SINEAX F534 Transducer for frequency<br />
<strong>Camille</strong> <strong>Bauer</strong><br />
Frequency and Phase Angle<br />
For the conversion of the frequency of a system into a proportional DC signal.<br />
Customer benefit<br />
• Determination of the progression and stability of the fundamental frequency of an electric system<br />
• Standard as GL (Germanischer Lloyd), suitable for ships (only SINEAX design)<br />
• Output signal useable for indication, registration, monitoring and control<br />
• Safety by galvanic isolation and shock-proof terminals (IP20)<br />
Application<br />
Frequency is an important command variable of electric systems or power distribution systems.<br />
Variations of the system frequency particularly occur in system overload or underload situations. They<br />
must be immediately recognised in order to take countermeasures in time. Frequency fluctuations<br />
impair the performance of connected machines disproportionately. However, this can also be utilised<br />
in drive <strong>engineering</strong> to improve start and speed characteristics e.g. in frequency converters where<br />
the frequency is employed as a control variable.<br />
The frequency is measured via a zero-phase voltage or voltage between phases which can be<br />
directly connected via a converter. The instrument is also suited to distorted voltages with dominant<br />
fundamental waves. A direct <strong>current</strong> signal proportional to the measured frequency is available at the<br />
output.<br />
Technical data<br />
Meas. input: Input nominal voltage 10…230 V or 230…690 V<br />
Meas. range: 45…50…55 Hz, 47…49…51 Hz, 47.5…50…52.5 Hz, 48…50…52 Hz,<br />
58…60…62 Hz<br />
or customised between 10 and 1500 Hz<br />
Meas. output: Maximum output value 0…20 mA, 4…20 mA, 0…10 V or<br />
customised in the 1…20 mA or 1…10 V range<br />
Output signal unipolar, symmetrically bipolar or live-zero<br />
Setting time selectable 2, 4, 8 or 16 cycles of the input frequency<br />
Accuracy: Class 0.2 at 15…30 °C<br />
Power supply: 24 –60 V AC/DC or 85–230 V AC/DC (also internally from measurement input)<br />
24 V AC / 24–60 V DC, connection on the low-voltage side<br />
H x W x D: 69.1 x 70 x 112.5 mm (SINEAX),<br />
assembly on top-hat rail (35 x 15 mm or 35 x 7.5 mm)<br />
13