Overvoltage protection for energy distribution systems<br />

Sold by <strong>AA</strong> <strong>Electric</strong> 1-800-237-8274 Lakeland, FL • Lawrenceville, GA • Greensboro, NC • East Rutherford, NJ www.A-Aelectric.com<br />

Protection in the TN-S-system<br />

Protection in the TT system<br />

In contrast to normal air gap protectors, Weidmüller’s air gap<br />

protectors PU 1 TSG+ and PU 1 TSG work with electronic<br />

triggering. This triggers the air gap protector so early that the<br />

following arrestor is relieved (PucX). Decoupling to downstream<br />

arrestors in class II (C) is not necessary because triggered<br />

air gap protectors work with low operating voltage.<br />

One difference between PU 1 TSG+ and PU1 TSG is the follow<br />

current interruption. PU 1 TSG+ distributes the arc voltage<br />

to several chambers; as soon as the sum of the arc voltages<br />

of the different chambers is higher than the current mains voltage,<br />

the follow current is interrupted. In PU1 TSG, the follow<br />

current is interrupted in the next zero crossing of the mains<br />

voltage.<br />

Overvoltage protection<br />

I<br />

I.5