br />

COMM<br />

RF RF<br />

SYS<br />

COMM<br />

RF RF<br />

SYS<br />

Fast flashing green light (1s off time)<br />

Slow flashing green light (3s off time)<br />

3. MODBUS communication error(s): 4. Normal FSK HART TM communication:<br />

Slow flashing red light (3s off time)<br />

Fast flashing red light (1s off time)<br />

5. COMM light permanently off: MODBUS master is disabled.<br />

36<br />

IM-P337-62 MI Issue 1


6. Maintenance<br />

Frequency of re-calibration depends upon the service conditions experienced by the flowmeter<br />

and the application. Re-calibration frequency can be typically between 2 and 5 years.<br />

7. Spare parts<br />

There are no spare parts available <strong>for</strong> the wireless <strong>TVA</strong> flowmeter.<br />

8. Fault finding<br />

Many faults which occur on commissioning are found to be due to incorrect installation or<br />

commissioning, there<strong>for</strong>e it is recommended that a thorough check is carried out should there<br />

be a problem.<br />

The <strong>TVA</strong> flowmeter display has in-built diagnostic features and will indicate a number of errors<br />

on the display.<br />

The errors will alternate <strong>with</strong> the normal run mode display and will be shown according to priority.<br />

The errors will be latched and can only be cancelled by pressing the 'OK' button. Once the error<br />

message has been cancelled the display will show the next (if any) error.<br />

Any continuous error will re-instate itself 2 seconds after it has been cancelled, and will be<br />

indicated by a flashing exclamation mark (!).<br />

8.1 Function fault finding<br />

Symptom Action<br />

1. Ensure either the TEG10 or if in commissioning mode the 5 - 12 Vdc<br />

commission supply is connected correctly.<br />

2. Disconnect the supply and measure / verify the device is being<br />

1 supplied <strong>with</strong> the correct voltage. See technical in<strong>for</strong>mation below<br />

All lights are off and TEG10 IMI technical in<strong>for</strong>mation (IM-P196-02).<br />

3. Investigated local sources of electrical noise.<br />

Symptom Action<br />

1. Refer to: <strong>Spirax</strong>-<strong>Sarco</strong> Limited.<br />

2<br />

Display shows:<br />

NO SIGNL<br />

Symptom Action<br />

3<br />

Display shows:<br />

POWER Out<br />

Symptom Action<br />

4<br />

Display shows:<br />

SENSR CONST<br />

1. Power supply may have been interrupted. Ensure power supply is<br />

secure and cancel error using the 'OK' key.<br />

2. Totals transmitted may not be valid.<br />

1. Cone is possibly jammed. Remove unit from pipeline and<br />

check cone movement.<br />

2. Electronics faulty. Refer to: <strong>Spirax</strong>-<strong>Sarco</strong> Limited.<br />

IM-P337-62 MI Issue 1 37


Symptom Action<br />

5<br />

Display shows:<br />

HIGH FLOW<br />

Symptom Action<br />

6<br />

Flow indicated<br />

responds to<br />

changes in<br />

actual flow but<br />

value indicated<br />

does not<br />

correspond to<br />

actual flowrate<br />

1. The flowmeter is possibly undersized. Check sizing and replace if<br />

necessary.<br />

1. <strong>Flowmeter</strong> not properly centred in the pipeline. The axis of the flowmeter<br />

bore should be aligned <strong>with</strong> that of the pipe.<br />

2. Pipe Gaskets at the flowmeter protrude into the pipe bore. See<br />

Section 3, Figures 24, 25 and 26 <strong>for</strong> proper installation of gaskets.<br />

