RF Fans<br />

Accessories<br />

Air Pressure Loss of VS Low-Pressure Dampers<br />

Δp - Air pressure loss [Pa]<br />

22,2<br />

5<br />

<br />

4<br />

11,1<br />

3<br />

VS 180<br />

<br />

VS 250<br />

V - Air flow rate [m 3 /h]<br />

5000<br />

1<br />

<br />

2<br />

VS 315<br />

VS 400<br />

VS 560<br />

VS 630<br />

v - Air flow velocity in the damper‘s cross-section VS [m/s]<br />

The nomogram of pressure losses is valid for all VS dampers.<br />

For the selected air flow rate , the air flow velocity in the free<br />

damper‘s cross-section can be read in the lower graph, and<br />

then the corresponding VS damper‘s air pressure loss at the<br />

known velocity can be determined in the upper part .<br />

Example: At an air flow rate of 5,000 m3/h, the velocity of the air<br />

flow in the damper will be 11.1 m/s. The air pressure loss of the<br />

VS 400 damper for the above-mentioned air flow rate will be<br />

22 Pa.<br />