<strong>Camille</strong> <strong>Bauer</strong><br />
Displaying Power Meters, „All in one“<br />
Multifunctional power meter with display<br />
The display<br />
The APLUS offers all which is requested from a device with display:<br />
• Excellent legibility from almost any distance and each angle<br />
• Clear and explicit display of measured data<br />
• Free com<strong>position</strong> of measurement displays<br />
• Free allocation of alarms to status LED’s<br />
• Free definable plaintext display for alarming<br />
• Preference display and roll mode<br />
Free com<strong>position</strong> of the required functions<br />
The APLUS basic unit is already comprehensively equipped with a relay output for alarming, a digital<br />
output, e.g. for pulse output, and a digital input, e.g. for tariff switching.<br />
For applications where this is not sufficient, the optional I/O extensions 1 or 2 are available:<br />
• I/O extension 1: 2 relays, 4x ±20 mA (galvanically isolated), 2 digital I/O’s 12/24 V DC<br />
• I/O extension 2: 2 relays, 6 digital I/O’s 12/24 V DC<br />
The digital I/Os of the I/O extensions can be configured individually as inputs or outputs.<br />
Parametrization, service and measurement acquisition<br />
These functions are facilitated by the included CB-Manager software. A security system can be<br />
activated to restrict the access to device data. This way e.g. changing a limit value via display can be<br />
locked, but a setting via configuration could still be possible.<br />
A Modbus/RTU interface (RS-485) or an optional Ethernet interface with Modbus/TCP protocol are<br />
available for communication.<br />
Data logger (option)<br />
The optional data logger can be used for the non-volatile storage of measured value progressions<br />
(e.g. load profiles), events, alarms, meter readings and disturbance recordings. The SD card used<br />
for storage may be replaced on-site. For a tabular or graphical analysis of the recorded data the CB-<br />
Analyzer software is available.<br />
Technical data<br />
Measuring input :Nominal voltage up to 693 V (PH-Ph), nominal <strong>current</strong> up to 5 A,<br />
override up to 7.5 A programmable, nominal frequency 50/60 Hz<br />
Systems: Single-line AC, split phase, 3/4 wire rotary <strong>current</strong> balanced /<br />
unbalanced load, rotating clockwise and counter-clockwise<br />
Energy meter: Active energy incoming+outgoing, reactive energy incoming+<br />
outgoing+inductive+capacitive for measured system as well as<br />
incoming active and reactive energy per phase, max. 7 meters<br />
for external variables via digital inputs. High and low tariff for all<br />
meters, if tariff switching is active.<br />
Accuracy: Voltage and <strong>current</strong> 0.1%, power and voltage asymmetry 0.2%<br />
harmonics, THD and TDD 0.5%, power factor ±0.1°, frequency ±0.01 Hz<br />
Active energy Class 0.5S (EN 62053-22), reactive energy Class 2 (EN 62053-23)<br />
Analogue outputs ±0.2%<br />
Dimensions: 96 x 96 x 105 mm<br />
Accessories<br />
Article No. Description<br />
163 189 Interface converter USB RS485<br />
Part of the scope of delivery<br />
For CB-Manager configuration software see Page 61<br />
For CB-Analyzer analysis software for logger and lists see Page 61<br />
35