Detailed set-up (continued)<br />

Parameters in bold can be changed / edited.<br />

Trigger<br />

level<br />

Process<br />

variable<br />

Event<br />

notification<br />

control<br />

Event<br />

notification<br />

re-try time<br />

Maximum<br />

update time<br />

Event<br />

debounce<br />

interval<br />

Device<br />

status<br />

mask<br />

Ext dev<br />

status<br />

mask<br />

The level at which a transmission is<br />

triggered.<br />

Available if cmd 9 or cmd 33 is<br />

selected. Enables the user to map the<br />

device variables onto the process /<br />

burst variables.<br />

Enables the device to notify the<br />

gateway of changes in condition and<br />

status. The time of the change is also<br />

send by the device.<br />

The time the device will continuously<br />

re-send the notification of the event<br />

until an acknowledgement has been<br />

received.<br />

If an event or condition has not<br />

occurred <strong>with</strong>in this time period, then<br />

the device will automatically send an<br />

event notification to the gateway. This<br />

period should be equal or greater than<br />

event notification re-try time. Occurs<br />

only once.<br />

The time an event or a condition<br />

must be present, be<strong>for</strong>e notification<br />

is sent. This prevents spurious event<br />

notifications.<br />

Enables the status flags to trigger and<br />

event notification<br />

• More status Available: More<br />

operational in<strong>for</strong>mation is available<br />

• Cold start: Power failure or device<br />

reset has occurred<br />

• Configuration Changed. The device<br />

has been re-configured<br />

• Field Device Malfunction. The device<br />

has detected a serious problem.<br />

• Maintenance required: Not used.<br />

• Device variable alert: Not used.<br />

• Critical Power failure: Not used.<br />

- 0<br />

Various, see<br />

device variables<br />

Off or Enable<br />

event notification<br />

on TDMA data<br />

link layer<br />

0.1, 0.25, 0.5, 1,<br />

2, 4, 8, 16, 32, 60<br />

to 3600 seconds<br />

0.1, 0.25, 0.5, 1,<br />

2, 4, 8, 16, 32, 60<br />

to 3600 seconds<br />

0.1, 0.25, 0.5, 1,<br />

2, 4, 8, 16, 32, 60<br />

to 3600 seconds<br />

total<br />

Off<br />

32 seconds<br />

60 seconds<br />

4 seconds<br />

- Unmasked<br />

- Unmasked<br />

46<br />

IM-P337-62 MI Issue 1