DC UPS<br />

<strong>SITOP</strong> <strong>power</strong> · Standard 24 V<br />

Uninterruptible <strong>power</strong> <strong>supplies</strong><br />

■ Overview<br />

By combining a DC UPS module with at least one 24 V battery<br />

module and a <strong>SITOP</strong> <strong>power</strong> supply unit, longer <strong>power</strong> failures<br />

can be bridged without any interruption.<br />

This combination is used, for example, in machine tool manufacture,<br />

in the textile industry, with all types of production lines and<br />

filling systems, and in conjunction with 24 V industrial PCs. The<br />

negative effects which frequently result from <strong>power</strong> failures can<br />

thus be prevented.<br />

For nonstop use in the event of <strong>power</strong> failures, Siemens offers<br />

the uninterruptible <strong>power</strong> <strong>supplies</strong><br />

• DC UPS 6 A<br />

• DC UPS 15 A<br />

• DC UPS 40 A<br />

as well as the battery modules<br />

• 1.2 Ah<br />

• 3.2 Ah<br />

•7 Ah<br />

•12 Ah<br />

• 2.5 Ah (high-temperature battery).<br />

9<br />

■ Selection table for battery modules with <strong>power</strong> failure buffer times<br />

Load current Battery module 1.2 Ah Battery module 3.2 Ah Battery module 7 Ah<br />

(6EP1935-6MC01) (6EP1935-6MD11) (6EP1935-6ME21)<br />

Note:<br />

• The <strong>power</strong> failure buffer times are based on the discharge period<br />

of the completely charged battery module down to a battery<br />

voltage of 21 V; ambient temperature 25 °C.<br />

• With the DC UPS 40 A module, high electronically limited peak<br />

currents (120 A for approx. 12 ms, up to 40 A for several minutes<br />

depending on the battery capacity) are automatically delivered<br />

in the event of increased load current requirements<br />

(e.g. when switching on incandescent lamps, contactors with<br />

DC autotransformer winding, DC motors, DC/DC converters,<br />

electronic modules with high input capacitance). To achieve<br />

this, at least two battery modules of 7 Ah or more must be connected<br />

in parallel.<br />

Battery module 12 Ah<br />

(6EP1935-6MF01)<br />

1 A 30 min 2.5 h 6 h 10 h 2 h<br />

2 A 11 min 45 min 2.5 h 4 h 45 min<br />

4 A 2 min 20 min 45 min 2.5 h 20 min<br />

6 A 1 min 10 min 30 min 1 h 13 min<br />

8 A - 4 min 20 min 40 min 9 min<br />

10 A - 1.5 min 15 min 30 min 7 min<br />

12 A - 1 min 10 min 25 min 5.5 min<br />

14 A - 50 s 8 min 20 min 4.5 min<br />

16 A - 40 s 6 min 15 min 4 min<br />

20 A - - 2 min 11 min -<br />

Battery module 2.5 Ah<br />

(6EP1935-6MD31)<br />

• Following a <strong>power</strong> failure, the battery module is automatically<br />

disconnected from the loads electronically and rapidly recharged<br />

at 0.2/0.4 A (DC UPS 6 A module), at 0.35/0.7 A<br />

(DC UPS 15 A module) or at 2 A (DC UPS 40 A module) (V/I<br />

characteristic with 27 V or 27.3 V end-of-charge voltage).<br />

■ DC UPS software<br />

The DC UPS 6 A and 15 A modules are optionally available with<br />

a serial interface or USB interface. All relevant messages concerning<br />

the status of the DC UPS can then be sent to a PC (e.g.<br />

SIMATIC PC). The <strong>SITOP</strong> DC UPS software, with which the signals<br />

sent from the DC UPS module can be processed further on<br />

the PC, is very easy to use. In monitoring mode, the statuses of<br />

the DC UPS module are visualized on the PC. The safe shutdown<br />

in the event of a <strong>power</strong> failure and the automatic restart of the PC<br />

are supported. It is also possible to freely define the responses<br />

to the various operating states of the DC UPS module, permitting<br />

extremely flexible incorporation into many different applications.<br />

The software executes under the WinNT 4.0, Win2000 and<br />

WinXP operating systems. It is available as freeware on the<br />

<strong>SITOP</strong> Internet site for free downloading.<br />

Monitoring and configuration windows of the <strong>SITOP</strong> UPS software<br />

9/2<br />

Siemens KT<strong>10.1</strong> · <strong>2004</strong>