. Ensure timer <strong>and</strong> photocell are operating <strong>and</strong> set correctly; repair/replace as<br />
needed, IAW operation manual.<br />
M2. Faucets/General Plumbing<br />
a. Inspect all faucets for proper operation - adjust or replace as needed.<br />
b. Adjust faucet h<strong>and</strong>les for proper alignment.<br />
c. Inspect flush valves — adjust or repair as needed.<br />
M3. Elevators ("tasks to be completed by ThyssenKrupp with maintenance contractor<br />
overview')<br />
air *> Provide escort as needed for <strong>TRACON</strong> passenger <strong>and</strong> freight elevator, <strong>and</strong> TOC<br />
passenger <strong>and</strong> freight elevator.<br />
M4. Roof <strong>and</strong> Caulking<br />
a. Inspect roof for tears in membrane, even distribution of ballast, proper roof <strong>and</strong><br />
gutter drainage, exterior caulking in need of repair, <strong>and</strong> security of flashing <strong>and</strong><br />
roof components; repair as necessary.<br />
M5. Flag Pole<br />
a. Inspect halyard, turnbuckle, <strong>and</strong> pole. Repair, replace, or repaint as needed.<br />
M6. Guard Shack<br />
a. Inspect guard shack systems (electrical, plumbing, doors, <strong>and</strong> structure) for proper<br />
operation <strong>and</strong> repair or replace as needed. Complete exterior/interior painting as<br />
needed.<br />
M7. Refrigeration Equipment (dining room refrigerator <strong>and</strong> icemaker)<br />
a. Clean dust <strong>and</strong> dirt from condenser fins.<br />
b. Clean door gaskets.<br />
c. Check <strong>and</strong> tighten all electrical connections.<br />
d. Ensure unit refrigerant is correct - add as needed.<br />
e. Check actual vs. set temperature - adjust as needed.<br />
f. Check <strong>and</strong> clean condensate drains.<br />
g. Check <strong>and</strong> record amperage of unit.<br />
h. Check <strong>and</strong> record evap temperature both in <strong>and</strong> out <strong>and</strong> ambient temperature,<br />
i. Clean around unit.<br />
M8. Carpet Tiles<br />
a. Replace damaged, worn, or soiled carpet tiles as requested by the COR.<br />
Mil. Insect Control<br />
a. Perform escort as needed.<br />
M12. Central Vacuum System<br />
a. Test operation of unit<br />
b. Inspect dirt collection bags for tears, rips, <strong>and</strong> functionality. Repair, replace, clean as<br />
needed.<br />
c. Ensure vacuum suction pressure is 4.0 HG<br />
d. Check <strong>and</strong> record motor amperage against manufacture data.