OVL1<br />

Automatic (AUTO): The contact of checkback B1-B2 is closed. The output relay R switches into on-position (yellow LED illuminated) when<br />

the signal voltage applied at the terminals YR-A2 exceeds the the value adjusted at the regulator. The output relay switches into off-position<br />

(yellow LED not illuminated) when the signal voltage falls below the set value by more than the fixed hysteresis.<br />

Permanently OFF (0): The contact of checkback B1-B2 is opened. The output relay R remains in off-position (yellow LED not illuminated)<br />

independent from the connected signal voltage.<br />

Permanently ON (HAND): The contact of checkback B1-B2 is opened. When the supply voltage U is applied at terminal A1 the output<br />

relay R switches into on-position (yellow LED illuminated). Changes of the signal voltage do not influence the state of the output relay.<br />

OCL1<br />

Automatic (AUTO): The contact of checkback B1-B2 is closed. The output relay R switches into on-position (yellow LED illuminated) when<br />

the signal voltage applied at the terminals YR-A2 exceeds the the value adjusted at the regulator. The output relay switches into off-position<br />

(yellow LED not illuminated) when the signal voltage falls below the set value by more than the fixed hysteresis.<br />

Permanently OFF (0): The contact of checkback B1-B2 is opened. The output relay R remains in off-position (yellow LED not illuminated)<br />

independent from the connected signal voltage.<br />

Permanently ON (HAND): The contact of checkback B1-B2 is opened. When the supply voltage U is applied at terminal A1 the output<br />

relay R switches into on-position (yellow LED illuminated). Changes of the signal voltage do not influence the state of the output relay.<br />

Functions<br />

Diode gate Series TREND<br />

Array with ‚or‘ function<br />

< Diode gate with 10 inputs and one output<br />

< Combined alarm signal<br />

< Width 22,5mm<br />

< Plug-in mounting<br />

OVL1 OCL1 Connections<br />

24V<br />

0V<br />

0-10V<br />

24V<br />

0V<br />

0-20mA<br />

Type TD1 TD2<br />

A1<br />

A2<br />

A1<br />

A2<br />

B1<br />

B2<br />

B1<br />

B2<br />

11<br />

11<br />

12 14<br />

12 14<br />

11<br />

12<br />

YR<br />

14<br />

11<br />

12<br />

YR<br />

14<br />

Art.No. (PQ1) 2490000 2490001<br />

Art.No. (PQ10) - -<br />

EAN13-Code 9008662005846 9008662005853<br />

Width 17,5mm<br />

Dimensions<br />

Controls - -<br />

Indicators (LEDs) - -<br />

Functions logical function ‚OR‘ logical function ‚OR‘<br />

Inputs semiconductor elements: pins 2 to 11<br />

10 diodes (types 1N4007)<br />

anode is common<br />

peak voltage: 1000V<br />

forward voltage: approx. 0,8V<br />

forward current per diode: 0,7A (single channel)<br />

forward current per diode: 0,1A (all channels)<br />

semiconductor elements: pins 2 to 11<br />

10 diodes (types 1N4007)<br />

cathode is common<br />

peak voltage: 1000V<br />

forward voltage: approx. 0,8V<br />

forward current per diode: 0,7A (single channel)<br />

forward current per diode: 0,1A (all channels)<br />

Supply - -<br />

Output semiconductor element: pins 1<br />

1 diodes (types 1N4007)<br />

peak voltage: 1000V<br />

forward voltage: approx. 0,8V<br />

forward current: max. 1A<br />

semiconductor element: pins 1<br />

1 diodes (types 1N4007)<br />

peak voltage: 1000V<br />

forward voltage: approx. 0,8V<br />

forward current: max. 1A<br />

Width 22,5mm 22,5mm<br />

Certificates CE • GOST CE • GOST<br />

Mechanical<br />

design<br />

Ambient<br />

conditions<br />

Accessories<br />

Self-extinguishing plastic housing, IP rating IP40 • Connection and mounting by 11-pin socket in accordance with IEC 60067-1-18a (types<br />

R11X or ES12) • Mounting position any<br />

Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1) • Storage temperature: -25 to +70°C • Transport temperature: -25 to<br />

+70°C • relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree: 3 (in accordance with IEC 60664-1)<br />

Plug-in socket R11X or ES12<br />

Page 232 www.tele-online.com<br />

Page 233