3 Technical descriptions<br />
3.1 R 100 and R 101 Construction and function<br />
R 100 and R 101 are gas pressure regulators.<br />
Constant outlet pressure is ensured when the inlet<br />
pressure or flow capacity vary.<br />
The gas flows through the regulator housing in<br />
arrow direction. The main diaphragm is actuated<br />
via an impulse line from the outlet side by pressure.<br />
The required outlet pressure is adjusted at<br />
the spring.<br />
The valve remains open as long as the outlet pressure<br />
is below the set value. When reaching the set<br />
point the regulator valve closes.<br />
The measure work is directly mounted and operates<br />
independant from the inlet pressure.<br />
R 100 with double seat regulating valve.<br />
Nominal diameters: DN 50, 80, 100, 150, 200.<br />
R 101 with single seat valve<br />
Nominal diameters: DN 25, 40, 50, 65, 100.<br />
R 100-U Circulation regulators to limit pressure on<br />
gas pressure discharge plants. Gas flows back to<br />
the suction side of the compressor when the set<br />
opening pressure is exceeded.<br />
Nominal diameters: DN 50, 80, 100, 150, 200.<br />
R 100<br />
R 100-U<br />
4<br />
1<br />
2<br />
3<br />
4<br />
5<br />
7<br />
8<br />
7<br />
8<br />
9<br />
1<br />
2<br />
3<br />
R 100-UD negative pressure regulators control the<br />
gas throughput proportional to vacuum, f. e. of a<br />
gas motor or negative pressure gas appliance.<br />
Nominal diameters: DN 50, 80, 100, 150, 200.<br />
5<br />
R 101<br />
1<br />
2<br />
3<br />
4<br />
R 100-UD<br />
7<br />
8<br />
7<br />
8<br />
9<br />
4<br />
5<br />
6<br />
5<br />
3<br />
7<br />
8<br />
7<br />
8<br />
9<br />
7<br />
8<br />
9<br />
1 Pressure setting screw<br />
2 Setting spring<br />
3 Main diaphragm<br />
4 Vent connection<br />
5 Impulse connection<br />
6 Compensation<br />
diaphragm<br />
7 Regulator valve seat<br />
8 Single seat valve<br />
9 Cover<br />
4<br />
2<br />
1