7.1.<br />
Safety valve for burner<br />
control<br />
Field of application<br />
Safety <strong>valves</strong> are fitted in the supply or<br />
return of the oil line for use in oil burner<br />
installations.<br />
Design<br />
Two versions of safety valve are mounted<br />
on the block.<br />
Use as supply valve: the valve is normally<br />
open and is tight up to 30 bar.<br />
Use as return valve: the valve is normally<br />
closed and is tight up to 30 bar<br />
in the direction of the safety shut-off.<br />
At the same time, the valve operates<br />
as a check valve and opens starting<br />
with a pressure of 0.15 bar in the return<br />
direction.<br />
If a burner or installation is switched<br />
off, the return valve operates as a<br />
check valve (spring-controlled). Oil<br />
which is not used flows unhindered<br />
back into the tank. The supply valve<br />
shuts off in the safety shut-off (both<br />
<strong>valves</strong> are energized). No oil is routed<br />
to the burner and the oil in the line at<br />
the burner end is discharged via the<br />
return valve.<br />
Characteristics<br />
■ Body material: brass, stainless steel<br />
■ Seal material: brass, stainless steel<br />
■ Seal material: FPM, PTFE, graphite<br />
■ Media: neutral gases and fluids;<br />
oils and hydraulic fluids<br />
■ Media temperature: 10 to +140 °C<br />
■ Ambient temperature: max. +55 °C<br />
■ Operating voltage: 110 V, 50 Hz<br />
■ Voltage tolerance: ±10%<br />
■ Duty cycle: continuous operation<br />
■ Electrical connection: tag connectors<br />
in accordance with DIN 43<br />
650 A for Type 2508 appliance<br />
plug socket<br />
■ Installation position: any position,<br />
preferably actuator pointing upwards<br />
■ Type of protection: IP 65 with<br />
appliance plug socket<br />
■ Upstream filter: the use of the <strong>valves</strong><br />
is allowed only with upstream<br />
strainer (mesh aperture less than<br />
0.5 mm)<br />
Supply <strong>valves</strong><br />
P U<br />
Burner<br />
Tank<br />
Return flow<br />
Return <strong>valves</strong><br />
Components/Function Quantity Typical parameters<br />
Supply valve 1 2/2-way valve ; WW B (normally open)<br />
DN 13 mm, flow rate = 2.0 m 3 /h<br />
Pressure range = 1 to 30 bar; back-pressure 1 bar<br />
Return valve 1 2/2-way valve; WW A (normally closed)<br />
DN 13 mm, flow rate = 2.0 m 3 /h<br />
Pressure range = 1 to 30 bar; back-pressure 1 bar