Chapter 3<br />

CIP Safety I/O for the <strong>GuardLogix</strong> Control System<br />

Diagnostics<br />

CIP Safety I/O modules perform self-diagnostics when the power is<br />

turned ON and periodically during operation. If a diagnostic failure is<br />

detected, safety input data (to the controller) and local safety outputs<br />

are set to their safe state (OFF).<br />

Status Data<br />

In addition to safety input and output data, CIP Safety I/O modules<br />

support status data to monitor module and I/O circuit health. Refer to<br />

your module’s product documentation for specific product<br />

capabilities.<br />

Status Indicators<br />

The CIP Safety I/O modules include status indicators. For details on<br />

status indicator operation, refer to the product documentation for your<br />

specific module.<br />

On- or Off-delay Function<br />

Some CIP Safety I/O modules may support On-delay and Off-delay<br />

functions for input signals. Depending upon your application, you<br />

may need to include Off-delay, On-delay, or both when calculating<br />

system reaction time.<br />

See Appendix C for information on system reaction time.<br />

30 Publication <strong>1756</strong>-<strong>RM093F</strong>-<strong>EN</strong>-P - January 2010