3. Irregularities on the surface of the pipe bore. Pipe bore should be free<br />

of irregularities.<br />

4. Signal falsified due to bi-phase medium. Bi-phase media are not<br />

permitted.<br />

5. Use a separator <strong>for</strong> wet steam applications to remove moisture<br />

droplets from the steam.<br />

6. Insufficient upstream/downstream pipe lengths. See Section 3 <strong>for</strong><br />

correct lengths of upstream and downstream pipes.<br />

7. Flow direction reversed. Check flow direction arrow on primary.<br />

Symptom Action<br />

1. Insufficient upstream and downstream pipe lengths. Re-install<br />

following the installation guidelines (Section 3).<br />

7<br />

Produces large<br />

amount of noise<br />

(banging and<br />

clattering)<br />

Symptom Action<br />

1. See actions in Symptom 1.<br />

2. Switch off the power, leave disconnected to 10 seconds and<br />

8 reconnect power.<br />

System failure.<br />

COMM: red<br />

RF: amber<br />

SYS: green<br />

(flashing together)<br />

Symptom<br />

9<br />

Device is not<br />

connecting to<br />

the wireless<br />

network.<br />

(RF fast flashing<br />

green light)<br />

Symptom<br />

10<br />

Burst rate<br />

declined<br />

(RF slow flashing<br />

amber light)<br />

Action<br />

1. See actions in Symptom 1.<br />

2. Ensure the wireless network complies <strong>with</strong> the recommended<br />

guidelines. See network installation section.<br />

Action<br />

1. Refer to gateway wireless bandwidth specifications, and decrease<br />

devices burst rate accordingly.<br />

38<br />

IM-P337-62 MI Issue 1


Symptom Action<br />

1. See actions in Symptom 2.<br />

2. Via the front panel keypad, ensure the <strong>TVA</strong> flowmeters commissioning<br />

11 parameters are correct. See Modbus parameters.<br />

Device COMM<br />

Error (COMM<br />

slow flashing amber/<br />

red light)<br />

Symptom<br />

12<br />

Device does<br />

not recognize<br />

the HART<br />

configuration<br />

tool<br />

Symptom<br />

13<br />

Device does<br />

not update<br />

the gateway<br />

<strong>with</strong> the flow<br />

meter variables<br />

(RF light off)<br />

Symptom<br />

14<br />

Host receiving<br />

unexpected<br />

event<br />

notifications<br />

Action<br />

1. See actions in Symptom 1.<br />

2. Ensure the tools leads are correctly connected to the maintenance<br />

port.<br />

3. Ensure the tools drivers are installed correctly.<br />

4. Ensure the pc port parameters are correctly set up. See modem<br />

manual.<br />

5. Ensure the host software has been correctly installed. See host<br />

manuals.<br />

6. Ensure the DD host polling address is the same as the devices<br />

polling address.<br />

Action<br />

1. See actions in Symptom 1.<br />

2. Ensure via the devices front panel display that the variables are<br />

actually changing.<br />

3. See actions in Symptom 11.<br />

4. Ensure the burst parameters are set correctly.<br />

Action<br />

1. See actions in Symptom 1.<br />

2. Investigate which events are occurring.<br />

See Section 8.3 - Appendix (page 40).<br />

Symptom<br />

15<br />

Device<br />

intermittently<br />

does not<br />

connect to the<br />

network<br />

Action<br />

1. Check signal strengths and communication quality.<br />

See Section 8.3 - Appendix (page 40).<br />

2. See actions in Symptom 1.<br />

3. See actions in Symptom 3.<br />

If symptoms are still present return and replace product.<br />

IM-P337-62 MI Issue 1 39


8.3 Appendix<br />

Abbreviations and definitions<br />

Access point<br />

ASME<br />

Cmd<br />

CRC<br />

dBi<br />

dBm<br />

DSSS<br />

Dyn<br />

FSK<br />

WirelessHART<br />

Gateway<br />

HART<br />

Hexadecimal<br />

HMI<br />

Host<br />

IAPWS<br />

MAC address<br />

Master<br />

Modem<br />

The radio which provides the connectivity to the WirelessHART TM<br />

network<br />

American Society of Mechanical Engineers<br />

Command<br />

Cyclic Redundancy Check. Error detecting code used to check<br />

communications and storage devices.<br />

Gain of the antenna in decibels. 'i' means relative to isotropic antenna.<br />

Power in decibels relative to 1 mW.<br />

Example: 0 dBm = 1 mW, 10 dBm = 10 mW, 20 mW = 100 mW<br />

Direct Sequence Spread Spectrum<br />

Dynamic<br />

Frequency Shift Keying. A scheme in which digital in<strong>for</strong>mation is<br />

