<strong>SITOP</strong> <strong>power</strong> · Standard 24 V<br />

Uninterruptible <strong>power</strong> <strong>supplies</strong><br />

Battery module 3.2 Ah<br />

9<br />

■ Overview<br />

• Battery module for DC UPS module 6 A and 15 A<br />

• Contains two maintenance-free, sealed lead-acid batteries<br />

from the same batch fitted in a holder and connected in series<br />

• Includes battery fuse holder and terminals<br />

• Low self-discharge rate of approx. 3 % per month (at +20 °C)<br />

■ Technical specifications<br />

Battery module 3.2 Ah<br />

Order No.<br />

6EP1 935-6MD11<br />

Battery type, charging current/ Maintenance-free, sealed leadacid<br />

batteries 1)<br />

charging voltage<br />

Recommended end-of-charge voltage (standby use)<br />

• For +25 °C battery temperature 27.0 V DC<br />

• For other battery temperatures 27.8 V for +10 °C;<br />

27.3 V for +20 °C;<br />

26.8 V for +30 °C;<br />

26.7 V for +35 °C;<br />

26.6 V for +40 °C<br />

Recommended charging current Max. 0.8 A<br />

Protection<br />

Short-circuit protection<br />

Battery fuse 15 A/32 V<br />

(FK2 flat fuse + holder)<br />

Battery protection<br />

Valve control<br />

Safety<br />

Protective class<br />

Class III<br />

UL/cUL (CSA) approval<br />

UL/cUL recognized (UL1778,<br />

CSA 22.2 No. 107.1-95),<br />

File E219627<br />

Degree of protection (EN 60529)<br />

Operating specifications<br />

Ambient temperature range<br />

Transportation and storage temperature<br />

range<br />

Self-discharge rate<br />

IP00<br />

+5 to +40 °C with natural<br />

convection<br />

-20 to +50 °C<br />

Approx. 3 % per month at a<br />

battery temperature of 20 °C<br />

(increased value at higher temperature)<br />

Service life<br />

The service life of the chemical lead-acid batteries (reduction to 50 % of<br />

original capacity) depends on the battery temperature as follows:<br />

At +20 °C<br />

Approx. 4 years<br />

At +25 °C<br />

Approx. 3.5 years<br />

At +30 °C<br />

Approx. 3 years<br />

At +35 °C<br />

Approx. 2.5 years<br />

At +40 °C<br />

Approx. 2 years<br />

At +45 °C<br />

Approx. 1.5 years<br />

At +50 °C<br />

Approx. 1 year<br />

Mechanical specifications<br />

Connection<br />

1 terminal each for 0.08 to<br />

2.5 mm 2 for + BAT and - BAT<br />

Supplied accessories<br />

Accessory pack with FK2 fuse<br />

15 A<br />

Dimensions (W x H x D) in mm Approx. 190 x 151 x approx. 82<br />

Weight<br />

Approx. 3.2 kg<br />

Mounting<br />

Snap-mounting on DIN rail<br />

EN 50022-35x15/7.5 or keyhole<br />

mounting for hanging in M4<br />

screws<br />

1) For storage, installation and operation of the lead-acid batteries, the<br />

appropriate DIN/VDE regulations or the country-specific directives (e.g.<br />

VDE 0510 Part 2/EN 50272-2) must be observed. The battery location must<br />

be sufficiently ventilated, potential ignition sources must be at least 50 cm<br />

away.<br />

9/16<br />

Siemens KT<strong>10.1</strong> · <strong>2004</strong>