<strong>SITOP</strong> <strong>power</strong><br />

Alternative voltages<br />

■ Overview <strong>SITOP</strong> <strong>power</strong> flexi 120 W <strong>SITOP</strong> <strong>power</strong> dual 15 V <strong>SITOP</strong> modular 48 V/20 A<br />

■ Application<br />

The <strong>power</strong> supply unit with<br />

adjustable output voltage<br />

from 3 V to 52 V; suitable for all<br />

applications where a special<br />

voltage deviating from 24 V is<br />

required.<br />

The industry-standard <strong>power</strong><br />

supply unit with two 15 V outputs<br />

which can be connected<br />

in parallel or in series; can be<br />

used, for example, for supplying<br />

electronic loads with<br />

±15 V.<br />

The modular 48 V <strong>power</strong> supply<br />

unit with three-phase widerange<br />

input for <strong>power</strong>ful loads<br />

which are <strong>power</strong>ed by twice the<br />

voltage instead of the usual<br />

24 V.<br />

10<br />

■ Technical specifications<br />

<strong>Power</strong> supply, type 3 to 52 V/2 to 10 A 2 x 15 V/3.5 A 48 V/20 A<br />

Order No. 6EP1 353-2BA00 6EP1 353-0AA00 6EP1 457-3BA00<br />

Input Single-phase AC Single-phase AC Three-phase AC<br />

Rated voltage V in rated<br />

120/230 V AC<br />

120 to 230 V AC<br />

400 to 500 V 3 AC<br />

Settable using wire jumper<br />

wide-range input<br />

wide-range input<br />

Voltage range 85 to 132 V/170 to 264 V AC 93 to 264 V AC 320 to 550 V<br />

(startup from V in > 340 V)<br />

Overvoltage strength 2.3 x V in rated , 1.3 ms Surge voltage acc. to<br />

2.3 x V in rated , 1.3 ms<br />

EN 61000-6-2 Table 4<br />

Mains buffering at I out rated<br />

> 10 ms at V in = 93/187 V<br />

> 10/40 ms at V in = 120/187 V > 6 ms at V in = 400 V<br />

(P out = 120 W)<br />

Rated line frequency; range 50/60 Hz, 47 to 63 Hz 50/60 Hz; 47 to 63 Hz 50/60 Hz; 47 to 63 Hz<br />

Rated current I in rated 2.2/0.9 A 1.9 to 1.15 A 2.2 A (V in = 400 V)<br />

Inrush current limitation (+ 25 °C) < 32 A < 30 A, typ. 3 ms < 70 A<br />

I 2 t < 0.8 A 2 s < 3 A 2 s < 2.8 A 2 s<br />

Integrated line-side fuse T3.15 A/250 V (not accessible) T4 A/250 V (not accessible) none<br />

Recommended circuit-breaker From 6 A Characteristic C<br />

From 10 A Characteristic C or Required: 3-pole coupled circuit-breaker<br />

(IEC 898) in mains supply line<br />

from 16 A Characteristic B<br />

10 to 16 A Char. C<br />

or motor circuit-breaker<br />

3RV1021-1DA10, setting 3 A<br />

Output Stabilized, floating direct voltage Stabilized, floating direct voltage Stabilized, floating direct voltage<br />

Rated voltage V out rated 3 to 52 V DC 2 x 15 V DC 48 V DC<br />

Total tolerance ± 1 % ± 2 % ± 3 %<br />

• Stat. mains compensation Approx. 0.1 % Approx. 0.2 % Approx. ± 0.1 %<br />

• Stat. load compensation Approx. 0.2 % Approx. 0.2 % Approx. ± 0.2 %<br />

Sense line connection<br />

Yes, maximum voltage control - -<br />

0.5 V per line<br />

Residual ripple (clock frequency: < 50 mV pp < 50 mV pp (typ. 20 mV pp ) < 100 mV pp<br />

approx. 50 kHz)<br />

Spikes (bandwidth: 20 MHz) < 100 mV pp < 150 mV pp (typ. 150 mV pp ) < 200 mV pp<br />

Setting range<br />

3 to 52 V, via potentiometer or 14.5 to 17 V 42 to 56 V (max. 960 W)<br />

analog control voltage signal<br />

0 to 2.5 V<br />

Status display Green LED for 24 V O.K. Green LED for V out >10 V<br />

Green LED for 48 V O.K.<br />

Signalling<br />

Continued on page 10/3.<br />

<strong>Power</strong> Good via relay contact,<br />

current monitor signal<br />

0 to 2.5 V<br />

(summation display)<br />

- possible using signalling module<br />

(6EP1 961-3BA10)<br />

<strong>Power</strong> ON/OFF behavior No overshoot of V out (soft start) Overshoot of V out < 3% No overshoot of V out (soft start)<br />

Starting delay/voltage rise < 3 s/typ. 80 ms < 1 s < 2.5 s/< 500 ms<br />

Rated current I out rated 2 to 10 A (max. 120 W) 2 x 3.5 A 20 A<br />

Current range<br />

• up to + 45 °C 0 to 10 A (max. 120 W) 2 x 0 to 3.5 A 0 to 20 A<br />

• up to + 60 °C 0 to 10 A (max. 120 W) 2 x 0 to 2.5 A 0 to 20 A<br />

10/2<br />