transmitted through discrete frequency changes.<br />

Manages and connects the WirelessHART TM to the wired world. It<br />

normally comprises of an Access Point, Network Manager, Security<br />

Manager, Virtual Gateway and HOST Interface.<br />

Highway Addressable Remote Transducer<br />

0 1 2 3 4 5 6 7 8 9 A B C D E F<br />

Human Machine Interface. A graphics based interface between the<br />

user and the system.<br />

One of possibly several user applications that can be executed<br />

sequentially or simultaneously on a master.<br />

International Association <strong>for</strong> the Properties of Water and <strong>Steam</strong><br />

Media Access Control address. Unique identifier <strong>for</strong> assigned to a<br />

network interface.<br />

A device(s) that initiates communication on a WirelessHART TM network<br />

by issuing commands to the Field devices. HART TM supports primary<br />

and secondary masters.<br />

A modem (modulator-demodulator) device that enables a computer to<br />

transmit data to and from a digital to an analogue signal.<br />

MODBUS Communications Protocol (master-slave / client-server )<br />

Network<br />

manager<br />

Packed ASCII<br />

Preamble<br />

PRT<br />

PV<br />

QV<br />

SV<br />

TEG<br />

TDMA<br />

TV<br />

Var<br />

Forms, organizes, monitors and extends the network. It takes care <strong>for</strong><br />

distributing Join and Network Keys as well as communication slots and<br />

channels <strong>for</strong> all participants.<br />

Valid characters: @ A B C D E F G H I J K L M N O P Q R S T U V W X<br />

Y Z [ \ ] ^ _ SP ! " # $ % & ' ( ) * + , - . / 0 1 2 3 4 5 6 7 8 9 : ; < = > ?<br />

A synchronising pattern generating at the beginning of the HART<br />

message to allow proper start-up.<br />

Platinum Resistance Thermometer<br />

Primary Variable<br />

Quaternary Variable<br />

Secondary Variable<br />

Thermoelectric Generator<br />

Time Division Multiple Access<br />

Tertiary Variable<br />

Variable<br />

40<br />

IM-P337-62 MI Issue 1


9.1 Technical electrical data<br />

9.1.1 Commission supply (green connector)<br />

Supply voltage (Vdc)<br />

Supply current Maximum<br />

Cable length<br />

4.95 to 12.12 (regulated)<br />

20 mA<br />

9.1.2 External supply (TEG10 Only)<br />

3 metres (maximum)<br />

Parameter Minimum Typical Maximum<br />

Switch- on voltage (Vdc) 1.696 1.867 2.043<br />

Switch- off voltage (Vdc) 1.027 1.111 1.196<br />

To ensure the devices power cycle is clean and predictable, the external supply input has a<br />

