Relay coupler – overview<br />

Relay coupler with plugged relay Derating curve Notes on application<br />

Relay coupler<br />

K<br />

Relay couplers with plugged relay have<br />

only limited suitability for use in a highly<br />

oscillating environment. Preference should<br />

be given to relay couplers with soldered<br />

relays.<br />

The transition resistance of the relay contacts<br />

is a key factor contributing to temperature<br />

increase inside the relay modules.<br />

This relationship is illustrated by a<br />

derating curve, defined as the function of<br />

the permissible current plotted against the<br />

ambient temperature.<br />

The permissible current (Curve a) is determined<br />

for the following operating conditions:<br />

– Continuous operation<br />

– Rated input voltage + 10 percent<br />

– Several relay modules working under<br />

load, mounted horizontally in rows on<br />

mounting rail, without any spacing<br />

If the modules are mounted with a spacing<br />

> 20 mm, this results in a higher current<br />

load (Curve b). Curve b also shows<br />

the maximum values for switching or<br />

short-time operation in horizontally<br />

mounted state.<br />

The key data of the triggering device must<br />

be precisely adhered to when using UC<br />

versions in DC circuits. As a result of their<br />

pre-circuitry, UC versions take up larger<br />

quantities of current. The internal current<br />

limit of standard initiators can mean that<br />

the triggered relay couplers are not<br />

switched through.<br />

Relay couplers with 24 V AC/DC input are<br />

not suitable for triggering by initiators;<br />

purely DC versions are recommended for<br />

these applications.<br />

RC combination<br />

Long leads are subject to greater electrical<br />

and electromechanical influences. This<br />

may cause malfunctions and even failure<br />

of the relay modules. One possible remedy<br />

is to insert an RC combination to filter<br />

out the interference. RC combinations are<br />

available for all common relay couplers,<br />

as pluggable (PLUGSERIES) solutions or<br />

WDU 12C and DKU 12C terminals.<br />