06.09.2014 Views

A guide to VE configure - Zanshin

A guide to VE configure - Zanshin

A guide to VE configure - Zanshin

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

General settings<br />

2. Three-phase setting<br />

3. System frequency setting<br />

4. The scale division for shore current limit on a connected remote panel<br />

depends on the number of ‘slaves’.<br />

5. Set the sensitivity of frequency measurement.<br />

6. Connection between N and PE during inverter operation<br />

7. Voltage limits at which feedback relay opens/closes. Also, charger s<strong>to</strong>ps at<br />

lower limit.<br />

8. Determines whether the Multi should be critical of the dis<strong>to</strong>rtion in the<br />

supply waveform.<br />

9. Maximum shore current setting (is overruled by the remote panel if<br />

connected)<br />

10. Setting for use with ‘small’ genera<strong>to</strong>r<br />

Explanation<br />

1. If multiple devices are connected in parallel, a phase shift can be selected <strong>to</strong> create 2-, 3- or splitphase<br />

configuration. The first unit in a multiple-phase system must be set as the LEADER; the others<br />

must be set <strong>to</strong> the desired phase shift. If multiple units are then also connected in parallel for each<br />

phase, no setting should be made on the additional units!<br />

2. Alters the output frequency setting for the inverter.<br />

3. Number of slaves indicates that there are units connected in parallel. To maintain the shore current<br />

limit scale on the remote control for the installation as a whole, the setting must be divided between<br />

the number of parallel units. If more shore current is available than the scale allows, then an<br />

alternative value may be entered. In this case, the scale on the remote is no longer correct and it is<br />

possible <strong>to</strong> draw more current from shore.<br />

4. This setting is used <strong>to</strong> indicate whether it is necessary for the input frequency <strong>to</strong> be exactly 50 or 60<br />

Hz. This is a setting that is primarily used in conjunction with genera<strong>to</strong>rs (speed may not always be<br />

stable) <strong>to</strong> prevent the Multi from rejecting the input supply<br />

5. To permit use of a Residual Current Device (RCD). During operation as and inverter, a connection<br />

between PE and N is required.<br />

6. These are the limits at which the unit will accept or reject the supply. If the input voltage drops below<br />

the set value of the lower limit, the charger output will be reduced <strong>to</strong> the minimum <strong>to</strong> prevent further<br />

reduction of the voltage.<br />

7. If waveform detection is deselected, this au<strong>to</strong>matically activates the function preventing the lower<br />

voltage limit from being exceeded with heavy start-up loads! (previously labelled ‘Allow inrush current’)<br />

8. This setting is only active if no system panel is installed. Also keep number 3 in mind!<br />

9. If an inverter-genera<strong>to</strong>r is used, such as the HONDA EU series, the shore current setting will be<br />

dynamically reduced (following a period of low current consumption) <strong>to</strong> compensate for the engine<br />

reaction time when higher loads are activated.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!