different switch-on and switch off threshold (hysteresis).<br />

9.1.3 Technical wireless data<br />

Wireless protocol WirelessHART TM Version 7.3<br />

Operating frequency<br />

Number of channels 15<br />

Channel separation<br />

RF power level (configurable)<br />

Range (10 dB), typical<br />

Range (0 dB) , typical<br />

Antenna<br />

2.4000 to 2.4835 GHz<br />

5 MHz<br />

10 dBm or 0 dBm<br />

100 m Indoors<br />

300 m Outdoors<br />

25 m Indoors<br />

200 m Outdoors<br />

Omnidirectional dipole, position adjustable in<br />

vertical plane.<br />

9.1.4 Communication per<strong>for</strong>mance<br />

Device Variables<br />

Typical Update Rate (seconds)<br />

Total 16<br />

Flow 2<br />

Pressure 8<br />

Temperature 16<br />

Power 16<br />

Energy 16<br />

3.3 V Supply 1<br />

9 V supply 1<br />

9. Technical data<br />

IM-P337-62 MI Issue 1 41


9.2 HART TM parameters<br />

Basic set-up<br />

Parameters in bold can be changed/edited.<br />

Parameter Explanation Format Default<br />

Tag<br />

Long tag<br />

(required)<br />

Date<br />

Descriptor<br />

Message<br />

Final<br />

Assembly<br />

Number<br />

Modbus<br />

polling<br />

mode<br />

Device flags<br />

Device<br />

profile<br />

Identifies the device in<br />

Wireless network. In most<br />

installations it indicates<br />

the mounting locations<br />

and function. The term<br />

originates from the physical<br />

tags that were attached to<br />

the device.<br />

Identifies the device in<br />

Wireless network. It is also<br />

used <strong>for</strong> setting up burst<br />

mode and event notification.<br />

This must be unique.<br />

Enables the user to enter a<br />

specific date to be stored,<br />

e.g. installation, last<br />

parameter change or last<br />

calibration date.<br />

Description of device<br />

location or location. Can be<br />

used by the user in any way.<br />

Text associated about the<br />

field device. Can be used by<br />

the user in any way.<br />

The manufacturer revision<br />

number. Do not change.<br />

Enables polling if meter is<br />

attached or disable if acting<br />

as a repeater. The device<br />

will reset and there will<br />

be a brief loss of wireless<br />

connection after a change<br />

to this parameter.<br />

List the special features<br />

in the device. Using the<br />

mouse, right click and select<br />

'display value' to see the<br />

flag status.<br />

A description of the type of<br />

device.<br />

8 alphanumeric<br />

characters max.<br />

(Packed ASCII<br />

String)<br />

32 alphanumeric<br />

characters max.<br />

(ISO Latin 1)<br />

mm / dd / yy<br />

(Gregorian<br />

calendar)<br />

16 alphanumeric<br />

characters max.<br />

(Packed ASCII<br />

String)<br />

16 alphanumeric<br />

characters max.<br />

(Packed ASCII<br />

String)<br />

WITEG<br />

IDX**<br />

Date of manufacture<br />

DEFLT<br />

DESCRIPTOR<br />

SPIRAX SARCO<br />

DEFAULT<br />

MESSAGE VOID<br />

0 to 16,777215 -<br />

Enabled or disabled<br />

0x00 to 0xFF<br />

(hexadecimal)<br />

-<br />

Enabled<br />

0x00<br />

WirelessHART<br />

Device<br />

42<br />

IM-P337-62 MI Issue 1


Parameter Explanation Format Default<br />

Total burst<br />

message<br />

Number<br />

of events<br />

supported<br />

Universal<br />

Revision<br />

Field device<br />

revision<br />

Software<br />

revision<br />

Hardware<br />

revision<br />

Device id**<br />

Reset<br />

Default Cal<br />

Data<br />

The total amount of burst<br />

messages supported by this<br />

device.<br />

Details the number of<br />

events supported.<br />

Revision of the universal<br />

device description.<br />

The revision of the firmware<br />

in the device.<br />

Revision of the<br />

corresponding software or<br />

firmware.<br />

Revision of the<br />

corresponding electronics.<br />

Manufactures unique<br />

identification number. This<br />

number is also the devices<br />

serial number and part of<br />

