Function Code List (cont.)<br />

Heating<br />

Auto Curve<br />

Settings<br />

Frost Protection<br />

Back Up Heater<br />

Control<br />

Night Setback<br />

Function<br />

Function Code Number<br />

Hydro Unit<br />

Quick Reference Guide - Page 25<br />

Remote<br />

Controller<br />

Range<br />

Default<br />

Outside temperature T1 °C 29 - -15 ~ 0 -10<br />

Outside temperature T2 °C - - 0 0<br />

Outside air temperature T3 °C 2B - 0 ~ 15 10<br />

Setting temperature A at -20 °C 2C - 20 ~ 55 40<br />

Setting temperature B at T1°C 2D - 20 ~ 55 35<br />

Setting temperature C at T2°C 2E - 20 ~ 55 30<br />

Setting temperature D at T3°C 2F - 20 ~ 55 25<br />

Setting temperature E at +20°C 30 - 20 ~ 55 20<br />

Ratio of Zone 2 in Zone 1 Auto mode (%) 31 - 0 ~ 100 80<br />

Temperature shift of entire Auto curve (°C) 27 - -5 ~ 5 0<br />

Function 0 = Valid; 1 = Invalid 3A - 0 ~ 1 1<br />

Setting temperature °C 3B - 8 ~ 20 15<br />

Back up heater downtime. 0=5min; 1=10min;<br />

2=15min; 3=20min<br />

Back up heater uptime. 0=10min; 1=20min;<br />

2=30min; 3=40min<br />

Zone Selection: 0=Zones 1 and Zone 2;<br />

1=Zone 1 Only<br />

33 - 0 ~ 3 1<br />

34 - 0 ~ 3 0<br />

58 - 0 ~ 1 0<br />

Change Setback temperature °C 26 - 3 ~ 20<br />

5<br />

Start time (hour) - 0E 0 ~ 23 22<br />

End time (hour) - 0F 0 ~ 23 06<br />

Room temperature control adjustment. 0=Valid;<br />

1=Invalid<br />

- 02 0 ~ 1 0<br />

Compensation for temperature °C 35 - 1 ~ 5 1<br />

Room Temperature<br />

Setting<br />

1 ~ 24<br />

Downtime Zone B (x 5min) 36 -<br />

6<br />

(5 ~ 120mins)<br />

Uptime Zone C (x5min) 37 -<br />

1 ~ 24<br />

(5 ~ 120mins)<br />

6<br />

2 Way Valve<br />

Operation Control<br />

3 Way valve<br />

Operation Control<br />

2 way valve activation for cooling.<br />

0=activated during cooling;<br />

1=not activated during cooling<br />

3 way valve activation.<br />

0=activated during hot water operation;<br />

1=not activated during hot water operation<br />

3C - 0 ~ 1 0<br />

54 - 0 ~ 1 0<br />

2 Zone Mixing<br />

V alve Drive Time<br />

Boiler & Heat<br />

Pump<br />

Synchronisation<br />

Specified Drive Time for Mixing Valve to 90°<br />

open (x 10 sec)<br />

Boiler synchronisation with heat pump.<br />

0=synchronised; 1=not synchronised<br />

Maximum<br />

Ope ration Time of Maximum heat pump operation time in hot<br />

Hot Water Heat water operation priority mode (minutes)<br />

Pump<br />

0C - 3 ~ 24 6<br />

3E - 0 ~ 1 0<br />

07 - 1 ~ 120 30<br />

Cooling Operation<br />

Activate cooling mode.<br />

0=cooling & heating mode; 02 - 0 ~ 1 1<br />

1=heating mode only