Function Code List (cont.)<br />
Heating<br />
Auto Curve<br />
Settings<br />
Frost Protection<br />
Back Up Heater<br />
Control<br />
Night Setback<br />
Function<br />
Function Code Number<br />
Hydro Unit<br />
Quick Reference Guide - Page 25<br />
Remote<br />
Controller<br />
Range<br />
Default<br />
Outside temperature T1 °C 29 - -15 ~ 0 -10<br />
Outside temperature T2 °C - - 0 0<br />
Outside air temperature T3 °C 2B - 0 ~ 15 10<br />
Setting temperature A at -20 °C 2C - 20 ~ 55 40<br />
Setting temperature B at T1°C 2D - 20 ~ 55 35<br />
Setting temperature C at T2°C 2E - 20 ~ 55 30<br />
Setting temperature D at T3°C 2F - 20 ~ 55 25<br />
Setting temperature E at +20°C 30 - 20 ~ 55 20<br />
Ratio of Zone 2 in Zone 1 Auto mode (%) 31 - 0 ~ 100 80<br />
Temperature shift of entire Auto curve (°C) 27 - -5 ~ 5 0<br />
Function 0 = Valid; 1 = Invalid 3A - 0 ~ 1 1<br />
Setting temperature °C 3B - 8 ~ 20 15<br />
Back up heater downtime. 0=5min; 1=10min;<br />
2=15min; 3=20min<br />
Back up heater uptime. 0=10min; 1=20min;<br />
2=30min; 3=40min<br />
Zone Selection: 0=Zones 1 and Zone 2;<br />
1=Zone 1 Only<br />
33 - 0 ~ 3 1<br />
34 - 0 ~ 3 0<br />
58 - 0 ~ 1 0<br />
Change Setback temperature °C 26 - 3 ~ 20<br />
5<br />
Start time (hour) - 0E 0 ~ 23 22<br />
End time (hour) - 0F 0 ~ 23 06<br />
Room temperature control adjustment. 0=Valid;<br />
1=Invalid<br />
- 02 0 ~ 1 0<br />
Compensation for temperature °C 35 - 1 ~ 5 1<br />
Room Temperature<br />
Setting<br />
1 ~ 24<br />
Downtime Zone B (x 5min) 36 -<br />
6<br />
(5 ~ 120mins)<br />
Uptime Zone C (x5min) 37 -<br />
1 ~ 24<br />
(5 ~ 120mins)<br />
6<br />
2 Way Valve<br />
Operation Control<br />
3 Way valve<br />
Operation Control<br />
2 way valve activation for cooling.<br />
0=activated during cooling;<br />
1=not activated during cooling<br />
3 way valve activation.<br />
0=activated during hot water operation;<br />
1=not activated during hot water operation<br />
3C - 0 ~ 1 0<br />
54 - 0 ~ 1 0<br />
2 Zone Mixing<br />
V alve Drive Time<br />
Boiler & Heat<br />
Pump<br />
Synchronisation<br />
Specified Drive Time for Mixing Valve to 90°<br />
open (x 10 sec)<br />
Boiler synchronisation with heat pump.<br />
0=synchronised; 1=not synchronised<br />
Maximum<br />
Ope ration Time of Maximum heat pump operation time in hot<br />
Hot Water Heat water operation priority mode (minutes)<br />
Pump<br />
0C - 3 ~ 24 6<br />
3E - 0 ~ 1 0<br />
07 - 1 ~ 120 30<br />
Cooling Operation<br />
Activate cooling mode.<br />
0=cooling & heating mode; 02 - 0 ~ 1 1<br />
1=heating mode only