the devices MAC address.<br />

This must not be changed.<br />

Reset to factory default.<br />

Note 1: This does not affect<br />

the flowmeters calibration<br />

data.<br />

Note 2: Burst parameters<br />

needs to be restored<br />

manually.<br />

Note 3: There will be a brief<br />

loss of wireless connection.<br />

- 4<br />

1<br />

- 7<br />

- -<br />

- -<br />

- -<br />

101 to 16,777215 -<br />

- -<br />

IM-P337-62 MI Issue 1 43


9.3 Detailed set-up<br />

Parameters in bold can be changed / edited.<br />

Polling<br />

address<br />

Num req<br />

preams<br />

Num resp<br />

preams<br />

Burst mode<br />

The HART address. As the MAC<br />

address and long tag are used to<br />

identify the device, leave this as<br />

address 0.<br />

The number of preambles required<br />

from the master, requested by the<br />

device.<br />

The number of preambles sent in the<br />

response message from the device to<br />

the master.<br />

Enables the device to periodically<br />

transmit data <strong>with</strong>out the master<br />

requesting it. Four burst messages can<br />

be commissioned.<br />

0 to 63 0<br />

- 5<br />

5 to 20 5<br />

Off or<br />

WirelessHART<br />

enabled<br />

Burst 1:<br />

Enabled<br />

Burst 2: OFF<br />

Burst 3: OFF<br />

Burst 4: OFF<br />

44<br />

IM-P337-62 MI Issue 1


Detailed set-up (continued)<br />

Parameters in bold can be changed / edited.<br />

Burst<br />

command<br />

Update<br />

period<br />

Max update<br />

period<br />

Trigger<br />

mode<br />

Trigger<br />

class<br />

Trigger<br />

units<br />

Selects the type of data sent:<br />

1: Send the primary variable (total)<br />

and units (kg).<br />

3: Sends up to four selectable<br />

dynamic variables loop current.<br />

Note the device does not have<br />

4 - 20 mA output so 0.00 mA will<br />

be sent.<br />

9: Sends the value and status of up to<br />

eight device variables.<br />

33: Sends the value and units of up to<br />

four device variables.<br />

48: Send the status of the device.<br />

The time interval the data is sent.<br />

Note: For the minimum update period<br />

see Communication Per<strong>for</strong>mance<br />

Table.<br />

Used when window, rising, falling or<br />

on-change has been selected as a<br />

trigger mode (see below). If a burst has<br />

not been triggered <strong>with</strong>in this period,<br />

the device will automatically send a<br />

burst to the gateway. This time must<br />

be equal to or greater than the update<br />

period (see above).<br />

Selects when the data is to be<br />

transmitted to the master:<br />

Continuous:<br />

Every update period (see above).<br />

Window:<br />

New data is sent if it exceeds (either<br />

above or below) the previous value by<br />

the specified level (see below).<br />

Rising:<br />

New data is sent if it has risen above<br />

the specified level.<br />

Falling:<br />

New data is sent if it has fallen below<br />

the specified level.<br />

On-change:<br />

Not used.<br />

Defines the class of the data that is<br />

being sent<br />

Define the units of the data that is<br />

being sent.<br />

Cmd 1 PV,<br />

Cmd 3 Dyn vars /<br />

current,<br />

Cmd 9 Device<br />

vars w / status,<br />

Cmd 33 Device<br />

variables,<br />

Cmd 48 Read<br />

additional Device<br />

Status<br />

1, 2, 4, 8, 16,<br />

32, 60 to 3600<br />

seconds<br />

1, 2, 4, 8, 16,<br />

32, 60 to 3600<br />

seconds<br />

Continuous<br />

Window<br />

Rising<br />

Falling<br />

On-change (Not<br />

used)<br />

Various, see<br />

options listed<br />

Various, see<br />

options listed<br />

Cmd 9<br />

16<br />

16<br />

Continuous<br />

Mass<br />

kg<br />

IM-P337-62 MI Issue 1 45


Detailed set-up (continued)<br />

Parameters in bold can be changed / edited.<br />

Trigger<br />

level<br />

Process<br />

variable<br />

Event<br />

notification<br />

control<br />

Event<br />

notification<br />

re-try time<br />

Maximum<br />

update time<br />

