SINEAX F534 Transducer for frequency<br />

<strong>Camille</strong> <strong>Bauer</strong><br />

Frequency and Phase Angle<br />

For the conversion of the frequency of a system into a proportional DC signal.<br />

Customer benefit<br />

• Determination of the progression and stability of the fundamental frequency of an electric system<br />

• Standard as GL (Germanischer Lloyd), suitable for ships (only SINEAX design)<br />

• Output signal useable for indication, registration, monitoring and control<br />

• Safety by galvanic isolation and shock-proof terminals (IP20)<br />

Application<br />

Frequency is an important command variable of electric systems or power distribution systems.<br />

Variations of the system frequency particularly occur in system overload or underload situations. They<br />

must be immediately recognised in order to take countermeasures in time. Frequency fluctuations<br />

impair the performance of connected machines disproportionately. However, this can also be utilised<br />

in drive <strong>engineering</strong> to improve start and speed characteristics e.g. in frequency converters where<br />

the frequency is employed as a control variable.<br />

The frequency is measured via a zero-phase voltage or voltage between phases which can be<br />

directly connected via a converter. The instrument is also suited to distorted voltages with dominant<br />

fundamental waves. A direct <strong>current</strong> signal proportional to the measured frequency is available at the<br />

output.<br />

Technical data<br />

Meas. input: Input nominal voltage 10…230 V or 230…690 V<br />

Meas. range: 45…50…55 Hz, 47…49…51 Hz, 47.5…50…52.5 Hz, 48…50…52 Hz,<br />

58…60…62 Hz<br />

or customised between 10 and 1500 Hz<br />

Meas. output: Maximum output value 0…20 mA, 4…20 mA, 0…10 V or<br />

customised in the 1…20 mA or 1…10 V range<br />

Output signal unipolar, symmetrically bipolar or live-zero<br />

Setting time selectable 2, 4, 8 or 16 cycles of the input frequency<br />

Accuracy: Class 0.2 at 15…30 °C<br />

Power supply: 24 –60 V AC/DC or 85–230 V AC/DC (also internally from measurement input)<br />

24 V AC / 24–60 V DC, connection on the low-voltage side<br />

H x W x D: 69.1 x 70 x 112.5 mm (SINEAX),<br />

assembly on top-hat rail (35 x 15 mm or 35 x 7.5 mm)<br />