Three-phase induction motor softstarter - Teledyne Relays
Three-phase induction motor softstarter - Teledyne Relays
Three-phase induction motor softstarter - Teledyne Relays
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Series EMC48S50-03<br />
POWER<br />
INTERNAL SUPPLY ELECTRICAL CHARACTERISTICS<br />
Characteristics<br />
Labels<br />
Values<br />
(Given at 20° C ambient unless otherwise specified)<br />
Concerned Terminals<br />
3L2 & 5L3<br />
Voltage<br />
Range<br />
Consumption<br />
Ve<br />
Is<br />
200-480Vac<br />
1mA typical<br />
Frequency<br />
Range<br />
f 40-65Hz<br />
Turn-On Time<br />
tm<br />
100ms<br />
Remarks<br />
See Fig. 1<br />
POWER SIDE CHARACTERISTICS<br />
Characteristics<br />
Labels<br />
Values<br />
(Given at 20° C ambient unless otherwise specified)<br />
Concerned Terminals<br />
1L1, 2T1, 3L2, 4T2, 5L3, 6T3<br />
Max Power of the Motor<br />
@400VAC Star Wiring (Y)<br />
Pn<br />
11kW<br />
Max Power of the Motor<br />
@230VAC Star Wiring (Y)<br />
Pn<br />
6.4kW<br />
Max Power of the Motor<br />
@400VAC Delta Wiring (D)<br />
Pn<br />
19kW<br />
Max Power of the Motor<br />
@230VAC Delta Wiring (D)<br />
Pn<br />
11kW<br />
Nom.<br />
Operating Voltage<br />
Operating Voltage Range<br />
Max.<br />
Non-repetitive Peak Voltage<br />
Integrated Overvoltage Protection<br />
Ven<br />
Ve<br />
Vep<br />
230Vac & 400Vac<br />
200-480Vac<br />
1200V<br />
Yes<br />
510V size 14 varistors<br />
Remarks<br />
Device wired inside<br />
the delta<br />
Device wired inside<br />
the delta<br />
See Fig. 16 & 17<br />
AC53a Nom. Current according to Ie<br />
Hard conditions<br />
15.5A<br />
EN60947-4-2 (Induction Motor) (AC53a)<br />
See Fig. 15<br />
AC53a Max. Permanent Current Ie<br />
Normal conditions<br />
22A<br />
(Induction Motor)<br />
(AC53a)<br />
See Fig. 15<br />
Max. AC1 Permanent Current<br />
(Resistive Loads)<br />
Ith (AC1)<br />
25A<br />
e.g. softstarting lamps<br />
Non-repetitive Peak Overload<br />
Current (1 cycle of 10ms)<br />
ITSM<br />
1500A<br />
See Fig. 14<br />
Fusing Limit Current for Choosing<br />
the Protecting Fuses<br />
I 2 t<br />
11000A<br />
2<br />
s @10ms<br />
Min.<br />
Load Current<br />
Iemin<br />
100mA<br />
Max.<br />
Leakage Current<br />
I1k<br />
7mA<br />
@400Vac 50Hz<br />
Power<br />
Factor<br />
Pf<br />
0-1<br />
Operating Mains Frequency Range F 40-65Hz<br />
Off-state<br />
dv/dt<br />
d v/dt<br />
500V/<br />
µs<br />
Integrated Transient Voltage<br />
Protection<br />
Max.<br />
Current Rising Time<br />
Direct<br />
Voltage Drop<br />
Resistive Part<br />
of the Direct Voltage Drop<br />
Threshold Part<br />
of the Direct Voltage Drop<br />
Max.<br />
Junction Temperature<br />
Junction/Plate Thermal Resistance<br />
Per Power Element<br />
Plate/Heatsink<br />
Thermal Resistance<br />
Vertically Mounted Heatsink<br />
Thermal Resistance<br />
Heatsink<br />
Thermal Time Constant<br />
d i/dt<br />
/<br />
Vd<br />
rt<br />
Vto<br />
Tjmax<br />
Rthjc<br />
Rthcs<br />
Rthra<br />
Tthra<br />
Yes<br />
RC network<br />
50A<br />
µs<br />
1.4V<br />
@Ith<br />
3.5mΩ @125° C<br />
0.9V<br />
@125° C<br />
125° C<br />
0.3° K/ W<br />
0.05° K/ W<br />
Total = 3 power<br />
elements<br />
0 .9° K/ W<br />
@∆Tra=60°<br />
C<br />
35min<br />
@∆Tra=60°<br />
C<br />
EMC48S50-03 6 SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE © 2003 TELEDYNE RELAYS<br />
EMC48S50-03\032003\Q1