Chapter 1<br />
Safety Integrity Level (SIL) Concept<br />
Introduction<br />
This chapter introduces you to the Safety Integrity Level (SIL) concept<br />
and how the <strong>GuardLogix</strong> controller meets the requirements for SIL 3<br />
certification.<br />
Topic<br />
Page<br />
SIL 3 Certification 13<br />
Functional Verification Tests 14<br />
<strong>GuardLogix</strong> Architecture for SIL 3 Applications 15<br />
<strong>GuardLogix</strong> System Components 16<br />
<strong>GuardLogix</strong> Certifications 18<br />
<strong>GuardLogix</strong> PFD and PFH Specifications 19<br />
Safety Integrity Level (SIL) Compliance Distribution and Weight 20<br />
System Reaction Time 21<br />
Safety Task Period and Safety Task Watchdog 21<br />
Contact Information If Device Failure Occurs 22<br />
SIL 3 Certification<br />
<strong>1756</strong> and 1768 <strong>GuardLogix</strong> controller systems are type-approved and<br />
certified for use in safety applications up to and including SIL 3<br />
according to IEC 61508 and IEC 62061, safety applications up to and<br />
including Performance Level PLe (Category 4) according to<br />
ISO 13849-1. SIL requirements are based on the standards current at<br />
the time of certification.<br />
IMPORTANT<br />
When the <strong>GuardLogix</strong> controller is in the Run or Programming<br />
mode and the application has not been validated by the user,<br />
the user is responsible for maintaining safe conditions.<br />
In addition, the standard tasks within <strong>1756</strong> <strong>GuardLogix</strong> controllers can<br />
be used either for standard applications or SIL 2 safety applications as<br />
described in the Using ControlLogix in SIL 2 Applications Reference<br />
Manual, publication <strong>1756</strong>-RM001. In either case, do not use SIL 2 or<br />
standard tasks and variables to build up safety loops of a higher level.<br />
The safety task is the only task certified for SIL 3 applications.<br />
The standard task in 1768 Compact <strong>GuardLogix</strong> controllers may not be<br />
used for SIL 2 safety applications.<br />
RSLogix 5000 programming software is required to create programs<br />
for <strong>1756</strong> and 1768 <strong>GuardLogix</strong> controllers.<br />
13Publication <strong>1756</strong>-<strong>RM093F</strong>-<strong>EN</strong>-P - January 2010 13