SINEAX U553<br />

SINEAX U554<br />

Transducer for alternating voltage<br />

To measure sinusoidal or distorted alternating voltages,<br />

with power supply connection.<br />

Customer benefit<br />

• RMS value measurement up to crest factor 6<br />

• Possibility of adjusting the maximum value of the measuring range on site<br />

• Standard as GL (Germanischer Lloyd), suitable for ships<br />

• Can also be used for 400 Hz systems<br />

Technical data<br />

Meas. input: Different ranges from 0…100/√3 to 0…500 V or customized<br />

0…20 V to 0…690 V, maximum 400 V nominal value of the system against earth<br />

Nominal frequency 50/60 Hz or 400 Hz<br />

Maximum value of the measuring range can be set via potentiometer<br />

(approx. ±15%)<br />

Meas. output: 0…20 mA, 4…20 mA, 0…10 V or customized<br />

0…1 to 0…20 mA or 0.2…1 to 4…20 mA or<br />

0…1 to 0…10 mA or 0.2…1 to 2…10 V<br />

Setting time 50 ms or 300 ms<br />

Accuracy: Class 0.5 at 15…30 °C<br />

Power supply: 24 –60 V AC/DC or 85–230 V AC/DC (also from measurement input) or<br />

24 V AC / 24–60 V DC, connection on the low-voltage side<br />

H x W x D: 69.1 x 70 x 112.5 mm<br />

Transducer for alternating voltage<br />

To measure sinusoidal or distorted alternating voltages, with power supply connection.<br />

Customer benefit<br />

• RMS value measurement up to crest factor 6<br />

• The measuring range which is of interest can be highlighted<br />

Technical data<br />

Meas. input: Minimum value 0 V, maximum value of the measuring range E3 = 20…690 V,<br />

Step point 0.1 · E3…0.9 · E3<br />

Nominal frequency 50/60 Hz or 400 Hz<br />

Meas. output: Maximum value A3 = 1 mA, 5 mA, 10 mA, 20 mA, 10 V or customised 1…20 mA<br />

or 1…10 V<br />

A3<br />

A2<br />

A<br />

A1<br />

E<br />

E1 E2 E3<br />

A3<br />

A2<br />

A<br />

A1<br />

E<br />

E1 E2 E3<br />

E1 = 0 E1 = 0<br />

0,1 · E3 ≤ E2 ≤ 0.9 · E3 0.1 · E3 ≤ E2 ≤ 0.9 · E3<br />

A1 = 0 A1 = 0.2 · A3<br />

A1 ≤ A2 ≤ 0.9 · A3 A1 ≤ A2 ≤ 0.9 · A3<br />

<strong>Camille</strong> <strong>Bauer</strong><br />

Voltage Transducers<br />

Accuracy: Class 0.5 at 15…30 °C<br />

Power supply: 24 –60 V AC/DC or 85–230 V AC/DC (also from measurement input)<br />

24 V, 110 V, 115 V, 120 V, 230 V, 400 V AC 50/60 Hz or<br />

24 V AC / 24–60 V DC, connection on the low-voltage side<br />

H x W x D: 69.1 x 70 x 112.5 mm<br />