Event<br />

debounce<br />

interval<br />

Device<br />

status<br />

mask<br />

Ext dev<br />

status<br />

mask<br />

The level at which a transmission is<br />

triggered.<br />

Available if cmd 9 or cmd 33 is<br />

selected. Enables the user to map the<br />

device variables onto the process /<br />

burst variables.<br />

Enables the device to notify the<br />

gateway of changes in condition and<br />

status. The time of the change is also<br />

send by the device.<br />

The time the device will continuously<br />

re-send the notification of the event<br />

until an acknowledgement has been<br />

received.<br />

If an event or condition has not<br />

occurred <strong>with</strong>in this time period, then<br />

the device will automatically send an<br />

event notification to the gateway. This<br />

period should be equal or greater than<br />

event notification re-try time. Occurs<br />

only once.<br />

The time an event or a condition<br />

must be present, be<strong>for</strong>e notification<br />

is sent. This prevents spurious event<br />

notifications.<br />

Enables the status flags to trigger and<br />

event notification<br />

• More status Available: More<br />

operational in<strong>for</strong>mation is available<br />

• Cold start: Power failure or device<br />

reset has occurred<br />

• Configuration Changed. The device<br />

has been re-configured<br />

• Field Device Malfunction. The device<br />

has detected a serious problem.<br />

• Maintenance required: Not used.<br />

• Device variable alert: Not used.<br />

• Critical Power failure: Not used.<br />

- 0<br />

Various, see<br />

device variables<br />

Off or Enable<br />

event notification<br />

on TDMA data<br />

link layer<br />

0.1, 0.25, 0.5, 1,<br />

2, 4, 8, 16, 32, 60<br />

to 3600 seconds<br />

0.1, 0.25, 0.5, 1,<br />

2, 4, 8, 16, 32, 60<br />

to 3600 seconds<br />

0.1, 0.25, 0.5, 1,<br />

2, 4, 8, 16, 32, 60<br />

to 3600 seconds<br />

total<br />

Off<br />

32 seconds<br />

60 seconds<br />

4 seconds<br />

- Unmasked<br />

- Unmasked<br />

46<br />

IM-P337-62 MI Issue 1


Detailed set-up (continued)<br />

Parameters in bold can be changed / edited.<br />

Device<br />

diagnostic<br />

status 0<br />

mask<br />

Device<br />

diagnostic<br />

status 1<br />

mask<br />

Device<br />

diagnostic<br />

status 2<br />

mask<br />

AO<br />

saturation<br />

mask<br />

Operation<br />

mode mask<br />

• Simulation active: Device is in<br />

simulation mode.<br />

• Non-Volatile memory failure: The<br />

memory has been corrupted.<br />

• Volatile memory error<br />

• Watchdog reset executed: A<br />

watchdog reset has occurred.<br />

• Voltage conditions out of range:<br />

Supply out of range.<br />

• Environmental conditions:<br />

Environmental condition exceeded<br />

• Electronic failure: Hardware problem.<br />

- Unmasked<br />

Reserved. - Unmasked<br />

• Capacity Denied: Network manager<br />

has denied the burst request burst,<br />

five times in a row.<br />

• Sub device list change.<br />

• Duplicate master detect.<br />

• Device Diagnostic Status 3 mask.<br />

• Bandwidth allocation pending: The<br />

device has requested a bandwidth<br />

and is waiting <strong>for</strong> a response.<br />

- Unmasked<br />

No used. - Unmasked<br />

Not defined. - Unmasked<br />

IM-P337-62 MI Issue 1 47


Device<br />

specific<br />

status 0<br />

mask (1 - 5<br />

not used)<br />

Network ID<br />

These are flags specific to this device:<br />

• 3.3 V out of range: Indicates the<br />

internal voltage rail is outs of<br />

specification.<br />

• 9 V out of range: Indicates the<br />

internal voltage rail is outs of<br />

specification.<br />

• Flash CRC invalid: Internal nonvolatile<br />

memory has been corrupted.<br />

• Modbus fault: The devices internal<br />

modbus communication is not<br />

functioning correctly. 3 out of 5 polls<br />

unsuccessful.<br />

• Mote unresponsive: The devices<br />

