Valves<br />
Valves with Thermoelectric Actuators (230 V~)<br />
<strong>GEA</strong> <strong>Elite</strong>-<strong>Geko</strong><br />
Thermoelectric valve actuators<br />
– Plastic actuator casing<br />
Technical data:<br />
Function type<br />
T<br />
Control type<br />
2-point (modulating)<br />
Operating voltage<br />
230 V AC<br />
50/60 Hz<br />
Power consumption [W] 3<br />
Heat up current [A] 0.6<br />
Rated current [A] 0.014<br />
Type of protection<br />
IP44<br />
Run time (approx.) [min] 2.5<br />
Operating force [N]<br />
90 N<br />
Control stroke [mm] 4<br />
Max. allowed ambient temp. 50 °C<br />
Connecting cable [m] 1<br />
Fig. 25<br />
Two and three way valves<br />
– Brass or red brass valve body<br />
– Stainless steel spindle and cone<br />
Technical data:<br />
Rated pressure<br />
16 bar<br />
max. medium temperature 120 °C<br />
max. glycol concentration 50 %<br />
Rated dimensions<br />
[mm]<br />
Stroke 2,5<br />
mm<br />
a b c d e<br />
G 1/2" A<br />
G 3/4" A<br />
56<br />
66<br />
40<br />
40<br />
34.5<br />
36.6<br />
5<br />
5<br />
Fig. 26<br />
The regulation valves are mounted by others on site,<br />
i.e. with piping and wired.<br />
Three valve valves:<br />
DN<br />
k VS A-AB<br />
[m 3 /h]<br />
k VS B-AB<br />
[m 3 /h]<br />
Valve external<br />
thread<br />
Dp max<br />
[kPa]<br />
Order-Nr.<br />
15 1.6 1.0 G 1/2" A 200 VGE.T316.0#<br />
20 4.0 2.5 G 3/4" A 100 VGE.T340.0#<br />
Pressure drop Δp [kPa]<br />
Fig. 27<br />
•<br />
Water flow rate V [l/h]<br />
Two valve valves:<br />
DN<br />
k VS A-AB<br />
[m 3 /h]<br />
Valve external<br />
thread<br />
Dp max<br />
[kPa]<br />
Order-Nr.<br />
15 1.6 G 1/2" A 300 VGE.T216.0#<br />
20 4.0 G 3/4" A 100 VGE.T240.0#<br />
With mounted valves for a 4-pipe system the order<br />
number must be specified with k vs value and number of<br />
ways of heating valve, e.g. VGE.T340T216.0# (see<br />
Product Type Code on page 23).<br />
The symbol "#" is reserved for medium connection left<br />
(L) or right (R).<br />
Note: The max. pressure drop in heat exchanger with<br />
fully open valve should not exceed 25 kPa in cooling<br />
mode and 20 kPa in heating mode.<br />
22 PR-2009-0103-GB • Subject to modifications • Status 08/2009