Chapter 4<br />
CIP Safety and the Safety Network Number<br />
Considerations for<br />
Assigning the Safety<br />
Network Number (SNN)<br />
The assignment of the SNN is dependent upon factors including the<br />
configuration of the controller or CIP Safety I/O module.<br />
Safety Network Number (SNN) for Safety Consumed Tags<br />
When a safety controller that contains produced safety tags is added<br />
to the I/O Configuration tree, the SNN of the producing controller<br />
must be entered. The SNN may be copied from the producing<br />
controller’s project and pasted into the new controller being added to<br />
the I/O Configuration tree.<br />
Refer to the <strong>GuardLogix</strong> <strong>Controller</strong>s User Manual, publication<br />
<strong>1756</strong>-UM020, or the 1768 Compact <strong>GuardLogix</strong> <strong>Controller</strong>s User<br />
Manual, publication 1768-UM002, for information on how to copy and<br />
paste an SNN.<br />
Safety Network Number (SNN) for Out-of-box Modules<br />
Out-of-box CIP Safety I/O modules do not have an SNN. The SNN is<br />
set when a configuration is sent to the module by the <strong>GuardLogix</strong><br />
controller that owns the module.<br />
IMPORTANT<br />
To add a CIP Safety I/O module to a configured <strong>GuardLogix</strong><br />
system (the SNN is present in the <strong>GuardLogix</strong> controller), the<br />
replacement CIP Safety module should have the correct SNN<br />
applied before it is added to the CIP Safety network.<br />
Safety Network Number (SNN) for Safety Module with a Different<br />
Configuration Owner<br />
When a CIP Safety I/O module is owned by a different <strong>GuardLogix</strong><br />
controller (controller B), and then is added to another <strong>GuardLogix</strong><br />
project (controller A project), RSLogix 5000 software assigns the SNN<br />
based on the current project. Since the current project (controller A<br />
project) is not the true configuration owner, you need to copy the<br />
original SNN (controller B project) into the configuration in controller<br />
A’s project. This is easy to do with standard copy and paste<br />
<strong>com</strong>mands. The result is that the CIP Safety I/O module produces data<br />
to two <strong>GuardLogix</strong> controllers at the same time. You can do this for a<br />
maximum of 16 controllers.<br />
38 Publication <strong>1756</strong>-<strong>RM093F</strong>-<strong>EN</strong>-P - January 2010