internal wireless module has stopped<br />

working.<br />

• Invalid Modbus slave ID: The<br />

flowmeters modbus slave ID is<br />

incorrect or has not been detected.<br />

Verify from the front panel the<br />

Modbus parameters are correct. See<br />

below.<br />

The identification number of the<br />

network. This must be the same as the<br />

gateway and network. See gateway<br />

setup.<br />

- Unmasked<br />

0 to 99999<br />

(decimal)<br />

12345<br />

Join key 1<br />

53504952<br />

Join key 2 An encryption key used to keep<br />

41585341<br />

private sent and received data during<br />

8 Character<br />

the joining process. It also serves as<br />

(hexadecimal)<br />

authentication to the security manager<br />

Join key 3 that the device belongs to this network.<br />

52434F52<br />

Join key 4<br />

554C455A<br />

Radio<br />

power<br />

Join mode<br />

Radio output signal strength 0 or 10 dB 10<br />

When to join to the network.<br />

Do not attempt<br />

to join, join now<br />

or attempt to join<br />

immediately on<br />

power up or reset<br />

Attempt<br />

to join<br />

immediately<br />

on power up<br />

or reset<br />

**(X is the allocated device-id)<br />

48<br />

IM-P337-62 MI Issue 1


9.3.1 Test device – Device status – Configuration change<br />

Cfg chng count<br />

Battery life<br />

remaining<br />

Power status<br />

The number of time the device configuration has been updated.<br />

Not used.<br />

Not used.<br />

9.3.2 Test device – Device status – Time<br />

Current date and<br />

time<br />

Set date and<br />

time<br />

Power status<br />

Current date and time based on the real-time clock calendar in<br />

the device. The device does not maintain these parameters whilst<br />

powered-down, there<strong>for</strong>e initially these will read 01:01:1900 and time<br />

since boot-up until the current date and time is obtained from the<br />

wireless network.<br />

The date and time the real-time clock calendar in the device was<br />

updated from the wireless network. Updated every 15 minutes.<br />

Not used.<br />

9.3.3 Test device - Wireless status<br />

Wireless mode<br />

Join status<br />

Advertisement<br />

count<br />

Neighbour count<br />

Join attempts<br />

Search time<br />

See below.<br />

This shows the joining status. With the left mouse key, select join<br />

status and select display value using the right key. Note this display<br />

is not dynamic, ie it will not update whilst window is open. Need to<br />

repeat this sequence to refresh window.<br />

Counts the number of advertisements received from the gateway.<br />

The number of neighbours the device is connected to.<br />

The number of attempts the device has made to connect to the<br />

network.<br />

Time the device has taken to listen to the first advertisement from the<br />

gateway.<br />

IM-P337-62 MI Issue 1 49


9.3.4 Test device - Wireless Status - Mode<br />

Idle<br />

Active search<br />

Negotiating<br />

Quarantined<br />

Operational<br />

Deep sleep<br />

Suspended<br />

Re-synching<br />

The devices wireless transceiver is not active. It has no knowledge of<br />

the WirelessHART TM network.<br />

Looking <strong>for</strong> other WirelessHART TM neighbours<br />

Connection parameters are being exchanged between the device and<br />

the gateway<br />

The device has successfully joined the network but only has a<br />

security clearance to talk <strong>with</strong> the Network Manager. It is not<br />

available or allowed to per<strong>for</strong>m data acquisition or control functions<br />

or otherwise communicate <strong>with</strong> the Gateway.<br />

The device can be accessed by host Applications via the Gateway.<br />

It is integrated in the system's operation.<br />

The device is not connected to the network.<br />

The gateway manager has prevented the device from connecting to<br />

the network.<br />

The device is listening <strong>for</strong> a network and trying to synchronise to a<br />

slot time and absolute slot number.<br />

9.4.5 Test device - Event Status<br />

Shows an event notification has been sent and whether it has been<br />

acknowledged.<br />

Event status • Configuration Changed Event pending.<br />

• Device Status Event Pending.<br />

• More Status Available Event Pending.<br />

Time first unack<br />

The time stamp of the first event still unacknowledged (hh:mm:ss).<br />

event triggered<br />

50<br />

IM-P337-62 MI Issue 1


9.4 HART TM device variables<br />

No Name Explanation Units<br />

0 Total Totalized value of mass flow of steam over time. kg<br />

1 Flow<br />

2 Pressure<br />

3 Temperature<br />

4 Power<br />

5 Energy<br />

6 3.3 V supply<br />

7 9 V supply<br />

Mass flow reading (pressure, density, dryness, and<br />

viscosity compensated). Derived by measured the<br />

<strong>for</strong>ce exerted by fluid on a fixed target or moving<br />

cone. The <strong>for</strong>ce is measured using a strain gauge<br />

attached to a beam.<br />

<strong>Steam</strong> pressure which is derived from a PRT<br />

mounted in the steam space. The correlation<br />

between saturated steam temperature and pressure<br />

is obtained using ASME standard steam tables<br />

(IAPWS-97 / ASME).<br />

<strong>Steam</strong> temperature which is derived from a PRT<br />

mounted in the steam space.<br />

Calculated using enthalpy obtained from ASME<br />

standard steam tables, multiplied by instantaneous<br />

mass flow.<br />

Calculated using enthalpy obtained from ASME<br />

standard steam tables, multiplied by the total mass<br />

flow.<br />

Internal voltage supply generated from the<br />

TEG10 input. This variable is used <strong>for</strong> fault finding<br />

purposes.<br />

Internal voltage supply generated from the<br />

TEG10 input. This variable is used <strong>for</strong> fault finding<br />

purposes.<br />

kg / h<br />

bar g<br />

°C<br />

kW<br />

kWh<br />

mV<br />

mV<br />

9.4.1 WirelessHART TM signal strength guide<br />

Signal strength (dBm)<br />

Greater than -50<br />

Quality<br />

Excellent<br />

-60 to -50 Good<br />

-70 to -60 Medium<br />

-80 to -70 Poor<br />

Less than -80<br />

Bad<br />

IM-P337-62 MI Issue 1 51


9.4.2 WirelessHART TM communication quality guide<br />

Packets received (%)<br />

Quality<br />

100 Excellent<br />

93 to 99 Good<br />

69 to 92 Medium<br />

31 to 68 Poor<br />

less than 31%<br />

Bad<br />

9.4.3 HART TM dynamic variables (fixed mapped)<br />

Device variable number Name Units<br />

PV 0 Total kg<br />

PV 1 Flow kg / h<br />

TV 2 Pressure bar g<br />

QV 3 Temperature °C<br />

9.4.4 Modbus parameters (differs from standard <strong>TVA</strong>)<br />

Baud rate 1200<br />

Serial Communication Protocol<br />

MODBUS<br />

Address 002<br />

9.4.5 Compliance<br />

CE mark<br />

EMC and LVD<br />

RTT&T<br />

FCC<br />

Con<strong>for</strong>ms to all relevant EU directives<br />

Electromagnetic Compatibility Directive 2004 / 08 / EG and<br />

Low Directive 93 / 68 / EEC – EN 61010-1:2010<br />

Interference emission: EN 61326-1: 2006, Class B<br />

Interference immunity: EN 61326-1: 2006, Table 2 (industrial<br />

environment) also EN 61326-2-3 :2006 and EN 61326-2-1:2006<br />

Radio and Telecommunications Terminal Directive 1999 / 5 / EC,<br />

EN 301489 - 17 v 2.1.1 (2009-05) using technical requirements of<br />

EN 301489 - 1 v 1.1 (2008-04)<br />

Con<strong>for</strong>ms to unintentional radiator requirements of FCC rules<br />

CFR47:July 2008 Parts 15.109, ClassB<br />

Please note:<br />

This unit must not be used outside the EU and USA<br />

52<br />

IM-P337-62 MI Issue 1


10. Settings table<br />

This Table shows all changeable options, and enables records to be made of any changes<br />

made to the pass code or other settings. It provides a convenient reference should future changes<br />

be required.<br />

Sub-menu<br />

Changeable Factory Customer Further<br />

settings settings settings changes<br />

Dryness fraction 1.0<br />

Basic data<br />

Units<br />

Nominal pressure<br />

Atmospheric pressure<br />

4-20 mA<br />

Source data<br />

Metric<br />

1.01 bar a<br />

Flow<br />

4 mA setting 0<br />

<strong>Flowmeter</strong><br />

Outputs 20 mA setting maximum<br />

@ 32 bar g<br />

Pulse<br />

Source data<br />

Number of pulses<br />

Pulse width<br />

ON<br />

Total<br />

1 per kg<br />

50 mS<br />

Error<br />

High<br />

Pass code 7452<br />

IM-P337-62 MI Issue 1 53


54<br />

IM-P337-62 MI Issue 1


IM-P337-62 MI Issue 1 55


56<br />

IM-P337-62 MI Issue 1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!